12.2 Loading default values

This procedure allows to restore factory settings of the device. Press Display Do Display shows 000 FNC | 0000 with the 1st 1 for 3s digit flashing. Change the flashing digit and move to the Enter password 999 2 or | 9999 next one pressing SET . Instrument loads SET default settings and 3 to confirm restarts.

12.3 Configuration parameters

ATR121 | ATR141 01 c.ou | c.out Command output Selects command output type. o1.2 | o1.o2 • Command on relay output Q1 (default) • Alarm on relay output Q2 o1.S | o1.o2 • Command on relay output Q1 • Alarm in tension for SSR SSr | SSr • Command in tension for SSR • Alarm on relay output Q1 o2.1 | o2.o1. • Command on relay output Q2 • Alarm on relay output Q1 Ser | Seru. • Valve opening on relay output Q1 • Valve closing on relay output Q2 (SSR with serial version)

26 - ATR121/141 - User manual