ACS355UM

Page 154

154 Program features

Example The time scheme below visualizes the operation of the sleep function. Motor speed

td = Sleep delay (4024) t<td td Control panel display:

Sleep level (4023)

PID SLEEP Stop

Actual value

Start

t

Wake-up delay (4026) Wake-up deviation (4025) t

Sleep function for a PID controlled pressure boost pump (when parameter 4022 SLEEP SELECTION is set to INTERNAL): The water consumption falls at night. As a consequence, the PID process controller decreases the motor speed. However, due to natural losses in the pipes and the low efficiency of the centrifugal pump at low speeds, the motor does not stop but keeps rotating. The sleep function detects the slow rotation, and stops the unnecessary pumping after the sleep delay has passed. The drive shifts into sleep mode, still monitoring the pressure. The pumping restarts when the pressure falls under the allowed minimum level and the wake-up delay has passed.

Settings Parameter

Additional information

9902 4022…4026, 4122…4126

PID control activation Sleep function settings

Diagnostics Parameter

Additional information

1401 1402/1403/1410

PID sleep function status through RO 1 PID sleep function status through RO 2…4. With option MREL-01 only. Additional information Sleep mode