162 Program features Note: The jogging speed overrides the constant speeds. Note: The jogging uses ramp stop even if parameter 2102 STOP FUNCTION selection is COAST. Note: The ramp shape time is set to zero during the jogging (ie linear ramp). Jogging function uses constant speed 7 as jogging speed and acceleration/deceleration ramp pair 2. It is also possible to activate jogging function 1 or 2 through fieldbus. Jogging function 1 uses constant speed 7 and jogging function 2 uses constant speed 6. Both functions use acceleration/deceleration ramp pair 2.
Settings Parameter 1010
Additional information Jogging activation
1208 1208/1207
Jogging speed Jogging speed for jogging function 1/2 activated through fieldbus Zero speed delay Acceleration and deceleration times Acceleration and deceleration ramp shape time: Set to zero during the jogging (ie linear ramp).
2112 2205, 2206 2207
Diagnostics Actual signal 0302
Additional information Jogging 1/2 activation through fieldbus
1401 1402/1403/1410
Jogging function status through RO 1 Jogging function status through RO 2…4. With option MREL-01 only.
1805
Jogging function status through DO