Lg ceiling cassette(50hz,r22) korea

Page 74

11. The Coefficient of Capacity Change Model No.: LT-C18(24)6FLA(E)0, LT-C286FLA(E/F)0

Capacity(%)

100 Heating(18k) Cooling(18k), Heating(24k) Heating(28k) Cooling(24k) Cooling(28k)

90

80

70 7.5

10

20

30

Total Pipe Length(m)

40

Model

Additional Refrigerant

18k

25 g/m

24k

30 g/m

28k

40 g/m

Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model.