Daikin - English Service Manual

Page 64

Indoor Unit

2.4

SiBE121135_A

FTXS60/71GV1B

Control PCB 1) 2) 3) 4) 5) 6) 7) 8)

S1 S21 S25 S32 S41 S46 S47 H1, H2, H3, FG 9) V1 10)JA

Connector for DC fan motor Connector for centralized control (HA) Connector for INTELLIGENT EYE sensor PCB Connector for indoor heat exchanger thermistor Connector for swing motors Connector for display PCB Connector for signal receiver PCB Connector for terminal board

11) JB JC

Varistor Address setting jumper ∗ Refer to page 253 for detail. Fan speed setting when compressor stops for thermostat OFF Power failure recovery function (auto-restart) ∗ Refer to page 257 for detail. LED for service monitor (green) Fuse (3.15 A, 250 V)

12)LED A 13)FU1 (F1U)

S41

S1 S32

LED A

H3 FG H2 FU1 H1 (3.15A)

S46

V1

S25

S21 S47 JC JA JB

2P227881-2

Caution

53

Replace the PCB if you accidentally cut the jumpers other than JA, JB, and JC. Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.