13.4 Controller wiring diagram CZ
PUMP P1
DK
L
N
L
230 V 50 Hz
COLD **
ES
N
L
HEAT
FI
OUTSIDE *
230 V 50 Hz 230 V 50 Hz
2
N
4
L
In2
N
In1
SENSORS
EE
SENSORS
Open
Close
230 V 50 Hz
Common
DE
ACTUATOR 230 V
POWER 230 V AC 50 Hz
WATER RETURN *****
WATER IN
In1/In2 ***
FR
In1
In1/In2 ***
In1/In2 **
In2
PUMP P2 ** CONTACT Ther ****
HR HU IT
*)
The outdoor temperature sensor can be connected to either the controller or to a thermostat.
**)
Connect either COLD or PUMP P2 (secondary heating/cooling circuit) to the connection terminal.
***) Select one of the inputs (heating/cooling switch, pump control signal, or immersion thermostat) and set parameter 11 – Wired Input 1 selection, or parameter 12 – Wired Input 2 Selection, accordingly. The heating/cooling option can only be used in systems without a registered wireless thermostat. ****) Optional temperature limiter connection, fitted with a cable bridgre from the factory. Remove the bridge if a temperature limiter is to be used together with PUMP P1.
LT
*****) Optional return sensor. Can only be used in systems without a registered wireless thermostat.
13.5 Reference data for sensors
LV
R eference
value for sensors
Check with an ohmmeter. The sensor must be unplugged
NL NO PL
Temperature (oC)
Resistance (Ohm)
Temperature (oC)
Resistance (Ohm)
-20
~ 94 kΩ
40
~ 5.3 kΩ
-10
~ 54 kΩ
50
~ 3.6 kΩ
0
~ 32 kΩ
60
~ 2.5 kΩ
10
~ 20 kΩ
70
~ 1.8 kΩ
20
~ 12.5 kΩ
80
~ 1.3 kΩ
30
~ 8 kΩ
PT S ensor
data
Sensor
RO RU
Outdoor temperature
CTN 10 kΩ at 25 °C (class II, IP55)
Supply water temperature
CTN 10 kΩ at 25 °C (class I, IP68, no coupling)
Return water temperature
CTN 10 kΩ at 25 °C (class I, IP68, no supply)
SE SK 96
U P O N O R S M AT R I X M O V E · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L