Instruction Manual
LCP100 Local Control Panel
August 2010
LCP100 LOOP
SWITCH TO LOOP POSITION AUX )
LOGIC SOLVER OUTPUT
8-20 mA
1 LOOP ) ) *
LOOP *
CASE GROUND
(USER SUPPLIED)
DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN POINT-TO-POINT MODE
SHIELD NOT CONNECTED TO LCP100
NOTE: 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA. GE26881-B, Sheet 1 E1083-1
POINT-TO-POINT MODE
LCP100
LOOP SWITCH TO LOOP POSITION
AUX )
1 LOOP )
) * (USER SUPPLIED)
SYS − /)
24VDC
FLD − /)
LOGIC SOLVER OUTPUT
CASE GROUND
LOOP *
LC340 LINE CONDITIONER
DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN MULTI-DROP MODE
SHIELD NOT CONNECTED TO LCP100
NOTE: 1 THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA.
E1384
MULTI-DROP MODE
Figure 5. Wiring for Loop-Powered Configuration; Logic Solver Wired to the FIELDVUE DVC6000 SIS then the Fisher LCP100
7