Page 53

circuit, the ‘single point of supply’ is the point at which the two ends of the ring part of the circuit are connected to the radial part (that is, at the joint box, switch or contactor in the example in Fig 1). A hybrid ring/radial final circuit must be arranged to meet all the relevant requirements of BS 7671, the main ones of which are summarised below. Protection against electric shock As for any other final circuit, the requirements of Chapter 41 for electric shock protection have to be met, including those of Section 411 for earth fault loop impedance (Zs) and, where applicable, RCD additional protection of the socket-outlets (IΔn ≤ 30 mA) in accordance with Regulation 411.3.3. Also, if any part of the circuit cable is concealed in a wall or partition, it must be provided with additional protection by an RCD (IΔn ≤ 30 mA) where required by Regulations 522.6.7 or 522.6.8 (numbers changed to 522.6.102 and 522.6.103, respectively, by Amendment 1 (2011) to BS 7671: 2008). Cable sizing with regard to normal load and overload The current-carrying capacity (Iz) of the cable in the radial part of the circuit must be not less than 30 A or 32 A, to match the circuit overcurrent protective device rating (In) of 30 A or 32 A. Where the protective device is a semi-enclosed (rewireable) fuse, Iz must be not less than In divided by 0.725. Regulation 433.1.3 refers (number changed to 433.1.101 by Amendment 1 (2011) to BS 7671: 2008). The ring part of the circuit must meet the same overload protection requirements as for any other ring final circuit. The usual way to comply with these requirements is to comply with Regulation 433.1.5 (number changed to 433.1.103 by Amendment 1 (2011) to BS 7671: 2008). Despite the non-conventional form of a hybrid ring/ radial circuit, the total load current (Ib) to be supplied by the circuit, making due allowance for any diversity, must still be no greater than the 30 A or 32 A rating of the circuit protective device. Thus, for example, the floor area served by the circuit should be no greater than would be the case if an ordinary ring final circuit having the same protective device rating was installed instead of the hybrid circuit. Accessibility of connections As is required for all electrical connections, the connections between the radial and ring parts of the circuit (in the junction box, switch or contactor in Fig 1) must be arranged to be accessible throughout the life of the installation for inspection, testing and maintenance. The only exception is where a connection method excused from this requirement by Regulation 526.3 is used.

www.niceic.com

50_63_technical.2.vb.indd 53

Voltage drop Account must be taken of the voltage drops in both the radial and ring parts of the circuit. These voltage drops added together make up the total voltage drop in the circuit. This may mean, for example, that the maximum allowable length of the ring part of the circuit will be less than that for a ring final circuit connected directly to the distribution board. Protective conductor in the ring part of the circuit Except where the circuit protective conductor in the ring part of the circuit is formed by a metal covering (such as a metallic cable sheath) or enclosure (such as metal conduit) containing all the conductors of the ring, the protective conductor must be run in the form of a ring, as required by Regulation 543.2.9. Both ends of the protective conductor ring must be connected to the earthing terminal at the origin of the ring (that is, the junction box, switch or contactor in Fig 1). Earthing for equipment having high protective conductor currents If the circuit is intended to supply one or more items of equipment where it is known or reasonably to be expected that the total protective conductor current is likely to exceed 10 mA, the circuit will require a high integrity protective conductor connection in accordance with Regulation Group 543.7. In the radial part of the circuit this will necessitate the use of a 10 mm2 circuit protective conductor in accordance with Regulation 543.7.1.3(i), or one of the three arrangements (a), (b) and (c) listed in Regulation 543.7.2.1 (ii), for example. In the ring part of the circuit, the requirement for a high integrity protective conductor connection will be met automatically provided the circuit protective conductive in that part is run in the form of a ring (Regulation 543.7.2.1(i) refers), as referred in the previous item of this article. Use of a standard circuit might be easier It will be appreciated from this article that the use of a hybrid ring/radial circuit arrangement can involve significant design effort. As an alternative, for household and similar installations, installers should consider the use of the standard ring or radial socket-outlet circuit arrangements shown in Appendix 15 of BS 7671, for which tables of maximum cable length are given in the NICEIC Domestic Electrical Installation Guide.

NICEIC Connections Summer 2011

53

14/6/11 13:07:58


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
Connections June by Redactive Media Group - Issuu