Wall Mounted - WX

Page 1

WX SERIES

WALL MOUNTED TYPE HYDRONIC FAN COIL FOR STANDARD AND DISTRICT COOLING CONDITIONS

WX-CW&DW-INTER-0610-REV. 1


Wall Mounted Type We have a long and vast experience in developing the direct expansion wall mounted fan coil units of various looks and designs. New models of such types of units make their debut regularly. We have always kept an eye on the world trend for the demand of this kind of products and are always prepared to answer to the market needs. By far the split system wall mounted units are the most popular worldwide, capturing a majority of about 60 percent of the total mini split market. In recent years the demand for the hydronic wall mounted fan coil unit is on the increase in Europe and other regions because of the competitive price ,ready availability and the beauty of the wall mounted unit itself as well as the need to void or reduce the presence of the CFC refrigerant in the room. We have always put emphasis on our continuous development of new products, particularly the wall mounted units, as well as their high, reliable quality and performance. We extend our range of the wall mounted unit to include the hydronic versions in line with the world trend. So customers can be assured of the top quality of our products on offer as usual.

Technical Specifications – For Standard Conditions Model

WX10MPVC/H-CW

Chilled Water Cooling (A) Hot Water Heating (B) Hot Water Heating (C) Inlet and outlet Pipe connection Drain connection Evaporator Coil

Fan

Fan Motor

Nominal Air Flow Rate Sound pressure level Dimension Net weight

Total capacity Sensible capacity Water flow rate Pressure drop Capacity Capacity Water flow rate Pressure drop Type Diameter Nominal Diameter Face area Row Fin Type/ Fin pitch Tube diameter Type Size Dia. X Length No. Type Power supply Power Input Running Current RPM M3/H dB (A) HxWxD

( Watts ) ( Watts ) ( l/hr ) ( kPa ) ( Watts ) ( Watts ) ( l/hr ) ( kPa )

2750 2250 472 21.0 4030 6820 600 23.4

(Inch) (mm) (m2)

½ 16 OD 0.1638 2 Louver/ 1.21 ø 7 Smooth

(mm) ( mm.) (V/Ph/Hz) (W) (A) T/H/M/L T/H/M/L T/H/M/L (mm.) (Kg)

106 x 642 1 47.0 0.24 1340/1200/1080/1000 700/540/430/390 49/45/42/40 315 x 824 x 245 11

WX13MPVC/H-CW

WX18MPVC/H-CW

WX24MPVC/H-CW

3760 5870 2980 4430 646 1007 23.0 57.0 4680 7820 6940 12300 610 1081 20.0 58.7 Male Water Pipe Thread ½ ½ 16 OD 16 OD 0.2314 0.2318 2 2 Louver/ 1.21 Louver/ 1.21 ø 7 Smooth ø 7 Smooth Cross flow fan 106 x 642 106 x 920 1 1 Permanent Split Capacitor 220-240/1/50 47.0 51.0 0.24 0.23 1260/990/800/720 1380/1280/1170/1020 710/500/420/370 1125/980/840/690 46/36/31/28 48/46/43/39 315 x 824 x 245 315 x 1147 x 245 12 14

6340 4930 1088 63.0 8530 13830 1215 66.3 ½ 16 OD 0.3275 2 Louver/ 1.21 ø 7 Smooth 106 x 920 1 59.0 0.26 1320/1130/980/810 1140/890/760/600 49/43/38/33 315 x 1147 x 245 15

Note: A – Cooling capacity is based on : Inlet water temp. 7oC ; Outlet water temp. 12oC ; Inlet air temp. 27oC DB, 19oC WB at turbo fan speed. B – Heating capacity is based on : Inlet water temp. 50oC ; Same water flow as in cooling ; Inlet air temp. 20oC DB at turbo fan speed. C – Heating capacity is based on : Inlet water temp. 70oC ; Outlet water temp. 60oC ; Inlet air temp. 20oC DB at turbo fan speed.

Technical Specifications – For District Cooling Conditions Model

WX10MPVC-DW

Chilled water Cooling Inlet and Outlet Pipe Connection Drain Connection Evaporator Coil

Fan

Fan Motor

Nominal Air Flow Rate Sound pressure level Dimension Net weight

Total capacity Sensible capacity Water flow rate Pressure drop Type Diameter Nominal Diameter Face area Row Fin Type / Fin pitch Tube diameter Type Size Dia x Length No. Type Power supply Power Input Running Current RPM m3/hr T/H/M/L dB (A) T/H/M/L HxWxD

(Watts) (Watts) (l/hr) (kPa)

2480 1920 237 36.0

(Inch) (mm) (m2)

1/2 16 OD. 0.1638 2 Louver /1.21 ø 7 Smooth

(mm) (mm)

(V/Ph/Hz) (W) (A) T/H/M/L

(mm) (Kg)

ø 106 x 642 1

42 0.22 1340/1210/1130/1060 630 /500 /420 /380 49 /45 /42 /40 315 x 824 x 245 11

WX13MPVC-DW

WX18MPVC-DW

3090 4150 2350 3270 295 396 22.5 33.0 Male Water Pipe Thread 1/2 1/2 16 OD. 16 OD. 0.2314 0.2318 2 2 Louver /1.21 Louver /1.21 ø 7 Smooth ø 7 Smooth Cross Flow Fan ø 106 x 642 ø 106 x 920 1 1 Permanent Split Capacitor 220-240/1/50 43 51 0.23 0.23 1310/1130/990/880 1370/1260/1130/990 660 /510 /430 /390 1020 /850 /720 /550 46 /36 /31 /28 48 /46 /43 /39 315 x 824 x 245 315 x 1147 x 245 12 14

WX24MPVC-DW 5320 4010 508 36.6 1/2 16 OD. 0.3275 2 Louver /1.21 ø 7 Smooth ø 106 x 920 1

56 0.25 1330/1180/1040/830 1050 /880 /730 /580 49 /43 /38 /33 315 x 1147 x 245 15

Note : Cooling capacity is based on : Inlet water temp.5.5 oC ; Outlet water temp. 14.5oC ; Inlet air temp. 24oC DB, 18oC WB at turbo fan speed.


Product Nomenclature Pipe connection P = Male thread Q = Male thread with valve

Size 10, 13, 18, 24

WX

10

Model WX = Wall flat panel WA = Wall line panel

M

P

Remote B = Without M = Wireless LCD L = Room thermostat

System C = Cooling only H = Cool + Heat

V

C

-

Power V = 220-240/1/50 W = 208-230/1/60

CW Suitable condition CW = Standard DW = District cooling

Performance Data – Standard Conditions Cooling Capacity (kW)

UNIT MODEL

WATER TEMP. RISE K.

WX24MPVC-CW WX18MPVC-CW WX13MPVC-CW WX10MPVC-CW

5 oC Entering Water Temperature

4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9

17° C WB Total SENSIBLE Cap. 23 24 DB DB

18° C WB Total SENSIBLE Cap. 24 25 DB DB

ENTERING AIR TEMPERATURE °C 19° C WB 20° C WB Total SENSIBLE Total SENSIBLE Cap. 26 27 Cap. 27 28 DB DB DB DB

2.60 2.29 2.00 1.64 1.32 1.00 3.52 3.19 2.87 2.58 2.27 1.96 5.91 5.07 4.63 4.10 3.56 2.93 5.84 5.44 4.98 4.45 3.95 3.26

3.03 2.75 2.45 2.12 1.78 1.44 4.10 3.79 3.48 3.18 3.90 2.58 6.19 5.87 5.49 5.05 4.57 3.98 6.76 6.35 5.89 5.35 4.88 4.24

3.52 3.20 2.89 2.60 2.29 1.96 4.68 4.38 4.07 3.74 3.43 3.11 7.01 6.68 6.30 5.92 5.44 5.00 7.59 7.19 6.86 6.41 5.96 5.34

1.95 1.82 1.71 1.57 1.32 1.00 2.59 2.45 2.31 2.19 2.06 1.94 4.06 3.70 3.51 3.29 3.07 2.82 4.26 4.09 3.89 3.67 3.46 3.19

2.11 1.98 1.87 1.64 1.32 1.00 2.79 2.65 2.51 2.39 2.26 1.96 4.35 3.98 3.80 3.58 3.35 2.93 4.59 4.42 4.22 4.00 3.79 3.26

2.08 1.97 1.85 1.72 1.59 1.44 2.79 2.65 2.52 2.39 2.28 2.15 4.09 3.95 3.79 3.60 3.41 3.17 4.56 4.38 4.19 3.96 3.77 3.52

2.24 2.13 2.01 1.88 1.75 1.44 2.99 2.85 2.72 2.59 2.48 2.35 4.37 4.24 4.07 3.89 3.69 3.46 4.89 4.71 4.52 4.29 4.09 3.84

2.39 2.26 2.14 2.03 1.91 1.79 3.17 3.04 2.91 2.77 2.64 2.52 4.62 4.47 4.32 4.16 3.97 3.79 5.13 4.96 4.82 4.63 4.45 4.20

2.55 2.42 2.30 2.19 2.07 1.95 3.37 3.24 3.11 2.97 2.84 2.72 4.90 4.76 4.61 4.45 4.26 4.08 5.46 5.29 5.15 4.96 4.78 4.53

3.96 3.66 3.38 3.11 2.79 2.45 5.17 4.88 4.61 4.31 4.05 3.71 7.82 7.48 7.14 6.78 6.43 5.94 8.48 8.08 7.77 7.38 6.93 6.37

2.51 2.39 2.28 2.18 2.06 1.94 3.30 3.17 3.06 2.94 2.83 2.70 4.84 4.69 4.55 4.41 4.27 4.08 5.38 5.21 5.09 4.92 4.74 4.52

2.67 2.55 2.44 2.34 2.22 2.10 3.50 3.37 3.26 3.14 3.03 2.90 5.13 4.99 4.85 4.70 4.56 4.36 5.71 5.54 5.41 5.25 5.07 4.85

Total Cap. 4.39 4.14 3.86 3.55 3.26 2.91 5.73 5.49 5.24 4.96 4.67 4.30 8.73 8.31 8.00 7.70 7.32 6.92 9.43 9.07 8.70 8.31 7.91 7.44

21° C WB SENSIBLE 28 29 DB DB 2.61 2.52 2.41 2.29 2.19 2.06 3.44 3.34 3.24 3.12 3.01 2.86 5.08 4.91 4.78 4.66 4.51 4.35 5.64 5.48 5.33 5.17 5.01 4.83

2.77 2.68 2.57 2.45 2.35 2.22 3.64 3.54 3.44 3.32 3.21 3.07 5.37 5.19 5.07 4.95 4.80 4.64 5.97 5.81 5.66 5.50 5.34 5.16

Total Cap. 4.90 4.62 4.38 4.11 3.85 3.56 6.42 6.18 5.88 5.58 5.31 4.95 9.65 9.30 8.92 8.58 8.30 7.94 10.46 10.01 9.65 9.30 8.96 8.57

22° C WB SENSIBLE 29 30 DB DB 2.74 2.63 2.54 2.44 2.35 2.24 3.63 3.53 3.41 3.29 2.81 3.04 5.31 5.17 5.01 4.88 4.77 4.63 5.91 5.72 5.57 5.43 5.30 5.14

2.90 2.79 2.70 2.60 2.51 2.40 3.83 3.73 3.61 3.49 3.01 3.37 5.60 5.45 5.30 5.17 5.06 4.92 6.23 6.05 5.90 5.76 5.63 5.47

UNIT MODEL

WATER TEMP. RISE K.

WX24MPVC-CW WX18MPVC-CW WX13MPVC-CW WX10MPVC-CW

6 oC Entering Water Temperature

4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9

17° C WB Total SENSIBLE Cap. 23 24 DB DB

18° C WB Total SENSIBLE Cap. 24 25 DB DB

ENTERING AIR TEMPERATURE °C 19° C WB 20° C WB Total SENSIBLE Total SENSIBLE Cap. 26 27 Cap. 27 28 DB DB DB DB

2.41 2.10 1.78 1.42 1.09 0.76 3.30 2.93 2.57 2.31 2.11 1.84 5.01 4.65 4.18 3.68 3.10 2.56 5.44 4.99 4.55 4.04 3.56 3.02

2.84 2.55 2.22 1.90 1.54 1.20 3.80 3.48 3.18 2.88 2.63 2.37 5.80 5.44 5.06 4.64 4.10 3.51 6.34 5.93 5.50 4.98 4.44 3.85

3.28 2.99 2.68 2.38 2.07 1.71 4.36 4.05 3.76 3.49 3.24 3.02 6.62 6.24 5.87 2.53 5.12 4.56 7.16 6.81 6.43 6.00 5.40 4.74

1.87 1.75 1.62 1.42 1.09 0.76 2.50 2.34 2.19 2.08 2.11 1.84 3.67 3.52 3.32 3.15 2.88 2.56 4.09 3.90 3.71 3.50 3.30 3.02

2.03 1.91 1.78 1.42 1.09 0.76 2.70 2.54 2.39 2.28 2.11 1.84 3.96 3.80 3.61 3.44 3.10 2.56 4.42 4.23 4.04 3.82 3.63 3.02

2.01 1.89 1.76 1.64 1.50 1.20 2.65 2.52 2.39 2.27 2.17 2.07 3.92 3.77 3.60 3.43 3.22 2.99 4.38 4.21 4.02 3.81 3.59 3.36

2.17 2.05 1.92 1.80 1.54 1.20 2.85 2.72 2.59 2.47 2.37 2.27 4.21 4.05 3.89 3.72 3.51 3.28 4.71 4.54 4.35 4.14 3.92 3.69

2.30 2.18 2.06 1.95 1.83 1.70 3.03 2.90 2.77 2.67 2.57 2.48 4.45 4.29 4.14 4.00 3.84 3.62 4.95 4.80 4.64 4.46 4.23 3.97

2.46 2.34 2.22 2.11 1.99 1.71 2.32 3.10 2.97 2.87 2.77 2.68 4.74 4.58 4.43 4.29 4.13 3.91 5.28 5.13 4.97 4.79 4.56 4.30

3.73 3.44 3.16 2.85 2.57 2.22 4.92 4.63 4.33 4.04 3.82 3.50 7.42 7.08 6.70 6.37 5.97 5.47 8.07 7.70 7.32 6.92 6.43 5.48

2.42 2.30 2.20 2.09 1.98 1.86 3.19 3.07 2.94 2.83 2.74 2.62 4.67 4.53 4.38 4.24 4.09 3.90 5.21 5.05 4.90 4.74 4.54 4.17

2.58 2.46 2.36 2.25 2.14 7.02 3.39 3.27 3.15 3.03 2.94 2.82 4.96 4.82 4.67 4.53 4.38 4.18 5.54 5.38 5.22 5.06 4.87 4.50

Total Cap. 4.20 3.91 3.60 3.32 3.06 2.76 5.51 5.26 4.94 4.66 4.40 4.12 8.24 7.94 7.56 7.23 6.92 6.56 8.97 8.65 8.30 7.84 7.43 7.00

21° C WB SENSIBLE 28 29 DB DB 2.54 2.43 2.31 2.21 2.12 2.01 3.35 3.24 3.12 3.00 2.90 2.80 4.88 4.75 4.61 4.48 4.35 4.22 5.44 5.31 5.17 4.99 4.82 4.64

2.70 2.59 2.47 2.37 2.28 2.17 3.55 3.44 3.32 3.20 3.10 3.00 5.17 5.04 4.90 4.77 4.64 4.51 5.77 5.64 5.50 5.32 5.15 4.97

Total Cap. 4.65 4.39 4.15 3.89 3.61 3.33 6.16 5.88 5.56 5.24 4.98 4.71 9.22 5.94 8.57 8.18 7.85 7.51 10.05 9.66 9.25 8.76 8.38 8.00

22° C WB SENSIBLE 29 30 DB DB 2.64 2.55 2.46 2.36 2.26 2.17 3.52 3.41 3.28 3.15 3.05 2.95 5.13 5.02 4.88 4.72 4.60 4.47 5.73 5.57 5.41 5.22 5.07 4.92

2.80 2.71 2.62 2.52 2.42 2.33 3.72 3.61 3.48 3.35 3.25 3.15 5.42 5.31 5.17 5.01 4.89 4.76 6.06 5.90 5.74 5.55 5.40 5.25


UNIT MODEL

WATER TEMP. RISE K.

WX24MPVC-CW WX18MPVC-CW WX13MPVC-CW WX10MPVC-CW

7 oC Entering Water Temperature

4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9

17° C WB Total SENSIBLE Cap. 23 24 DB DB

18° C WB Total SENSIBLE Cap. 24 25 DB DB

ENTERING AIR TEMPERATURE °C 19° C WB 20° C WB Total SENSIBLE Total SENSIBLE Cap. 26 27 Cap. 27 28 DB DB DB DB

2.17 1.84 1.52 1.21 0.91 0.67 3.01 2.68 2.37 2.07 1.84 1.57 4.61 4.20 3.71 3.15 2.59 2.02 5.01 4.55 4.07 3.57 3.08 2.52

2.60 2.29 2.00 1.64 1.32 1.00 3.55 3.25 2.92 2.65 2.33 2.03 5.90 5.07 4.62 4.10 3.56 2.93 5.83 5.44 4.98 4.45 3.95 3.26

3.03 2.75 2.45 2.12 1.78 1.44 4.06 3.76 3.46 3.20 2.90 2.58 6.19 5.87 5.48 5.05 4.56 3.98 6.76 6.34 5.89 5.35 4.87 4.24

1.78 1.64 1.52 1.21 0.91 0.67 2.37 2.23 2.10 1.99 1.84 1.57 3.50 3.33 3.12 2.90 2.59 2.02 3.90 3.71 3.51 3.31 3.08 2.52

1.94 1.80 1.52 1.21 0.91 0.67 2.57 2.43 2.31 2.07 1.84 1.57 3.79 3.62 3.41 3.15 2.59 2.02 4.23 4.04 3.84 3.57 3.08 2.52

1.91 1.79 1.68 1.54 1.32 1.00 2.55 2.42 2.29 2.18 2.05 1.94 3.96 3.61 3.43 3.22 3.01 2.77 4.16 4.00 3.81 3.60 3.40 3.13

2.07 1.95 1.84 1.64 1.32 1.00 2.75 2.62 2.49 2.38 2.25 2.03 4.25 3.90 3.72 3.51 3.30 2.93 4.49 4.33 4.14 3.93 3.73 3.26

2.20 2.09 1.97 1.85 1.73 1.44 2.90 2.78 2.65 2.55 2.43 2.31 4.27 4.14 3.98 3.81 3.62 3.40 4.78 4.60 4.42 4.21 4.02 3.78

2.36 2.25 2.13 2.01 1.78 1.44 3.10 2.98 2.85 2.75 2.63 2.51 4.56 4.43 4.27 4.10 3.91 3.69 5.11 4.93 4.75 4.54 4.35 4.10

3.48 3.21 2.95 2.65 2.30 1.89 4.63 4.37 4.05 3.78 3.50 3.14 7.03 6.72 6.34 5.95 5.53 5.02 7.68 7.25 6.82 6.34 5.93 5.39

2.32 2.22 2.12 2.01 1.88 1.74 3.07 2.96 2.83 2.73 2.62 2.48 4.51 4.38 4.24 4.08 3.92 3.73 5.05 4.85 4.70 4.51 4.35 4.14

2.48 2.38 2.28 2.17 2.04 1.89 3.27 3.16 3.03 2.93 2.82 2.68 4.80 4.67 4.53 4.37 4.21 4.02 5.37 5.20 5.03 4.84 4.67 4.47

Total Cap. 3.91 3.64 3.41 3.11 2.83 2.53 5.21 4.94 4.62 4.36 4.08 3.79 7.85 7.54 7.19 6.80 6.48 6.07 8.54 8.15 7.77 7.35 6.98 6.55

21° C WB SENSIBLE 28 29 DB DB 2.43 2.33 2.24 2.14 2.03 1.93 3.22 3.12 2.99 2.89 2.78 2.67 4.72 4.60 4.46 4.31 4.19 4.03 5.27 5.11 4.96 4.80 4.65 4.49

2.59 2.49 2.40 2.30 2.19 2.09 3.42 3.32 3.19 3.09 2.98 2.87 5.01 4.89 4.75 4.60 4.47 4.32 5.59 5.44 5.29 5.12 4.98 4.82

Total Cap. 4.45 4.16 3.85 3.56 3.30 3.03 5.80 5.56 5.24 4.93 4.68 4.44 8.73 8.45 8.09 7.69 7.41 7.02 9.43 9.13 8.80 8.35 7.93 7.56

22° C WB SENSIBLE 29 30 DB DB 2.57 2.46 2.35 2.25 2.15 2.06 3.38 3.28 3.15 3.04 2.94 2.85 4.94 4.83 4.69 4.54 4.43 4.29 5.48 5.36 5.23 5.06 4.90 4.76

2.73 2.62 2.51 2.41 2.31 2.22 3.58 3.48 3.35 3.24 3.14 3.05 5.23 5.12 4.98 4.83 4.72 4.58 5.81 5.69 5.56 5.38 5.23 5.09

UNIT MODEL

WATER TEMP. RISE K.

WX24MPVC-CW WX18MPVC-CW WX13MPVC-CW WX10MPVC-CW

8 oC Entering Water Temperature

4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9 4 5 6 7 8 9

17° C WB Total SENSIBLE Cap. 23 24 DB DB

18° C WB Total SENSIBLE Cap. 24 25 DB DB

ENTERING AIR TEMPERATURE °C 19° C WB 20° C WB Total SENSIBLE Total SENSIBLE Cap. 26 27 Cap. 27 28 DB DB DB DB

1.79 1.43 1.10 0.76 0.49 0.33 2.54 2.21 1.90 1.66 1.47 1.27 3.97 3.51 2.98 2.42 1.92 1.38 4.28 3.75 3.26 2.70 2.24 1.78

2.30 1.94 1.61 1.26 0.93 0.67 3.12 2.78 2.49 2.19 1.95 1.66 4.80 4.37 3.93 3.40 2.86 2.29 5.22 4.71 4.25 3.69 3.09 2.52

2.72 2.40 2.09 1.75 1.44 1.13 3.69 3.39 3.10 2.81 2.50 2.15 5.60 5.25 4.86 4.41 3.91 3.27 6.09 5.68 5.24 4.72 4.21 3.61

1.62 1.43 1.10 0.76 0.49 0.33 2.17 2.04 1.90 1.66 1.47 1.27 3.23 3.04 2.83 2.42 1.92 1.38 3.60 3.38 3.17 2.70 2.24 1.78

1.78 1.43 1.10 0.76 0.49 0.33 2.37 2.21 1.90 1.66 1.47 1.27 3.52 3.33 2.98 2.42 1.92 1.38 3.93 3.71 3.26 2.70 2.24 1.78

1.79 1.65 1.53 1.26 0.93 0.67 2.37 2.23 2.11 2.00 1.95 1.66 3.50 3.33 3.15 2.95 2.74 2.29 3.91 3.70 3.52 3.30 3.07 2.52

1.95 1.81 1.61 1.26 0.93 0.67 2.57 2.43 2.32 2.19 1.95 1.66 3.79 3.62 3.44 3.24 2.86 2.29 4.23 4.03 3.85 3.63 3.09 2.52

2.07 1.95 1.84 1.71 1.44 1.13 2.75 2.63 2.51 2.40 2.28 2.15 4.03 3.89 3.74 3.56 3.38 3.14 4.50 4.34 4.16 3.96 3.77 3.54

2.23 2.11 2.00 1.75 1.44 1.13 2.95 2.83 2.71 2.60 2.48 2.15 4.32 4.18 4.03 3.85 3.66 3.27 4.83 4.67 4.49 4.29 4.10 3.61

3.18 2.86 2.56 2.25 1.88 1.55 4.24 3.95 3.65 3.36 3.09 2.78 6.42 6.08 5.70 5.27 4.80 4.22 6.94 6.59 6.22 5.76 5.24 4.71

2.21 2.09 1.98 1.86 1.73 1.55 2.91 2.79 2.68 2.57 2.46 2.35 4.27 4.13 3.99 3.82 3.64 3.43 4.75 4.60 4.46 4.28 4.08 3.89

2.37 2.25 2.14 2.02 1.88 1.55 3.11 2.99 2.88 2.77 2.66 2.55 4.56 4.42 4.28 4.11 3.94 3.72 5.07 4.93 4.79 4.61 4.41 4.22

Total Cap. 3.65 3.33 3.07 2.75 2.47 2.11 4.84 4.54 4.25 3.89 3.63 3.33 7.25 6.92 6.28 6.19 5.81 5.31 7.91 7.57 7.21 6.71 6.25 5.78

21° C WB SENSIBLE 28 29 DB DB 2.33 2.22 2.12 2.00 1.91 1.79 3.07 2.96 2.84 2.71 2.62 2.50 4.49 4.35 4.11 4.08 3.94 3.76 5.01 4.88 4.74 4.54 4.38 4.20

2.49 2.38 2.28 2.16 2.07 1.95 3.28 3.16 3.04 2.91 2.82 2.70 4.78 4.64 4.40 4.37 4.23 4.05 5.34 5.21 5.07 4.87 4.71 4.53

Total Cap. 4.20 3.90 3.59 3.32 3.06 2.75 5.51 5.24 4.94 4.61 4.35 4.12 8.23 8.00 7.56 7.23 6.91 6.55 8.96 8.64 8.30 7.84 7.43 6.96

22° C WB SENSIBLE 29 30 DB DB 2.48 2.37 2.26 2.16 2.07 1.97 3.26 3.15 3.04 2.91 2.82 2.73 4.75 4.66 4.49 4.36 4.25 4.12 5.30 5.17 5.04 4.86 4.71 4.54

Performance Data – Standard Conditions in Heating Heating Capacity (kW) - (at Turbo Fan Speed) UNIT MODEL

WX10MPVC-CW

WX13MPVC-CW

WX18MPVC-CW

WX24MPVC-CW

Water flow rate l/h

20

30

318 472 740 955 1170 1380 1590 425 646 990 1270 1555 1840 2120 318 530 740 1007 1170 1380 1590 425 710 1088 1270 1555 1840 2120

2.50 2.68 2.83 2.88 2.92 2.94 2.96 2.93 3.11 3.23 3.29 3.32 3.34 3.37 4.17 4.75 5.01 5.19 5.26 5.32 5.37 4.86 5.38 5.66 5.76 5.83 5.88 5.93

3.77 4.03 4.26 4.34 4.40 4.43 4.46 4.42 4.68 4.87 4.96 5.00 5.04 5.07 6.29 7.15 7.55 7.82 7.93 8.01 8.08 7.32 8.10 8.53 8.67 8.78 8.86 8.93

Temp. diff. °K = Water entering temp.-Air entering temp. 40 50 60 5.05 5.41 5.71 5.82 5.90 5.94 5.98 5.92 6.28 6.53 6.64 6.70 6.75 6.80 8.43 9.59 10.12 10.48 10.62 10.74 10.83 9.80 10.86 11.43 11.62 11.77 11.88 11.97

6.34 6.78 7.16 7.30 7.39 7.44 7.50 7.43 7.87 8.19 8.33 8.40 8.46 8.52 10.57 12.02 12.69 13.14 13.32 13.46 13.58 12.29 13.61 14.34 14.57 14.76 14.89 15.01

7.62 8.15 8.61 8.78 8.88 8.95 9.01 8.93 9.47 9.84 10.01 10.10 10.18 10.25 12.71 14.45 15.26 15.80 16.02 16.19 16.33 14.78 16.37 17.24 17.52 17.75 17.91 18.05

70 8.88 9.50 10.03 10.23 10.35 10.43 10.50 10.41 11.03 11.47 11.77 11.77 11.86 11.94 14.81 16.84 17.79 18.42 18.66 18.86 19.03 17.23 19.07 20.09 20.42 20.68 20.87 21.04

2.63 2.53 2.42 2.32 2.23 2.13 3.46 3.35 3.24 3.11 3.02 2.93 5.03 4.94 4.78 4.65 4.54 4.41 5.62 5.50 5.37 5.19 5.04 4.87


Pressure Drop – Standard Conditions

UNIT MODEL WX10MPVC/H-CW WX13MPVC/H-CW WX18MPVC/H-CW WX24MPVC/H-CW

CAPACITY TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

FAN SPEED T 1 1 1 1 1 1 1 1

H 0.80 0.79 0.72 0.73 0.90 0.88 0.85 0.84

M 0.65 0.64 0.56 0.58 0.81 0.79 0.73 0.71

L 0.59 0.58 0.50 0.51 0.69 0.65 0.59 0.57


Performance Data – District Cooling Conditions Cooling Capacity (kW) 5.5 oC Entering Water Temperature UNIT MODEL

WX10MPVC-DW

WX13MPVC-DW

WX18MPVC-DW

WX24MPVC-DW

WATER TEMP. RISE K. 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0

Total Cap. 2.48 2.37 1.85 3.00 2.86 2.15 4.29 4.10 3.19 5.15 4.94 4.17

17° C WB SENSIBLE 23 DB 24 DB 2.01 2.14 1.94 2.07 1.58 1.69 2.40 2.56 2.31 2.46 1.83 1.97 3.51 3.74 3.38 3.61 2.74 2.95 4.07 4.34 3.93 4.19 3.40 3.51

ENTERING AIR TEMPERATURE °C 18° C WB 19° C WB SENSIBLE Total SENSIBLE 24 DB 25 DB Cap. 26 DB 27 DB 2.26 2.40 3.44 2.63 2.77 2.19 2.33 3.35 2.57 2.71 1.92 2.02 3.03 2.35 2.46 2.70 2.86 4.16 3.14 3.30 2.62 2.78 4.05 3.06 3.23 2.35 2.51 3.70 2.82 2.98 3.93 4.17 5.95 4.57 4.82 3.82 4.05 5.79 4.46 4.71 3.27 3.49 5.07 3.98 4.19 4.55 4.82 7.05 5.26 5.55 4.43 4.70 6.88 5.15 5.43 4.01 4.26 6.33 4.78 5.04

Total Cap. 3.90 3.82 3.55 4.71 4.60 4.28 6.74 6.59 5.98 7.96 7.80 7.29

20° C WB SENSIBLE 27 DB 28 DB 2.84 2.99 2.79 2.93 2.60 2.72 3.39 3.56 3.33 3.49 3.11 3.27 4.95 5.20 4.85 5.10 4.44 4.65 5.68 5.97 5.58 5.86 5.24 5.51

Total Cap. 2.65 2.19 2.00 3.24 2.65 2.39 4.44 3.75 3.46 5.54 4.60 4.28

ENTERING AIR TEMPERATURE °C 18° C WB 19° C WB SENSIBLE Total SENSIBLE 24 DB 25 DB Cap. 26 DB 27 DB 2.04 2.16 3.13 2.43 2.54 1.74 1.86 2.73 2.15 2.28 1.62 1.73 2.59 2.05 2.17 2.47 2.63 3.83 2.92 3.08 2.07 2.22 3.29 2.56 2.71 1.92 2.05 3.13 2.45 2.60 3.47 3.69 5.29 4.14 4.37 3.00 3.22 4.71 3.74 3.96 2.82 3.02 4.43 3.55 3.77 4.18 4.44 6.51 4.92 5.19 3.55 3.80 5.68 4.36 4.60 3.34 3.58 5.42 4.19 4.43

Total Cap. 3.61 3.23 3.11 4.39 3.92 3.76 6.12 5.58 5.36 7.44 6.78 6.44

20° C WB SENSIBLE 27 DB 28 DB 2.66 2.79 2.40 2.54 2.32 2.45 3.19 3.36 2.88 3.03 2.78 2.93 4.55 4.79 4.18 4.41 4.04 4.27 5.36 5.64 4.92 5.15 4.70 4.96

Total Cap. 2.22 2.01 1.80 2.69 2.42 2.12 3.80 3.47 3.10 4.68 4.25 3.83

ENTERING AIR TEMPERATURE °C 18° C WB 19° C WB SENSIBLE Total SENSIBLE 24 DB 25 DB Cap. 26 DB 27 DB 1.76 1.89 2.75 2.17 2.30 1.63 1.75 2.56 2.04 2.17 1.49 1.60 2.38 1.92 2.05 2.11 2.26 3.33 2.60 2.75 1.94 2.08 3.12 2.45 2.61 1.76 1.89 2.87 2.30 2.44 3.06 3.28 4.75 3.78 4.00 2.85 3.05 4.40 3.55 3.77 2.61 2.81 4.10 3.36 3.57 3.62 3.87 5.71 4.41 4.66 3.34 3.58 5.40 4.19 4.44 3.08 3.31 5.00 3.93 4.18

Total Cap. 3.24 3.09 2.89 3.92 3.74 3.53 5.60 5.30 4.99 6.68 6.40 6.10

20° C WB SENSIBLE 27 DB 28 DB 2.42 2.56 2.32 2.45 2.19 2.32 2.90 3.06 2.78 2.93 2.64 2.79 4.21 4.45 4.01 4.24 3.82 4.04 4.88 5.15 4.70 4.96 4.50 4.76

Total Cap. 2.97 2.87 2.48 3.59 3.47 3.09 5.14 4.97 4.15 6.12 5.94 5.32

6 oC Entering Water Temperature UNIT MODEL

WX10MPVC-DW

WX13MPVC-DW

WX18MPVC-DW

WX24MPVC-DW

WATER TEMP. RISE K. 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0

Total Cap. 2.04 1.56 1.31 2.60 1.79 1.14 3.50 2.70 2.29 4.52 3.34 2.86

17° C WB SENSIBLE 23 DB 24 DB 1.72 1.83 1.38 1.49 1.23 1.31 2.13 2.26 1.61 1.74 1.14 1.14 2.98 3.20 2.42 2.62 2.17 2.29 3.65 3.91 2.86 3.08 2.57 2.78

6.5 oC Entering Water Temperature UNIT MODEL

WX10MPVC-DW

WX13MPVC-DW

WX18MPVC-DW

WX24MPVC-DW

WATER TEMP. RISE K. 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0 8.0 8.5 9.0

Total Cap. 1.63 1.37 1.92 1.14 2.82 2.37 3.47 2.95 -

17° C WB SENSIBLE 23 DB 24 DB 1.44 1.56 1.27 1.37 1.70 1.84 1.14 1.14 2.52 2.72 2.23 2.37 2.97 3.20 2.64 2.86 -

Pressure Drop – District Cooling Conditions UNIT MODEL WX10MPVC/H-DW WX13MPVC/H-DW WX18MPVC/H-DW WX24MPVC/H-DW

CAPACITY

FAN SPEED T

H

M

L

TOTAL

1

0.87

0.63

0.70

SENSIBLE

1

0.86

0.75

0.70 0.65

TOTAL

1

0.81

0.71

SENSIBLE

1

0.81

0.71

0.65

TOTAL

1

0.91

0.83

0.67

SENSIBLE

1

0.90

0.81

0.65

TOTAL

1

0.87

0.75

0.62

SENSIBLE

1

0.87

0.75

0.62


Unit Dimensions

Wiring Diagram With LCD Wireless Control

UNICO CONSUMER PRODUCTS CO., LTD.

With Wired Digital Room Thermostat Control

136, 136/1 2nd Floor, Phrayasureant Rd., Bangchan ,Klongsamwa, Bangkok 10510, Thailand Tel : 662-517 1819 ; 662-517 1733 ; 662- 919 0823-5 Fax : 662-517 8530 E-mail: sales@amena-air.com Website: www.amena-air.com


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.