14.8 Holiday
O perating
When away on holiday, the system can be programmed in advance to reduce the system energy need by adjusting the setpoint while away. Set Enable Holiday mode to Yes to enable holiday mode during the set period. The holiday mode icon is displayed on the home screen during the set period. Cancel Holiday mode by entering the Holiday menu again and press Yes, when asked Cancel Holiday mode? This menu is not available when the system is in cooling mode.
S tart
CZ
Select how the system decides how to switch between heating and cooling.
DE
H/C Master lets the user (forced start) or the system (external sensor input) decide when to switch between heating and cooling. H/C Slave switch between heating and cooling with an external input signal (on/ off) connected to either the controller or a thermostat. A settings icon ( ) appears if choosing H/C Master.
DK EE
H/C Master:
ES
Default: Force Heating Setting range: Force Cooling, Force Heating, H/C Sensor
date
Default: Current time and date
Set a start date and time for the holiday.
E nd
mode
Default: H/C Slave Setting range: H/C Master, H/C Slave (H/C input)
date
Default: 24 hours later than set start date
Select to either force the system into cooling or heating, or to switch between cooling and heating with the help of an external sensor measuring the supply temperature.
FI
H/C Sensor:
FR
Set end date and time for the holiday.
Switch limit, default: 18.0 ˚C Switch limit, Setting range: 5.0 – 30.0 ˚C, 0.5 ˚C increments
H oliday
Hysteresis, default: 4.0 ˚C Hysteresis, Setting range: 1.0 – 10.0 ˚C, 0.5 ˚C increments
setpoint
Default: 17.0 ˚C Setting range: 5.0 – 35.0 ˚C, 0.5 ˚C increments
HR
Set an indoor temperature setpoint to be used during the holiday period.
Set the limit and hysteresis at which supply temperature the system decides when to switch between heating and cooling.
HU
E nable H oliday
14.10 Integration
IT
mode
Default: No Setting range: Yes, No
Select Yes and confirm to enable holiday mode during the set period.
14.9 Heating/Cooling
This menu manages settings when integrating the system with other devices.
C ontroller
relay
Default: Common pump (Base PRO), Individual pump (Base) Setting range: Common pump, Individual pump
In this menu, settings regarding switching between heating and cooling are made.
Set controller relay mode. This menu is only shown if several controllers are registered to the interface.
First select if cooling is available in the system. When answering Yes a settings menu appears. In the settings menu ( ) Cooling offset and Operating mode can be set.
Individual pump:
C ooling
offset
LT LV NL NO
Relay status is set on a controller basis. One pump per controller is connected. If there a demand in one room of the controllers, only the pump connected to that controller is started.
PL
Default: 2.0 ˚C Setting range: 0.0 – 5.0 ˚C, 0.5 ˚C increments
PT
Set the offset temperature for when to start cooling. This value will be added to the current setpoint temperature (setpoint + cooling offset) if cooling is activated.
RO
Cooling will start when the temperature in the room reaches setpoint + cooling offset.
RU SE SK
U P O N O R S M AT R I X B A S E / B A S E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L