Daikin engineering data sky air (cooling only) LU

Page 27

Specifications

ED21-301

FHYC (Ceiling Mounted Cassette Type) <60Hz> Model

Indoor Units Outdoor Units

∗1 Cooling Capacity (1)/(2)

Indoor Unit Dimensions Coil

Fan

H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level

Weight Piping Connections

Liquid Gas Drain Remote Controller (Option)

Decoration Panel (Option)

Wired Wireless

Model Color Dimensions (H×W×D) Air Filter Weight

Outdoor Units

Color Dimensions Coil

Comp.

Fan

Weight Piping Connections

H×W×D Type Row×Stages×Fin Pitch Face Area Model

Type Motor Output Model Type Motor Output Air Flow Rate Liquid Gas Drain

Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Note:

SONTEX 200LT 1.2

L

SUNISO 4GSDID–K 1.5 4D039107

1. ∗1 The above data based on the conditions shown in the table below. Mark

Cooling

Piping length

Standard

(1)

Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

5m

(2)

Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB

7.5m

JIS B8616

2. 3. 4. 5. 6.

22

FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE R71LUVAL R100LUVAL — — — — R125LUTAL R140LUTAL — — R125LUYAL R140LUYAL 8.3/8.1 11.6/11.4 14.5/14.3 16.1/15.8 28,200/27,800 39,700/38,900 49,600/48,800 55,000/53,900 7,100/7,000 10,000/9,800 12,500/12,300 13,800/13,500 FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE mm 230×840×840 288×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) Cross Fin Coil 2×8×1.5 2×12×1.5 m² 0.331 0.497 QTS45B14M QTS45A17M Turbo Fan W 45 90 m³/min. (H)19 (L)14 (H)28 (L)21 (H)33 (L)24 (H)35 (L)26 dB(A) — (H)44 (L)37 kg 24 28 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 6) BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 VAL R71LUVAL R100LUVAL — — TAL — — R125LUTAL R140LUTAL YAL — — R125LUYAL R140LUYAL Ivory mm 770×900×320 1,170×900×320 1,345×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 2×60×2.0 m² 0.634 0.983 1.134 VAL ZR36K3–PFV ZR47K3–PFV — TAL — JT170BC JT170BC YAL — JT170BC–YH JT170BC–YE Hermetically Sealed Scroll Type kW 2.24 2.92 3.75 4.50 P47L11S P47L11S×2 Propeller W 75 100 95+75 65+90 m³/min. 49 59 94 97–109 kg 75 92 98 112 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125·140>. Low Pressure Switch. Over Current Decive. Motor Protector (Compressor) <R71·100>. Reverse Phase Protector (TAL·YAL). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) 4.1 (Charged for 30m) VAL TAL YAL kW Btu/h kcal/h

1.6 4D040213

Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –