Uponor iom smatrix base pro 1068124

Page 78

UK R oom

check

CZ

This menu is only available to Base PRO systems with less than 5 controllers.

DE

This is a diagnostic function detecting whether a room thermostat is installed in the right room. The room check can be stopped any time by choosing Inactive in Room check: Active.

DK

1. Set start time (preferably during the night). Default: 22:00

EE

2. Set end time (preferably during the night). Default: 07:00

3. Set how much to increase the current setpoint value, for checking purposes.

ES

FR

Default: 5% Setting range: 0 – 50%, 1% increments

Room RH Setpoint: Default: 75% Setting range: 0 – 100%, 1% increments

Set the general relative humidity setpoint and humidity deadzone (hysteresis). The setpoint shuts off cooling for the zone when the limit is reached and the hysteresis decides when the system is allowed to start cooling again.

These settings are only available if cooling is allowed and a RH sensor is installed in the system.

Default: 0.5 ˚C Setting range: 0.0 – 5.5 ˚C, 0.1 ˚C increments

The function will check one thermostat per 24 hours.

6. Go back to the room check menu and select Active in Room check: Inactive.

IT

Deadzone (hysteresis):

HU

Default: 75% Setting range: 0 – 100%, 1% increments

4. Set how much to decrease the current setpoint value, for checking purposes.

Default: 1.0 ˚C Setting range: 0.0 – 5.5 ˚C, 0.1 ˚C increments

5. Enter the room list and select which rooms to check.

HR

General RH setpoint:

The controller list displays rooms with a relative humidity (RH) sensor, for each controller if more than one. It is possible to activate RH control ( to activate, to deactivate) and set individual room RH setpoints.

FI

RH C ontrol

SD

card

Use a microSD card to clone interface settings or update the software in the interface. See section 14.16 MicroSD card for more information.

C aution !

The result is shown in Room check results when the room check has run its course.

Do not remove the microSD card while updating.

= OK

LT

C eiling = Not OK

LV = Not checked

NL

R oom

bypass

cooling settings

Set if a registered channel produces ceiling cooling (if available) or underfloor heating/cooling, for each controller if more than one. These settings are only applicable if 4-pipe heating/ cooling is installed in the system.

Select a maximum of up to two rooms, for each controller, to act as a bypass in the system.

NO PL

The bypass ensures that the actuators for these rooms are opened when there is no heating demand to maintain a minimum flow in the system.

PT

Use rooms with a high heating demand (the coldest rooms) to avoid too high temperatures in rooms with low heating demands.

RO RU SE SK 78

U P O N O R S M AT R I X B A S E / B A S E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L