Inside Design Conditions - Summer and Winter Recommended indoor design conditions Sponsored Links

Summer

Extra

Winter

Commercial

With Humidification

Without Humidification

Application Dry Bulb Relative Dry Bulb Relative Dry Bulb Relative Temperature Humidity Temperature Humidity Temperature Humidity

Dry Bulb Temperature

(oF)

(%)

(oF)

(%)

(oF)

(%)

(oF)

General Comfort Apartment, House, Hotel, Office, Hospital, School . .

74 - 76

50 - 45

77 - 79

50 - 54

74 - 76

35 - 30

75 - 77

Retail Shops for shorter terms occupancy Bank, barber shop, beauty shop, department store, supermarket ..

76 - 78

50 - 45

78 - 80

50 - 45

72 - 74

35 - 30

73 - 75

High latent load and low sensible load applications

76 - 78

55 - 50

78 - 80

65 - 50

72 - 74

40 - 35

74 - 76


Summer

Extra

Winter

Commercial

With Humidification

Without Humidification

Application Dry Bulb Relative Dry Bulb Relative Dry Bulb Relative Temperature Humidity Temperature Humidity Temperature Humidity

Dry Bulb Temperature

(oF)

(%)

(oF)

(%)

(oF)

(%)

(oF)

77 - 80

55 - 45

80 - 85

60 - 50

68 - 72

35 - 30

70 - 74

Auditoriums, churches, bars, restaurants, kitchens Factories Work shops, assembly areas, machining rooms ..