Daikin engineering data split ,skyair ku (fhyc kve,fhy bve)

Page 98

ED21-002A

Specifications

4. Specifications 4.1

FHYC

4.1.1

Twin

FHYC (Ceiling Mounted Cassette Type) - Twin Model

Indoor Unit Outdoor Unit

∗1 Cooling Capacity (1)/(2)/(3)

∗1 Heating Capacity (1)/(2)/(3)

Indoor Unit ∗5 Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Decoration Model Panel Color (Option) Dimensions (H×W×D) Air Filter Weight Outdoor Unit Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate (C/H) ∗2 kg Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref. Max. Length Piping Max. Height Difference Refrigerant Model Charge Ref. Oil Model Charge Drawing No.

Notes:

1.

FHYC50KVE×2 FHYC60KVE×2 RY100KUV1 — RY100KUY1 RY125KUY1 10.5/10.4/10.4 13.0/12.8/12.8 35,700/35,300/35,300 44,500/43,600/43,600 9,000/8,900/8,900 11,200/11,000/11,000 11.2/11.2/11.2 14.2/14.2/14.2 38,100/38,100/38,100 48,400/48,400/48,400 9,600/9,600//9,600 12,200/12,200/12,200 FHYC50KVE×2 FHYC60KVE×2 mm 230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)14–16 (L)10–12 (H)15–17 (L)11–13 (H)19–21 (L)14–16 kg 24 mm φ6.4 (Flare) mm φ12.7 (Flare) φ15.9 (Flare) mm I.Dφ25×O.Dφ32 BRC1C61 (Note. 6) BRC7C612W BYC125K–W1×2 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 V1 RY71KUV1 RY100KUV1 — Y1 RY71KUY1 RY100KUY1 RY125KUY1 Ivory mm 816×880×370 1,215×880×370 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×36×2.0 2×54×2.0 m² 0.653 0.979 V1 JT95BC–V1 JT125BC–V1 — Y1 JT95BC–YE JT125BC–YE JT160BC–YE Hermetically Sealed Scroll Type kW 2.2 3.0 3.75 P45J11SM P45J11SM×2 Propeller W 60 70+55 m³/min. 46/41–48/43 87/78–89/80 V1 83 108 — Y1 80 105 106 mm φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Expansion Valve (Electronic Type) m 50 (Equivalent Length 70m) m 30 R22 kg 3.0 (Charged for 30m) 3.4 (Charged for 30m) 3.7 (Charged for 30m) SUNISO 4GSDID–K L 1.2 1.5 4D015035B

∗1 Nominal capacities are based on the following conditions.

Mark

Cooling

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

Indoor : 21°CDB Outdoor : 7°CDB, 6°CWB

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

Indoor : 20°CDB Outdoor : 7°CDB, 6°CWB

2. 3. 4. 5. 6.

2

FHYC35KVE×2 RY71KUV1 RY71KUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 7.9/7.9/7.9 27,000/27,000/27,000 6,800/6,800/6,800 FHYC35KVE×2

V1 Y1 kW Btu/h kcal/h kW Btu/h kcal/h

Heating

Conversion Formulae Piping length

Hz–Volts

Standard

5m

50Hz–220V (V1) 50Hz–380V (Y1)

5m

50Hz–220V (V1) 50Hz–380V (Y1)

JIS B8616

Indoor : 27°CDB, 19.0°CWB Indoor : 21°CDB 50Hz–240V (V1) (3) 7.5m Outdoor : 35°CDB, 24°CWB Outdoor : 7°CDB, 6°CWB 50Hz–415V (Y1) ∗2 AFR (Air flow rate) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. ∗5 Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir KU Series – Heat Pump –

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

AS 1861

93