inverter

Page 40

VFD-M Series

01: Two wire operation: Only Pr.38 can be set to “1”. RUN/STOP

M0 "Open": Stop, "Close": Run

M1 "Open": FWD, "Close":REV

REV/FWD

GND

Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in conjunction with M1 to operate two and three wire control. 02 Three Wire Control: Only Pr.38 can be set to “2”. STOP

RUN M0 Run command, Runs when "close" M2 Stop command, stops when "Open" M1 REV/FWD Run selection RUN/FWD "Open": FWD Run "Close": REV Run GND

Note: When the “2” setting is selected for Pr.38, the value in Pr.39 will be ignored.

Pr.39 Multi-function Input Terminal (M2)

Factory Setting: 05

Pr.40 Multi-function Input Terminal (M3)

Factory Setting: 06

Pr.41 Multi-function Input Terminal (M4)

Factory Setting: 07

Pr.42 Multi-function Input Terminal (M5)

Factory Setting: 08

Settings 00 to 32 Parameters & Functions table: Value 00 02 04 06

Function No Function Output OFF (N.C.) (enabled when running) External Fault (N.C.) Multi-Step Speed Command 1

Value 01

Function Output OFF (N.O.) (enabled when running)

03

External Fault (N.O.)

05 07

External Reset Multi-Step Speed Command 2

5-14

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED