VFD-M Series
01: Two wire operation: Only Pr.38 can be set to “1”. RUN/STOP
M0 "Open": Stop, "Close": Run
M1 "Open": FWD, "Close":REV
REV/FWD
GND
Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in conjunction with M1 to operate two and three wire control. 02 Three Wire Control: Only Pr.38 can be set to “2”. STOP
RUN M0 Run command, Runs when "close" M2 Stop command, stops when "Open" M1 REV/FWD Run selection RUN/FWD "Open": FWD Run "Close": REV Run GND
Note: When the “2” setting is selected for Pr.38, the value in Pr.39 will be ignored.
Pr.39 Multi-function Input Terminal (M2)
Factory Setting: 05
Pr.40 Multi-function Input Terminal (M3)
Factory Setting: 06
Pr.41 Multi-function Input Terminal (M4)
Factory Setting: 07
Pr.42 Multi-function Input Terminal (M5)
Factory Setting: 08
Settings 00 to 32 Parameters & Functions table: Value 00 02 04 06
Function No Function Output OFF (N.C.) (enabled when running) External Fault (N.C.) Multi-Step Speed Command 1
Value 01
Function Output OFF (N.O.) (enabled when running)
03
External Fault (N.O.)
05 07
External Reset Multi-Step Speed Command 2
5-14