Chimney Installation

A. Typical Chimney System

Storm Collar Roof Flashing

f)

(roo

Thimble Extension Mobile Home Thimble

(insulation)

(attic) (ceiling)

Must have 2 in. (51 mm) minimum clearance to header

Shaded areas represent 2 in. (51 mm) min. air space clearance required around pipe Figure 5.1 Typical Chimney System - Thimble Application

Chimney must extend beyond combustible roof structure Maintain minimum height of chimney above roof Install roof flashing according to minimum requirements

Offsets/returns may not exceed 30° from vertical

Lock chimney sections together firmly to resist movement

Termination Cap Additional support for tall chimneys Storm Collar Maintain minimum clearances to combustibles as specified Support straps for offsets (not shown) must be secured to adequate framing Offsets/returns must be secured with the screws provided (outer pipe only) Attic shield Ceiling firestops are required where chimney passes through ceiling or floor

Figure 5.2 Typical Chimney System - Attic Shield Application

14

Heatilator • MEL36, MEL42 Installation Manual • 4044-212 • Rev D • 01/06/15