Industrial Automation and Control Cables Belden

Page 19

INDUSTRIAL AUTOMATION

&

PROCESS

CONTROL

CABLES

18.19

Industrial Data Solutions® — Industrial Coax ControlNet™ Quad Shielded Coax

Description

Part No.

Standard Nominal Conductor UL NEC/ Standard Lengths Unit Weight Core OD (stranding) C(UL) CEC Diameter Type Ft. m Lbs. kg Nom. DCR Inch mm

Shielding Nominal OD Materials Nom. DCR Inch mm

Nominal Nom. Nom. Capacitance Imp. Vel. of (Ω) Prop. pF/Ft. pF/m

Nominal Attenuation dB/ dB/ MHz 100 Ft. 100m

RG-6/U Type • 18 AWG Solid Bare Copper-covered Steel Conductor • Duobond® IV* Quad Shield (100% Coverage) Foam Polyethylene Insulation • PVC Jacket (Black or Intrinsically Safe Blue) 3092A

NEC: CL2R CMR CEC: CMG FT4

500 1000 2000 2500

152.4 304.8 609.6 762.2

20.0 9.1 39.0 17.7 78.0 35.4 92.5 42.0

18 AWG .180 (solid) .040″ BCCS 28.0Ω/M′ 91.8Ω/km

4.57

Duobond IV .298 Quad Shield 3.6Ω/M′ 11.8Ω/km

7.57

75

82%

16.2

53.1

Sweep tested 5 MHz to 50 MHz. CPE jacket optional.

Allen-Bradley P/N 1786

1 2 5 10 20 50 100 200 300 400

.35 .38 .45 .59 .86 1.37 1.97 2.82 3.48 4.04

1.1 1.2 1.5 1.9 2.8 4.5 6.5 9.3 11.4 13.3

1 2 5 10 20 50 100 200 300 400

.36 .38 .50 .65 .95 1.50 2.12 2.99 3.66 4.23

1.2 1.2 1.6 2.1 3.1 4.9 7.0 9.8 12.0 13.9

1 2 5 10 20 50 100 200 300 400

.36 .47 .80 1.20 2.00 3.20 4.60 6.50 8.00 9.30

1.2 1.5 2.6 3.9 6.6 10.5 15.1 21.3 26.2 30.5

Plenum • Foam FEP Insulation • Fluorocopolymer Jacket (Black or Intrinsically Safe Blue◆) 150°C

3093A

NEC: CMP CEC: CMP FT6

1000 ◆ 2000 † 2500 †

304.8 609.6 762.0

40.0 18.2 80.0 36.3 95.0 43.1

18 AWG .170 (solid) .040″ BCCS 28.0Ω/M′ 91.8Ω/km

4.32

Duobond IV .274 Quad Shield 3.6Ω/M′ 11.8Ω/km

6.96

75

82%

16.3

53.5

Sweep tested 5 MHz to 50 MHz.

Blue available as standard in 1000 ft. only. Suitable for Outdoor and Direct Burial applications. • Allen-Bradley P/N 1786

RG-6/U Type • 20 AWG Stranded (105x40) Bare Copper Conductor • Duobond IV* Quad Shield (100% Coverage) Foam Polyethylene Insulation • Black PVC Jacket High-Flex

3092F

NEC: CL2R CMR CEC: CMG FT4

1000 5000

304.8 1524.0

44.0 20.0 220.0 99.8

20 AWG .183 (105x40) .040″ Bare Copper 10.5Ω/M′ 34.4Ω/km

4.65

Duobond IV .303 Quad Shield 3.6Ω/M′ 11.8Ω/km

7.70

75

79%

17.0

55.8

Sweep tested 5 MHz to 400 MHz. CPE jacket optional. 123092F — Aluminum Armor 133092F — Steel Armor

IEEE 802.4 MAP/IEEE 802.7 Mini-MAP. • Allen-Bradley P/N 1786 For Rockwell authorized Flexible ControlNet order YR28890 (Tinned Copper Braid version).

RG-6/U Type • 18 AWG Solid Bare Copper-Covered Steel Conductor • Duobond IV* Quad Shield (100% Coverage) Aluminum Interlocked Armor • Foam Polyethylene Insulation • PVC Inner Jacket • Black PVC Sunlight Resistant Outer Jacket 75°C

123092A

u

NEC: CM CEC: CMG, FT4, HL

1000 ††

304.8

180.0 81.7

18 AWG .180 (solid) .040″ BCCS 28.0Ω/M′ 91.9Ω/km

4.57

Duobond IV Inner Jacket Quad .298 7.57 Shield Overall: 3.6Ω/M′ .620 15.75 11.8Ω/km

75

82%

16.2

53.2

Sweep tested 5 MHz to 50 MHz. CPE jacket optional. 133092A — Steel Armor

Allen-Bradley P/N 1786 Jacket sequentially marked at 1 meter intervals.

1 2 5 10 20 50 100 200 300 400

.35 .38 .45 .59 .86 1.37 1.97 2.82 3.48 4.04

1.2 1.3 1.5 1.9 2.8 4.5 6.5 9.3 11.4 13.3

Continuously Corrugated Aluminum Armor • Foam Polyethylene Insulation • PVC Inner Jacket • Black PVC Outer Jacket 183092A

u

NEC: CL2, CM

2000 ▲

609.6

350.0 158.9

18 AWG .180 (solid) .040″ BCCS 28.0Ω/M′ 91.9Ω/km

4.57

Duobond IV Inner Jacket Quad .298 7.57 Shield Overall: 3.6Ω/M′ .570 14.48 11.8Ω/km

75

82%

16.2

53.2

Sweep tested 5 MHz to 50 MHz. Allen-Bradley P/N 1786 Jacket sequentially marked at 2 ft. intervals.

1 2 5 10 20 50 100 200 300 400

.35 .38 .45 .59 .86 1.37 1.97 2.82 3.48 4.04

1.2 1.3 1.5 1.9 2.8 4.5 6.5 9.3 11.4 13.3

BCCS = Bare Copper-covered Steel • DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene *Duobond IV Quad Shield = Duobond II Foil + 60% aluminum braid + Duofoil + 40% aluminum braid. †

Final put-up length may vary 0 to +10% from length shown. Final put-up length may vary ±5% from length shown. Final put-up length may vary ±10% from length shown.

†† ▲

ControlNet is a ControlNet International trademark.

F o r m o r e i n f o r m a t i o n , c o n t a c t B e l d e n Te c h n i c a l S u p p o r t : 1 - 8 0 0 - B E L D E N - 1 • w w w . b e l d e n . c o m

18 • Industrial Cables

75°C


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.