Ask the experts/Technical

Fully charged For handlamps

Fig 2 Automatic disconnection of supply used in conjunction with additional supplementary bonding

The only protective measure permitted to be used for the supply to handlamps is SELV, in accordance with Section 414. The SELV supply may be used to supply a fluorescent luminaire operating at a voltage exceeding extra-low voltage, incorporating an integral step-up transformer having electrically separated windings (indent (ii) a) of Regulation 706.410.3.10 refers).

Access

Protective device

Fixed equipment

For fixed equipment

Source

The protective measure of automatic disconnection of supply in accordance with Section 411 may be used, provided this includes supplementary bonding in accordance with Regulation Group 415.2. The supplementary bonding should connect together all exposed-conductive-parts within the location (such as metallic conduits and equipment enclosures) and the conductive parts of the location itself (such as the metalwork of a boiler, vessel, duct or similar). Fig 2 refers. The protective measure of double or reinforced insulation in accordance with Section 412 may be used, on condition that the circuits supplying the equipment are provided with additional protection by RCDs having a rated residual current (Iホ馬) not exceeding 30 mA and an operating time not exceeding 40 ms at a residual current of 5 Iホ馬.

cpc

Fortuitous contact with earth

Additional supplementary bonding conductor

Fig 3 The use of SELV and PELV to supply any type of equipment in a conducting location with restricted movement (a) SELV

(b) PELV

Access Protective device

SELV source

Protective device

SELV circuit

Source

Access

SELV current-using equipment

SELV source

PELV circuit

PELV current-using equipment

Source

cpc cpc

56

Winter 2013-14 Connections

44-61_technicals.FINAL.indd 56

20/01/2014 17:00