Specifications
ED21-301
FHY (Ceiling Suspended Type) <60Hz> Model
Indoor Units Outdoor Units
∗1 Cooling Capacity (1)/(2)
Indoor Unit Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units
Color Dimensions Coil
Comp.
Fan
Weight Piping Connections
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHY71BVE R71LUVAL — — 8.3/8.1 28,200/27,800 7,100/7,000 FHY71BVE
FHY100BVE FHY125BVE R100LUVAL — — R125LUTAL — R125LUYAL 11.6/11.4 14.5/14.3 39,700/38,900 49,600/48,800 10,000/9,800 12,500/12,300 FHY100BVE FHY125BVE White mm 195×1,160×680 195×1,400×680 195×1,590×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.233 0.293 0.341 4D12K1AA1 3D12K2AA1 4D12K2AA1 Sirocco Fan W 62 130 m³/min. (H)17 (L)14 (H)24 (L)20 (H)30 (L)25 Resin Net (with Mold Resistant) 32 35 kg 27 mm φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ20×O. Dφ26 BRC1C61 (Note. 4) BRC7E66 VAL R71LUVAL R100LUVAL — TAL — — R125LUTAL YAL — — R125LUYAL Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT160BC YAL — JT160BC–YH Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 P47L11S P47L11S×2 Propeller W 75 100 95+75 m³/min. 49 59 94 kg 75 92 98 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch. Over Current Device. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100-0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h
SONTEX 200LT 1.2
L
SUNISO 4GSDID–K 1.5 4D039110
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m (Horizontal)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m (Horizontal)
JIS B8616
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
2. Capacities are net, including a deduction for cooling for indoor fan motor heat. 3. Each value for indoor unit shows the specification per one unit. 4. Wire for remote controller : Field supplied.
24
SkyAir LU Series – Cooling Only –