Right Elevation 1-Before Remediation
Grid Location
Item Description
Moisture Readings
4E-I
Roof
N/A
5/6 F/G Moisture 30-40% N/A
N/A
N/A
5F
Flashing
N/A
Detail Photo
Observations
EPDM roof material delaminating on seam joints at flashing intersections creating entry points for water ingress. Red shaded area indicates 40% moisture content on 9.5-9.6 floor inside door under carpet and 30% on door header Metal panel vertical overlap seams loose in numerous 1.2, 1.6 locations where water can breach building envelope 1.1, 2.4, Metal "head flashing" design inverted and holding 2.6 water above doors 4.2-4.6
Chapter Reference