Daikin engineering data sky air (cooling only) LU

Page 122

ED21-301

Specifications

FHY (Ceiling Suspended Type) <50Hz> - Triple / Double Twin Model

Indoor Unit Outdoor Unit ∗1 Cooling Capacity (1)/(2)/(3)

kW Btu/h kcal/h

Indoor Unit ∗4 Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Fan Model Type Motor Output Air Flow Rate Air Filter Weight Piping Liquid Connections Gas Drain Remote Controller Wired (Option) Wireless Outdoor Unit Color Dimensions H×W×D Coil Type Row×Stages×Fin Pitch Face Area Comp. Model Type Motor Output Fan Model Type Motor Output Air Flow Rate ∗2 Weight Piping Liquid Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Ref. Piping Max. Length Max. Height Difference Refrigerant Model Charge (Factory Charge) Ref. Oil Model Charge Drawing No.

Notes:

FHY50BVE×3 R140LUY1 14.5/14.2/14.2 49,400/48,400/48,400 12,500/12,200/12,200 FHY50BVE×3

FHY71BVE×3 R200KUY1

FHY50BVE×4 R200KUY1

FHY60BVE×4 R250KUY1 27.1/26.6/26.3 92,500/90,800/89,800 23,300/22,900/22,600 FHY60BVE×4

22.5/22.2/22.0 76,800/75,800/75,100 19,400/19,100/18,900 FHY71BVE×3 FHY50BVE×4 White mm 195×960×680 195×1,160×680 195×960×680 195×1,160×680 Cross Fin Coil (Multi Louver Fins and N–hix Tubes) 3×12×1.75 m² 0.182 0.233 0.182 0.233 3D12K1AA1 4D12K1AA1 3D12K1AA1 4D12K1AA1 Sirocco Fan W 62 m³/min. (H)13 (L)10 (H)17 (L)14 (H)13 (L)10 (H)16 (L)13 Resin Net (with Mold Resistant) kg 24 27 24 26 mm φ6.4 (Flare) φ9.5 (Flare) φ6.4 (Flare) mm φ15.9 (Flare) mm I.Dφ20×O.Dφ26 BRC1C61 (Note. 5) BRC7E66 R140LUY1 R200KUY1 R200KUY1 R250KUY1 Ivory mm 1,345×900×320 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes) 2×60×2.0 2×40×2.0 2×50×2.0 m² 1.134 1.57 1.97 JT170BC–YE JT236D–P1YE JT335D–P1YE Hermetically Sealed Scroll Type kW 4.50 5.5 9.0 P47L11S×2 P52H11SM Propeller W 65+90 230+190 m³/min. 97–109 150–154 175–179 kg 109 178 202 mm φ9.5 (Flare) φ12.7(Flare) φ15.9(Flare) mm φ19.1 (Flare) φ25.4 (Flange) φ28.6 (Flange) mm φ26.0 (Hole) — Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Over Current Device. Reverse Phase Protector. Fuse. % 100–0 Electronic Expansion Valve Capillary Tube m 50 (Equivalent Length 70m) m 30 R22 kg 4.1 (Charged for 30m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID–K L 1.6 3.0 4D039101 4D028444 4D028439

1. ∗1 The above data based on the conditions shown in the table below.

Conversion Formulae

Mark

Cooling

Piping length

Hz–Volts

Standard

Model

(1)

Indoor : 27°CDB, 19.5°CWB Outdoor : 35°CDB, 24°CWB

5m

50Hz–380V

LU, KU

(2)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

KU

7.5m

(3)

Indoor : 27°CDB, 19.0°CWB Outdoor : 35°CDB, 24°CWB

7.5m

5m

50Hz–380V 50Hz–415V

JIS B8616

LU

AS 1861

LU, KU

kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3

2. ∗2 AFR (Air flow rate) is shown at 380V–415V. 3. Capacities are net, including a deduction for cooling for indoor fan motor heat. 4. ∗4 Each value for indoor unit shows the specification per one unit. 5. Wire for remote controller : Field supplied.

SkyAir LU Series – Cooling Only –

117

2