Channel - The Safety Book - Edition 10

Page 139

Smoke Detectors 7.5m

7.5m

7.5m >800mm

2m 15m

15m

In corridors less than 2m wide the horizontal spacing of detectors may be increased, the areas of coverage need not overlap as in the case of a room. Any corridor over 2m wide is deemed a room and device spacing should follow the standard for rooms (see page 9).

Voids less than 800mm in height need not have independent coverage, unless fire or smoke is able to spread from one area to another through the void or risk assessment shows AFD (Automatic Fire Detection) to be necessary.

Lift Shaft <1m

Lift Shaft

>1m 1.5m

Air Vent/Air Con

Vertical shafts like lifts and open stairways should have a device mounted within 1.5m of any opening. (This is not necessary for enclosed stairways, because as noted below, there are detectors on every landing within the stairway).

X

<300mm

X

<500mm

>10% Ceiling Height

Partition

<500mm

Beam

Do not site detectors less than 1m from air supply points or air circulating units.

X

A device should not be mounted within 500mm of any obstruction. If the top of a solid partition is less than 300mm from ceiling then treat it as a wall. Similarly, ceiling obstructions such as beams should be treated as walls if deeper than 10% of the ceiling height.

Enclosed stairways should have a detector at the top of the stairway and on each main landing.

Clause 20.2

D X

<2D

Route to travel 30m max. (undefined) at design stage

250mm (Max)

Light Fitting/ Obstruction

Never mount devices closer than twice the depth of light fittings or other obstructions on the ceiling.

0845 884 7000

0845 884 6000

Route to travel 45m max. (defined) at design stage

A person should not have to travel more than 45m to reach a Manual Call Point, for a defined escape route (25m if significant proportion of occupants have limited mobility or rapid fire development is likely). For an undefined route a person should not have to travel more than 30m to reach a Manual Call Point (16m if significant proportion of occupants have limited mobility or rapid fire development is likely).

sales@channelsafety.co.uk

139

THE KNOWLEDGE

08

FIRE DETECTION AND FIRE ALARM SYSTEMS FOR BUILDINGS


Articles inside

Induction Loop Systems

4min
page 135

Toilet Alarm Kits

3min
page 134

Emergency Lighting Specifications Help

2min
page 133

Emergency Lighting

2min
page 132

Nurse Call Systems

12min
pages 106-111

Kit Solutions (App Connect

1min
page 122

Toilet Alarm Kits

4min
pages 104-105

Induction Loop Systems

6min
pages 101-103

Beam Smoke Specialist Devices

2min
page 90

Fire System Accessories

1min
page 99

CCTV Surveillance Systems

2min
page 119

Analogue Addressable Systems

23min
pages 70-81

Mini Static Inverters

1min
page 49

Ac/Dc Central Battery Units

1min
page 48

Self Powered Exit Signage

1min
page 29

Led Luminaires

4min
pages 43-44

Static Inverters

2min
page 50

Aspirating Equipment

4min
pages 86-87

Specialist Batteries

1min
page 51
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.