Multi V Indoor,09.06.11

Page 37

6. Capacity Tables

Cassette 2-way

6.1 Cooling Capacity

Capacity Index

5.6

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, 째C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.4

4.2

12

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.3

4.1

14

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.2

4.1

16

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.1

4.0

18

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.0

4.0

20

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.9

3.9

21

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.8

3.9

23

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.7

3.8

25

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.6

4.2

6.6

3.8

27

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.1

6.6

3.7

29

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.0

6.5

3.7

31

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.9

6.4

3.6

33

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.2

3.9

6.3

3.6

35

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.0

3.8

6.2

3.5

37

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

5.9

3.7

6.1

3.5

39

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.7

3.9

5.8

3.7

6.0

3.4

Outdoor air temp. (DB, 째C)

Notes: TC: Total Capacity(kW)

2-7

Cooling capacity

SHC: Sensible Heat Capacity(kW)

Indoor unit

Ceiling Cassette 2-way


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.