LCP100 LOOP

SWITCH TO LOOP POSITION AUX )

LOGIC SOLVER OUTPUT

8-20 mA

1 LOOP ) ) *

LOOP *

CASE GROUND

(USER SUPPLIED)

DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN POINT-TO-POINT MODE

SHIELD NOT CONNECTED TO LCP100

NOTE: 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE AT LEAST 8 mA. THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA. GE26881-B, Sheet 1 E1083-1

POINT-TO-POINT MODE

LCP100

LOOP SWITCH TO LOOP POSITION

AUX )

1 LOOP )

) * (USER SUPPLIED)

SYS − /)

24VDC

FLD − /)

LOGIC SOLVER OUTPUT

CASE GROUND

LOOP *

LC340 LINE CONDITIONER

DVC6000 SIS TERMINAL BOX THE DVC6000 SIS MUST BE IN MULTI-DROP MODE

SHIELD NOT CONNECTED TO LCP100

NOTE: 1 THE LCP100, WHEN POWERED BY THE LOOP, CONSUMES APPROXIMATELY 4 mA.

E1384

MULTI-DROP MODE

Figure 5. Wiring for Loop-Powered Configuration; Logic Solver Wired to the FIELDVUE DVC6000 SIS then the Fisher LCP100