Actual signals and parameters 213
All parameters No.
Name/Value RESET 1908 COUNTER RES VAL 0…65535 1909 COUNT DIVIDER
Description Reset enabled Defines the value for the counter after reset.
Def/FbEq 9 0
Counter value Defines the divider for the pulse counter.
1=1 0
0…12 1910 COUNT DIRECTION DI1(INV)
Pulse counter divider N. Every 2N bit is counted. Defines the source for the counter direction selection.
1=1 UP
Counter direction selection through inverted digital input DI1. 1 = counts up, 0 = counts down. See selection DI1(INV). See selection DI1(INV).
-1
See selection DI1(INV). See selection DI1(INV). Counts up Counter direction selection through digital input DI1. 0 = counts up, 1 = counts down. See selection DI1. See selection DI1.
-4 -5 0 1
See selection DI1. See selection DI1. Counts down Selects the source for the drive start/stop command when parameter 1001 EXT1 COMMANDS value is set to COUNTER START / COUNTER STOP.
4 5 6 NOT SEL
DI2(INV) DI3(INV) DI4(INV) DI5(INV) UP DI1 DI2 DI3 DI4 DI5 DOWN 1911 CNTR S/S COMMAND
-2 -3
2 3
DI1(INV)
Start/stop command through inverted digital input DI1. -1 When parameter 1001 EXT1 COMMANDS value is COUNTER STOP: 0 = start. Stop when counter limit defined by parameter 1905 COUNTER LIMIT has been exceeded. When parameter 1001 value is COUNTER START: 0 = stop. Start when counter limit defined by parameter 1905 has been exceeded.
DI2(INV) DI3(INV) DI4(INV)
See selection DI1(INV). See selection DI1(INV). See selection DI1(INV).
-2 -3 -4
DI5(INV) NOT SEL
See selection DI1(INV). Not start/stop command source
-5 0