ED21-301
Specifications
1
FAY (Wall Mounted Type) <50Hz> Model
Indoor Units Outdoor Units
V1 Y1 kW Btu/h kcal/h
∗1 Cooling Capacity (1)/(2)/(3)
Indoor Units Color Dimensions Coil
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Air Flow Rate ∗2
Air Filter Weight Piping Connections
Liquid Gas Drain Remote Controller (Option)
Wired Wireless
Outdoor Units Color Dimensions Coil
Comp.
Fan
H×W×D Type Row×Stages×Fin Pitch Face Area Model Type Motor Output Model Type Motor Output Air Flow Rate
Weight Piping Connections
∗2 kg
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Ref.Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.
Note:
FAY71LVE R71LUV1 R71LUY1 7.8/7.7/7.7 26,600/26,200/26,200 6,700/6,600/6,600 FAY71LVE
FAY100FAVE R100LUV1 R100LUY1 10.6/10.5/10.5 36,100/35,700/35,700 9,100/9,000/9,000 FAY100FAVE
White 290×1,050×230 360×1,570×200 Cross Fin Coil (Multi Louver Fins and Hi–XA Tubes) 2×16×1.4 2×12×1.4 m² 0.289 0.332 QCL9686M QCL1163MA+QCL1163MB Cross Flow Fan W 43 46 m³/min. (H) 19–19 (L) 15–15 (H) 23–23 (L) 19–19 Resin Net (with Mold Resistant) kg 13 26 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm I. Dφ20×O. Dφ26 mm I. Dφ13×O. Dφ18 BRC1C61 (Note. 5, 6) BRC7E619 BRC7C611W V1 R71LUV1 R100LUV1 Y1 R71LUY1 R100LUY1 Ivory mm 770×900×320 1,170×900×320 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×34×2.0 2×52×2.0 m² 0.634 0.983 V1 ZR36K3–PFJ ZR48K3–PFJ Y1 ZR36K3–TFD ZR48K3–TFD Hermetically Sealed Scroll Type kW 2.24 3.00 P47L11S Propeller W 65 90 m³/min. 48–51 59–62 V1 72 87 Y1 71 84 φ9.5 (Flare) mm φ15.9 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) mm Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor Protector (Compressor). Reverse Phase Protector (Y1). Fuse. % 100–0 Electronic Expansion Valve m 50 (Equivalent Length 70m) m 30 R22 kg 2.8 (Charged for 30m) 3.7 (Charged for 30m) SONTEX 200LT L 1.2 4D039583 4D039106 mm
1. ∗1 The above data based on the conditions shown in the table below.
Conversion Formulae
Mark
Cooling
Piping length
Hz–Volts
Standard
(1)
Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB
5m
50Hz–220V (380V)
—
(2)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–220V (380V)
JIS B8616
(3)
Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB
7.5m
50Hz–240V (415V)
AS 1861
2. 3. 4. 5. 6.
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
∗2 AFR (Air flow rafe) is shown at 220V (380V)–240V (415V). Capacities are net, including a deduction for cooling for indoor fan motor heat. In case of drain piping for outdoor unit, drain piping kit (option) is needed. BRC1B61 is also available. Wire for remote controller : Field supplied.
SkyAir LU Series – Cooling Only –
17