ED21-301
4.3
Specifications
60Hz
1
FHC (Ceiling Mounted Cassette Type) <60Hz> Model
Indoor Units Outdoor Units ∗1 Cooling Capacity (1)/(2)
Indoor Unit Dimensions Coil
Fan
kW Btu/h kcal/h
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate Sound Pressure Level
Weight Piping Connections
Liquid Gas Drain Remote Controller (Option) Decoration Panel (Option)
Wired Wireless
Model Color Dimensions (H×W×D) Air Filter Weight
Outdoor Units Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FHC50KVE R50GVAL 5.64/5.6 19,300/19,100 4,850/4,820 FHC50KVE
FHC60KVE R60GVAL 6.84/6.8 23,400/23,200 5,880/5,850 FHC60KVE
mm
230×840×840 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×8×1.5 m² 0.331 QTS45B14M Turbo Fan W 45 m³/min. (H)15 (L)11 (H)19 (L)14 dB(A) — kg 24 φ6.4 (Flare) mm φ15.9 (Flare) mm mm I. Dφ25×O. Dφ32 BRC1C61 (Note. 5, 6) BRC7C613W BYC125K–W1 White mm 40×950×950 Resin Net (with Mold Resistant) kg 5 R50GVAL R60GVAL Ivory White mm 540×750×270 685×800×300 Cross Fin Coil (FL Fins and Hi–XA Tubes) 2×22×2.0 2×28×2.0 m² 0.372 0.465 RC60VHTNRT RC75VHTR2T Hermetically Sealed Rotary Type kW 1.5 1.8 PZ380 PZ430 Propeller W 45 53 m³/min. 30 44 kg 41 51 φ6.4 (Flare) mm φ15.9 (Flare) mm φ18.0 (Hole) mm Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse. % 100–0 Capillary Tube m 30 m 15 R22 kg 1.15 (Charged for 10m) 1.60 (Charged for 5m) SUNISO 4GS–DI L
0.85
1.00 4D006550B
1. ∗1 The above data based on the conditions shown in the table below. Mark
Cooling
Piping length
(1)
Indoor : 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
5m
(2)
Indoor : 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor : 35°C(95°F)DB, 24°C(75°F)WB
5m
2. 3. 4. 5. 6.
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. Each value shows the specification per one unit. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
21