Lg multi vrf iii mfl61741607 multi v network solution 10

Page 28

2. Central Control Devices 2.2.6 Indoor unit Address setting ■ Using wired remote controller •PQRCVSL0 / PQRCVSL0QW It's the function to use for connecting central control. Please refer to central controller manual for the details

1. Press the Function Setting button for 4 seconds to enter the installer setting mode until timer segment displays "01:01". 2. Repeatedly pressing Function Setting button to select function code 02 Ex) Setting Address as 'F5'

Indoor No. Function Code Group No

3. Set Group No. by pressing Up/Down button.(0~F) 4. Move to Indoor No. setting option by pressing Right button. 5. Set Indoor No. by pressing Up/Down button. 1, 2

3, 4, 5

7

6

6. Press OK/CLEAR button to save. 7. Press ESC button to exit or system will automatically exit after 25 seconds ❈ When exiting without pressing set button, the manipulated value is not reflected.

Network Solution Network Solution _ 25