Water treatment and water disinfection

Page 80

3

Chlorine Dioxide Systems Bello Zon®

3.10

Safety Accessories and Analysis

Gas warning device GMA 36 – chlorine dioxide The gas warning device GMA 36 for chlorine dioxide is designed as a compact measuring and switching unit for monitoring the surrounding air for dangerous concentrations of chlorine dioxide.

Technical Data

3 pk_7_004_1 Gas warning devices GMA 36

Type Warning at approx. Alarm at approx. Permissible ambient temperature Protection class housing Dimensions (without PGs, without sensor) H x W x D Supply Power consumption Warm-up phase max. "Warning" relay contact, self-resetting "Alarm" relay contact, latching "Horn" relay contact, latching, can be acknowledged Sensor measuring principle Sensor service life (depending on environmental cond.)

Chlorine dioxide 0.1 ppm/vol% 0.3 ppm/vol% -15…45°C IP 54 247 x 135 x 95 mm 85 – 264 / 50 – 60 V/Hz 5W 150 s 230 / 1 V/A 230 / 1 V/A 230 / 1 V/A electrochemical 2–3 years

Note: The sensor responds to all oxidising gases Order no. 1023156

Gas warning device GMA 36 – chlorine dioxide

Spare parts Replacement sensor Replacement sensor

for chlorine, chlorine dioxide, ozone for gas warning devices in the Life CGM range

Order no. 1023314 1003009

Warning label for chlorine dioxide system Soft PVC film, yellow/black, 300 x 200 mm, self-adhesive. Text "Behälter und Geräte nicht wechselweise benutzen" "Never mix up chemical containers" "Non usare serbatoi e apparecchi alternativamente"

Language german english italian

Order no. 607320 607318 791886

Language german english italian

Order no. 607322 607319 791885

Warning label for chlorine dioxide room PVC film yellow/black, 200 x 80 mm Text "Zutritt nur für unterwiesene Personen" "Entry for authorised persons only" "Vietato l'accesso ai non addetti ai lavori"