DUCTED PILT-GENERAL

Page 1

FORM NO. R/S2-0106

SPLIT SYSTEM RILE A - SAKB SERIES HIGH EFFICIENCY DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ

The RILE A series is the latest introduction in the range of RHEEM's split airconditioners with the most reliable unit design available. All air handler models are only 11 - 19

• EXPANSION DEVICE - Capillary / Flow check orifice. • FILTERS - woven synthetic / Half inch aluminium(optional) permanent washable filters are standard on all units.

inches high. These units can be matched with all • INSULATION -

RHEEM condensing units.

5mm thick irradiated grade EPE, fire

retardent. Engineering Features • EVAPORATOR COIL Air Handler

grooved copper tubes and aluminium fins mechanically

• CABINET - Made from heavy gauge galvanized steel, and powder coated by electrostatic painting process. • MOT OR -

Coils are constructed with inner

Permanently

lubricated with

bonded to the tubes for maximum heat transfer capabilities. •

thermal

overload protection & ventilated type motors are mounted inside of insulated cabinet to reduce motor noise and provide a neat looking installation. • BLOWER - Double inlet, double width, forward curved aluminum/GI construction dynamically balanced for low noise & high performance.

REFRIGERANT

CONNECTIONS

-

Field

piping

connections, RILE 018 A to 030 A flare & RILE 036 A to 072 A sweat type, are made through side of the unit. • DRAIN PAN -

Insulated galvanized steel drain pan is

designed to trap condensate drain. • SE RVICE ACCESS- For RILE 036A to 072A removable panels at the bottom of the unit, can be easily removed for access to motor & blowers. For RILE 018A to 030A entire fan &

• LOW PROFILE - Allow for horizontal installation in most

motor section can be separated from the coil section by wing

standard drop ceiling application, and the movement of units

nuts for servicing and maintenance.

through most standard doorways for addition or replacement work.

• TESTING - All units are run tested at the factory prior to shipment.


Engineering Features Condensing Units

• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.

The RHEEM Classic X High Efficiency SAKB -Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications. The RHEEM Classic X SAKB - Condensing Units are the result of an ongoing development program for improved efficiencies. With SEER's ranging to 10.50, these units continue a tradition of high efficiency.

• Compressors have an internal pressure-relief assembly to protect against excessive pressure differential. • All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations. • Cabinet is constructed of powder painted galvanized steel. The full wrap around louvered grille protects the coil from damage.This cabinet is also able to with stand 1000 hours of salt spray test.

• Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.

• Copper Tube - Aluminium Fin coils are used on all models.

• Air is discharged upward away from bushes and shrubs. The discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.

• The control box is located in the top corner of the cabinet providing for easy access through a service panel. • Service valves are standard on all models.

• Exclusive Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.

• Power and control wiring are kept separate. • Every unit is factory charged and tested.

• All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil. • Single speed motor is designed for low speed, quiet energysaving operation. • All Units tested in accordance with A.R.I. standard

• Separate compressor compartment for easy service access. • Drawn, painted base pan for extra corrosion resistance and sound reduction. • H.P. Cutout safety control is a standard feature on all the models.

no.2-10-81-360-86

CONDENSING UNITS SAKB SERIES

DIMENSIONS AND OPERATING WEIGHT

AIR HANDLING UNITS RILE A SERIES

RILE - 018A/024A/030A

CONTROL BOX (RILE 018A&024A)

CONTROL BOX (RILE 030A)

C1

DRAIN

B

HEIGHT

DEPTH AIR DISCHARGE ALLOW 60º[1524 mm] CLEARANCE

C2 WIDTH (30 A) WIDTH (18A & 24A ONLY) ACCESS PANEL

RILE - 036A/042A/048A/060A/072A DEPTH A CONTROL BOX

HEIGHT

C1

B

ALLOW 24º[610 mm] ACCESS CLEARANCE

AIR INLETS (LOUVERS) ALLOW 12º[305 mm] MIN. CLEARANCE 3 SIDES

C2

FRONT VIEW

CONDENSING UNITS

Model

SAKB 018 SAKB 024 SAKB 030 SAKB 036 SAKB 042 SAKB 048 SAKB 060 SAKB 065

Height H (Inches) 17.0 17.0 19.0 19.0 19.0 23.0 23.0 23.0

DRAIN

C3 SIDE VIEW

AIR HANDLING UNITS

Length L (Inches) 36.0 36.0 36.0 41.0 41.0 44.0 44.0 44.0

Width W (Inches) 23.0 23.0 23.0 27.0 27.0 31.0 31.0 31.0

Weight (Lbs)

Model

Height

Depth

Width

A

B

C1

C2

C3

130 135 145 170 180 200 230 230

RILE 018A

11.0

21.0

47.0

33.0

4.7

1.40

1.00

--

65

RILE 024A

11.0

21.0

47.0

33.0

4.7

1.40

1.00

--

66

RILE 030A

12.0

26.5

41.0

34.0

6.6

1.40

1.00

--

68

RILE 036A

15.0

34.0

30.0

10.6

9.6

1.25

1.25

5.60

85

RILE 042A

17.5

34.0

30.0

13.5

11.0

1.00

1.60

4.40

90

RILE 048A

17.5

34.0

30.0

13.5

11.0

1.00

1.60

4.40

90

RILE 060A

19.0

33.0

30.0

12.6

11.8

0.73

2.00

4.90

110

RILE 072A

19.0

37.0

30.0

13.5

12.5

3.75

2.00

2.65

115

(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)

Weight (Lbs)


EVAPORATOR AIR ENTERING AIR TEMP

AMBIENT TEMP : 115 deg F

724

Note:

* **

FULL LOAD CURRENT

CIRCUIT BREAKER SIZE

For shipping weight, add 10 Lbs to net weight Power supply : 1-50-220/240 & 3-50-380/415

NET WEIGHT (Lbs)*

NUMBER OF FANS

COIL FACE AREA

ELECTRICAL DATA

POWER INPUT

**POWER SUPPLY

EXPANSION DEVICE

1.5

AIR HANDLING UNIT

2

AIR HANDLING UNIT

LBS 130

AIR HANDLING UNIT

CONDENSING UNIT

1 65

CONDENSING UNIT

NOS.

5.0

CONDENSING UNIT

SQ.FT

7.9

CONDENSING UNIT

AMPS

20 1.3

15

AIR HANDLING UNIT

AMPS

CONDENSING UNIT

AIR HANDLING UNIT

1.60

0.26 KW

AIR HANDLING UNIT

CONDENSING UNIT

1-50-220

1-50-220

CONDENSING UNIT

AIR HANDLING UNIT

1

47

45

43

0.10

130

66

1

2

5.0

1.8

7.9

1.3

20

15

1.60

0.26

1-50-220

1-50-220

1

1

48

46

44

0.10

800

559 600

665

11.40

14.40

12.40

15.40

12.50

16.30

13.60

17.40

SAKB 018

RILE 024A

523

1

PH-HZ-VOLTS

dbA

INCHES OF WC

CFM

11.10

13.20

TMBH SMBH

10.30

14.20

TMBH SMBH

11.50

SMBH

TMBH

NUMBER OF CIRCUITS FOR THE AIR HANDLING UNIT

HIGH

MEDIUM

LOW

HIGH

MEDIUM

LOW

76DB / 63 WB Deg F

80DB / 67 WB Deg F

76DB / 63 WB Deg F

11.60 15.00

SMBH

16.10

NUMBER OF COMPRESSORS

NOISE LEVEL(AHU)

ESP

AIR FLOW PERFORMANCE

EVAPORATOR AIR ENTERING AIR TEMP

AMBIENT TEMP : 95 deg F

TMBH

SAKB 018

80DB / 67 WB Deg F

RILE 018A

CONDENSING UNIT MODEL

135

66

1

2

6.1

1.8

10.0

1.3

20

15

2.00

0.26

1-50-220

1-50-220

1

1

48

46

44

0.10

800

724

665

15.30

18.20

15.70

19.50

16.70

20.60

17.20

22.00

SAKB 024

RILE 024A

145

68

1

2

9.1

2.4

11.9

1.3

25

15

2.40

0.26

1-50-220

1-50-220

1

1

49

47

45

0.10

1000

905

835

17.00

21.20

17.60

22.70

18.20

24.00

19.70

25.80

SAKB 030

RILE 030A

145

85

1

1

9.1

2.4

11.9

2.0

25

15

2.40

0.4

1-50-220

1-50-220

1

1

50

48

46

0.10

1200

1088

1029

17.80

22.40

19.40

23.90

19.70

25.40

22.00

27.10

SAKB 030

RILE 036A

TABLE FOR TECHNICAL DATA

AIR HANDLING UNIT MODEL

170

85

1

1

11.0

2.4

14.3

2.0

30

15

2.80

0.4

1-50-220

1-50-220

CAPILLARY

1

1

50

48

46

0.10

1200

1088

1029

22.40

26.80

23.30

28.80

24.80

29.50

25.70

32.50

SAKB 036

RILE 036A

170

90

1

1

11.0

4.7

14.3

2.5

30

15

2.80

0.5

1-50-220

1-50-220

1

1

51

49

47

0.20

1380

1265

1112

23.10

28.40

25.00

30.30

25.90

32.20

26.40

34.30

SAKB 036

RILE 042A

180

90

1

1

11.0

4.7

6.6

2.5

15

15

3.90

0.5

3-50-380

1-50-220

1

1

51

49

47

0.20

1380

1265

1112

24.90

29.60

25.40

32.00

26.40

34.20

27.10

36.70

SAKB 042

RILE 042A

180

90

1

1

11.0

4.7

6.6

2.5

15

15

3.90

0.5

3-50-380

1-50-220

1

1

53

51

49

0.20

1600

1441

1265

25.80

31.90

27.20

34.20

28.80

36.10

30.00

38.60

SAKB 042

RILE 048A

200

90

1

1

15.8

4.7

7.5

2.5

15

15

4.40

0.5

3-50-380

1-50-220

1

1

53

51

49

0.20

1600

1441

1265

29.50

35.50

30.30

37.90

32.30

40.20

33.10

42.90

SAKB 048

RILE 048A

230

110

1

1

15.8

7.5

8.8

2.5

15

15

5.20

0.5

3-50-380

1-50-220

1

1

55

53

51

0.20

2000

1930

1865

36.70

44.20

40.20

47.20

42.00

50.10

43.50

53.40

SAKB 060

RILE 060A

230

115

1

1

15.8

7.5

11.0

5

20

15

6.50

1.1

3-50-380

1-50-220

ORIFICE

1

1

58

56

53

0.20

2400

2335

2223

46.70

55.80

51.50

59.50

54.20

63.30

55.80

67.50

SAKB 065

RILE 072A


Condensing Unit Refrigerant Line Size Information Liquid Line Size System

Line

Model

Size

Numbers

(inch O.D.)

Outdoor Unit Below Indoor Coil

Total Length - Feet (m) 25 [7.26]

50 [15.24]

[mm] 018

Liquid Line Size

Outdoor Unit Above Indoor Coil

1/4* [6.35]

Total Length - Feet (m)

100 [30.48] 125 [38.10] 150 [45.72]

25 [7.62]

50 [15.24]

Vertical Separation - Feet [m] 25 [7.62]

50 [15.24]

5/16 [7.94] 1/4* [6.35]

75 [22.86]

25 [7.62]

75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]

Vertical Separation - Feet [m]

70 [21.34]

25 [7.62]

36 [10.97] 42 [12.80]

48 [14.63] 54 [16.46]

34 [10.36] 44 [13.41]

54 [16.46] 64 [19.51]

50 [15.24]

25 [7.62]

23 [7.01]

8[2.44] 36 [10.97]

30 [9.14]

24 [7.32]

18 [5.49]

38 [11.58]

28 [8.53]

18 [5.49]

8 [2.44]

39 [11.89]

25 [7.62]

11 [3.35]

23 [7.01]

024 5/16 [7.94] 1/4* [6.35] 030

24 [7.32] 25 [7.62]

5/16 [7.94]

50 [15.24] 19 [5.79]

25 [7.62] 33 [10.06] 47 [14.33]

3/8 [9.53] 5/16* [7.94]

48 [14.63]

61 [18.59]

50 [15.24]

11 [3.35] 25 [7.62]

50 [15.24]

70 [21.34]

25 [7.62]

50 [15.24]

75 [22.86]

25 [7.62]

44 [13.41]

53 [16.15] 61 [18.59]

23 [7.01]

15 [4.57]

57 [17.37] 25 [7.62]

23 [7.01]

25 [7.62]

23 [7.01]

25 [7.62]

28 [8.53]

9 [2.74]

036 3/8 [9.53] 5/16* [7.94]

34 [10.36] 40 [12.19]

46 [14.02] 52 [15.85]

38 [11.58]

32 [9.75]

26 [7.92]

20 [6.10]

40 [12.19] 33 [10.66]

26 [7.92]

19 [5.79]

9 [2.74]

042 3/8 [9.53] 3/8* [9.53]

32 [9.75]

39 [11.89]

46 [14.02] 53 [16.15] 70 [21.34]

19 [5.79]

11 [3.35]

3 [.91]

048 1/2 [12.7] 060

3/8* [9.53]

065

1/2* [12.7]

25 [7.62]

48 [14.63]

37 [11.28]

39 [11.89]

38 [11.58]

41 [12.50]

61 [18.59] 72 [21.95] 35 [10.67]

35 [10.67] 33 [10.06] 25 [7.62]

23 [7.01]

11 [3.35]

3 [.91] 37 [11.28] 34 [10.36] 31 [9.45]

*Standard line size

NOTES :

NOTES

1. This chart is applicable for condensing units. Example 1:A 2.5 ton [nom.] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [nom.] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge. 5. No changes required for flow-check pistons or expansion valve coils.

1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes required for expansion valve coils. 4. Coils with flow-check pistons may require change of piston size,only incase of longer pipe lengths 5. Do not exceed table values for capillary tube coils. 6. Always use the smallest liquid line possible to minimize system charge. 7. Chart may be used to size horizontal runs.

Vapor Line Length / Size versus Capacity Multiplier System Model Numbers

018

024

-5/ " 8

Vapor Line Run-feet [m]

25' [7.62]

50' [15.24]

100' [30.48]

150' [45.72]

Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional

[15.88 mm] O.D. Standard 3/ " [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98

.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98

030

036

042

048

060/065

5/ " 8

[15.88mm] O.D Optional

7/ " 8

[22.23 mm] O.D. Optional

3/ " 4

[19.05mm] O.D. Standard

11 / " 8

[28.58mm] O.D. Standard

7/ " 8

[22.23 mm] O.D. Optional

13/ " 8

[34.94mm] O.D. Optional

1.00 1.01 .99 1.00 .97 .99 .95 .97

1.00 1.01 .98 1.00 .96 .99 .93 .97

1.00 1.01 .97 1.00 .94 .98 .90 .96

.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00

.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99

NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity. [ ] Designates Metric Conversions Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.

" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice. "


FORM NO. M2-06-B3

SPLIT SYSTEM RIZE - SAKB SERIES DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ

The RIZE Series is the latest introduction in the range of

• FILTERS - Woven synthetic, permanent washable filters are

RHEEM split airconditioners with the most reliable unit design

standard on all units. Optional - half inch aluminium washable

available. All air handler models are only 11 - 18 inches high.

filters.

These units can be matched with all the RHEEM's condensing units.

• INSULATION - 5mm thick irradiated grade EPE, fire retardent.

Engineering Features Air Handler

• EVAPORATOR COIL - Coils are constructed with inner grooved copper tubes and aluminium fins mechanically

• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are

bonded to the tubes for maximum heat transfer capabilities.

available optionally for use when units are to be installed

• REFRIGERANT

within conditioned space.

connections, sweat type, are made through side of the unit.

• MOTOR - Inherently protected, mounted on resilient

• DRAIN PAN - Insulated galvanized steel drain pan is

neoprene rubber mountings, to reduce noise level.

designed to trap condensate drain. The drain connections are

• BLOWER - Centrifugal, forward curved, double inlet double width type, made from heavy duty aluminium sheet.

• LOW PROFILE - Allow for horizontal installation in most standard drop ceiling application, and the movement of units through most standard doorways for addition or replacement work.

• EXPANSION DEVICE - Capillary

CONNECTIONS

-

Field

piping

on two sides of the unit to facilitate the site conditions for the convenience of installation.

• SERVICE ACCESS - Removable panels at the bottom of the unit, can be easily removed for access to motor & blowers. The entire fan and motor section can be separated from the coil section for servicing and maintenace.

• TESTING - All units are run tested at the factory prior to shipment.


Engineering Features Condensing Units

• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.

The RHEEM Classic X High Efficiency SAKB -Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications. The RHEEM Classic X SAKB - Condensing Units are the result of an ongoing development program for improved efficiencies. With SEER's ranging to 10.50, these units continue a tradition of high efficiency.

• Compressors have an internal pressure-relief assembly to protect against excessive pressure differential. • All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations. • Cabinet is constructed of powder painted galvanized steel. The full wrap around louvered grille protects the coil from damage.This cabinet is also able to with stand 1008 hours of salt spray test.

• Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.

• Copper Tube - Aluminium Fin coils are used on all models.

• Air is discharged upward away from bushes and shrubs. The discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.

• The control box is located in the top corner of the cabinet providing for easy access through a service panel. • Service valves are standard on all models.

• Exclusive Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.

• Power and control wiring are kept separate. • Every unit is factory charged and tested.

• All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil. • Single speed motor is designed for low speed, quiet energysaving operation. • All Units tested in accordanc with A.R.I. standard

• Separate compressor compartment for easy service access. • Drawn, painted base pan for extra corrosion resistance and sound reduction. • H.P. Cutout safety control is a standard feature on all the models.

no.2-10-81-360-86

DIMENSIONS AND OPERATING WEIGHT

AIR DISCHARGE ALLOW 60º[1524 mm] CLEARANCE

CONDENSING UNITS

Model

ACCESS PANEL

ALLOW 24º[610 mm] ACCESS CLEARANCE

AIR INLETS (LOUVERS) ALLOW 12º[305 mm] MIN. CLEARANCE 3 SIDES

SAKB 018 SAKB 024 SAKB 030 SAKB 036 SAKB 042 SAKB 048 SAKB 060 SAKB 065

Height H (Inches) 17.0 17.0 19.0 19.0 19.0 23.0 23.0 23.0

Length L (Inches) 36.0 36.0 36.0 41.0 41.0 44.0 44.0 44.0

Width W (Inches) 23.0 23.0 23.0 27.0 27.0 31.0 31.0 31.0

Weight (Lbs)

130 135 145 170 180 200 230 230

AIR HANDLING UNITS Model C E

AUXILIARY DRAIN PIPE

DRAIN PIPE G D

REFRIGERANT PIPE CONNECTIONS

PLAN

A

F

ELEVATION

B

R H SIDE VIEW

RIZE RIZE RIZE RIZE RIZE RIZE RIZE RIZE

018 024 030 036 042 048 060 A 072 A

A

B

C

D

E

F

G

(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)

35.9 35.9 35.9 42.6 42.6 42.6 44.0 44.0

10.9 10.9 10.9 15.0 15.0 15.0 18.0 18.0

24.7 24.7 24.7 28.9 28.9 28.9 28.9 30.9

34.8 34.8 34.8 41.4 41.4 41.4 42.8 42.8

9.7 9.7 9.7 10.4 10.4 10.4 10.4 10.4

7.5 7.5 7.5 9.4 9.4 9.4 9.4 9.4

33.3 33.3 33.3 40.1 40.1 40.1 41.1 41.1

Weight (Lbs) 49 50 51 92 95 97 113 114

RIZE 018/024/030/036/042/048/060A/072A


EVAPORATOR ENTERING AIR TEMP.

AMBIENT TEMP. 115 F 18.0

CIRCUIT BREAKER SIZE

POWER INPUT

FULL LOAD CURRENT

2

2

CONDENSING UNIT

LBS

130

130

1 50

1 49

CONDENSING UNIT

AIRHANDLING UNIT

NOS.

5.0

5.0

CONDENSING UNIT

AIRHANDLING UNIT

SQ. FT

7.9 1.5

7.9 1.5

0.6

0.6

15 20

15 20

CONDENSING UNIT

AMPS.

AMPS.

AIRHANDLING UNIT

AIRHANDLING UNIT

CONDENSING UNIT

AIRHANDLING UNIT

1.60

0.12

1.60

0.12

KW

AIRHANDLING UNIT

CONDENSING UNIT

1-50-220

1-50-220

1-50-220

1-50-220

CONDENSING UNIT

AIRHANDLING UNIT

* Optional power supply : 3-50-380/415 available.

NET WEIGHT

NUMBER OF FANS

COIL FACE AREA

DATA

ELECTRICAL

** POWER SUPPLY

EXPANSION DEVICE

PH - HZ - VOLTS

145

51

1

2

9.1

1.8

11.9

0.6

25

15

2.60

0.12

1-50-220

1-50-220

1

1

46

44

42

0.1

1000

905

835

14.9

20.8

15.4

22.3

16.0

23.9

16.6

25.2

SAKB 030

RIZE 030

145

92

1

2

9.1

2.9

11.9

2.0

25

15

2.60

0.40

1-50-220

170

92

1

2

11.0

2.9

14.3

2.0

30

15

2.83

0.40

1-50-220*

1-50-220

1

1

47

45

43

0.1

1200

1088

1029

20.5

26.3

21.3

28.5

22.6

30.2

23.5

32.3

SAKB 036

RIZE 036

CAPILLARY

1-50-220

1

1

47

45

43

0.1

1200

1088

1029

16.3

22.2

17.8

23.7

18.0

25.2

20.0

26.8

SAKB 030

RIZE 036

** Power Supply : 1-50-220/240 & 3-50-380/415

135

50

1

2

6.1

1.5

10.0

0.6

20

15

2.10

0.12

1-50-220

1-50-220

1 1

1 1

1 1

HIGH

MEDIUM

NUMBER OF COMPRESSORS

NOISE LEVEL (AHU)

NUMBER OF CIRCUITS FOR THE AIRHANDLING UNIT

41

41

40 43

0.1

0.1

0.1

45

800

800

600

43

665 724

665 724

523 559

45

dbA

INCHES WC.

CFM

13.9

14.3 10.4

10.0

13.1

SMBH

TMBH

19.3 14.5

11.3

14.2

9.4

14.1

TMBH

SMBH

15.6

11.5

10.5

SMBH

TMBH

42

LOW

SELECTED

HIGH

MEDIUM

LOW

76DB / 63WB F

80DB / 67WB F

76DB / 63WB F

16.0 21.3

12.4 16.1

10.6 14.9

SMBH

44

EXTERNAL STATIC PRESSURE

AIR FLOW PERFORMANCE

EVAPORATOR ENTERING AIR TEMP.

AMBIENT TEMP. 95 F

21.8

17.2

15.9

80DB / 67WB F

SAKB 024

SAKB 018

SAKB 018

TMBH

CONDENSING UNIT MODEL

RIZE 024

RIZE 024

RIZE 018

AIR HANDLING UNIT MODEL

TABLE FOR TECHNICAL DATA

170

95

1

2

11.0

3.1

14.3

2.4

30

15

2.83

0.48

1-50-220*

1-50-220

1

1

48

46

44

0.25

1350

1265

1112

22.2

28.8

22.9

30.7

23.7

31.7

25.8

33.8

SAKB 036

RIZE 042

180

95

1

2

11.0

3.1

6.6

2.4

15

15

3.90

0.48

3-50-380

1-50-220

1

1

48

46

44

0.2

1350

1265

1112

22.8

29.3

23.2

31.7

24.2

33.9

24.8

36.3

SAKB 042

RIZE 042

180

97

1

2

11.0

3.5

6.6

2.6

15

15

3.90

0.52

3-50-380

1-50-220

1

1

50

48

46

0.2

1650

1585

1490

23.8

31.6

25.0

33.8

26.6

37.3

27.5

38.2

SAKB 042

RIZE 048

200

97

1

2

15.8

3.5

7.5

2.6

15

15

4.40

0.52

3-50-380

1-50-220

1

1

50

48

46

0.2

1650

1585

1490

27.0

35.1

27.7

37.5

29.6

39.2

30.5

42.5

SAKB 048

RIZE 048

0.62

15

230

113

1

2

15.8

4.3

8.8

3.0

20

230

114

1

2

15.8

4.8

11.0

3.0

20

15

6.52

0.62 5.20

3-50-380

1-50-220

1

1

55

53

49

0.2

2420

2335

2223

42.7

55.2

47.1

58.9

49.6

62.7

51.1

66.8

SAKB 065

RIZE 072 A

3-50-380

1-50-220

1

1

52

50

48

0.2

2018

1930

1865

33.8

44.0

37.1

46.9

38.4

49.6

39.8

52.9

SAKB 060

RIZE 060 A


Condensing Unit Refrigerant Line Size Information Liquid Line Size System

Line

Liquid Line Size

Outdoor Unit Above Indoor Coil

Model

Size

Numbers

(inch O.D.)

SAKB

[mm]

Outdoor Unit Below Indoor Coil

Total Length - Feet (m)

1/4* [6.35]

25 [7.26]

50 [15.24]

75 [22.86]

Total Length - Feet (m)

100 [30.48] 125 [38.10] 150 [45.72]

25 [7.62]

50 [15.24]

Vertical Separation - Feet [m] 25 [7.62]

50 [15.24]

75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]

Vertical Separation - Feet [m]

70 [21.34]

25 [7.62]

23 [7.01]

8[2.44]

018 5/16 [7.94] 024

1/4* [6.35]

25 [7.62]

5/16 [7.94] 1/4* [6.35] 030

36 [10.97] 42 [12.80]

48 [14.63] 54 [16.46]

34 [10.36] 44 [13.41]

54 [16.46] 64 [19.51]

19 [5.79]

33 [10.06] 47 [14.33]

61 [18.59]

50 [15.24]

70 [21.34]

50 [15.24] 24 [7.32]

25 [7.62]

5/16 [7.94]

25 [7.62]

50 [15.24]

11 [3.35] 25 [7.62]

30 [9.14]

24 [7.32]

18 [5.49]

38 [11.58]

28 [8.53]

18 [5.49]

8 [2.44]

50 [15.24]

39 [11.89]

25 [7.62]

11 [3.35]

23 [7.01]

9 [2.74]

23 [7.01] 48 [14.63]

25 [7.62]

3/8 [9.53] 5/16* [7.94]

36 [10.97]

23 [7.01]

15 [4.57]

57 [17.37] 25 [7.62]

036 3/8 [9.53] 5/16* [7.94] 042

34 [10.36] 40 [12.19] 25 [7.62]

50 [15.24]

3/8 [9.53] 3/8* [9.53]

75 [22.86] 32 [9.75]

25 [7.62]

44 [13.41]

46 [14.02] 52 [15.85]

38 [11.58] 25 [7.62]

39 [11.89]

53 [16.15] 61 [18.59]

25 [7.62]

26 [7.92]

20 [6.10]

40 [12.19] 33 [10.66]

26 [7.92]

19 [5.79]

23 [7.01]

46 [14.02] 53 [16.15] 70 [21.34]

32 [9.75]

9 [2.74]

28 [8.53]

19 [5.79]

11 [3.35]

3 [.91]

048 1/2 [12.7] 060

3/8* [9.53]

065

1/2* [12.7]

25 [7.62]

48 [14.63]

37 [11.28]

39 [11.89]

38 [11.58]

41 [12.50]

61 [18.59] 72 [21.95] 35 [10.67]

35 [10.67] 33 [10.06] 25 [7.62]

23 [7.01]

11 [3.35]

3 [.91] 37 [11.28] 34 [10.36] 31 [9.45]

*Standard line size

NOTES :

NOTES

1. This chart is applicable for condensing units. Example 1:A 2.5 ton [8.79kW] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [17.58kW] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge. 5. No changes required for flow-check pistons or expansion valve coils.

1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes required for expansion valve coils. 4. Coils with flow-check pistons may require change of piston size,only incase of longer pipe lengths 5. Do not exceed table values for capillary tube coils. 6. Always use the smallest liquid line possible to minimize system charge. 7. Chart may be used to size horizontal runs.

Vapor Line Length / Size versus Capacity Multiplier SAKB-

018

024

-5/ " 8

Vapor Line Run-feet [m]

25' [7.62]

50' [15.24]

100' [30.48]

150' [45.72]

Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional

[15.88 mm] O.D. Standard 3/ " [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98

.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98

030

036

042

048

060/065

5/ " 8

[15.88mm] O.D Optional

7/ " 8

[22.23 mm] O.D. Optional

3/ " 4

[19.05mm] O.D. Standard

11 / " 8

[28.58mm] O.D. Standard

7/ " 8

[22.23 mm] O.D. Optional

13/ " 8

[34.94mm] O.D. Optional

1.00 1.01 .99 1.00 .97 .99 .95 .97

1.00 1.01 .98 1.00 .96 .99 .93 .97

1.00 1.01 .97 1.00 .94 .98 .90 .96

.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00

.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99

NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity. [ ] Designates Metric Conversions Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.

" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice"


FORM NO. R/S3-0106

RILE A - RAAB SERIES RILE A - SARB SERIES

HIGH EFFICIENCY,HIGH STATIC, DUCTED SPLIT SYSTEM AIR CONDITIONERS COOLING ONLY, HEAVYDUTY 50 HERTZ The RILE A Series is the latest introduction in the range of RHEEM split airconditioners with the most reliable unit design available. All air handler models are only 11 - 19 inches high. These units can be matched with all the RHEEM's condensing units.

Engineering Features Air Handler

• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are

• EXPANSION DEVICE - Capillary / Flow check orifice. • FILTERS - Woven synthetic, permanent washable filters are standard on all units. Optional - half inch aluminium washable filters.

• EVAPORATOR COIL- Coils are constructed with inner grooved copper tubes and aluminium fins mechanically bonded to the tubes for maximum heat transfer capabilities.

• REFRIGERANT CONNECTIONS - Field piping connections, sweat type, are made through side of the unit.

available optionally for use when units are to be installed within conditioned space.

• DRAIN PAN - Insulated galvanized steel drain pan is

• MOTOR - Inherently protected motors are mounted inside

designed to trap condensate drain.

of insulated cabinet to reduce motor noise and provide a neat

• SERVICE ACCESS - For RILE 036 A to 072 A removable

looking installation.

panels at the bottom of the unit, can be easily removed for

• LOW PROFILE - Allow for horizontal installation in most

access to motor & blowers. For RILE 018 A to 030 A entire fan

standard drop ceiling application, and the movement of units

and motor section can be separated from the coil section by

through most standard doorways for addition or replacement

wing nuts at four corners of the unit for maintenance.

work.

• TESTING - All units are run tested at the factory prior to shipment.


Engineering Features Condensing Units

• All refrigerant connection are on the exterior of the units, located close to the ground for neat appearing installation.

• Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor winding. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.

• Cabinet is constructed of galvanised steel with polyester powder coating for U.V radiation protection.

• Compressor has an internal pressure - relief assembly to protect against excessive pressure differential.

• The compressor and the control panel is located in separate compartment of the cabinet providing for easy access through service panels.

• Condenser fan motor, inherently protected and permanently lubricated type.

• Service valves are standard on all models.

• Metallic Condenser fan blades ensure safety & durability.

• Every unit is factory charged and tested.

• New design SARB version of low height condensing units for models 060 and 072 allow installation of units in the upper area of a balcony in any apartment. This gives clear space for normal use of the balcony

• H.P. & L.P. Safety controls are standard feature on all the models.

• Internally Grooved Copper Tube (IGT) - Aluminium Fin coils are used on all models.

• Heat Pump Optional, available under "UPAB" Model number.

DIMENSIONS AND OPERATING WEIGHT SARB 060 / 072

RAAB 018 / 024 / 030 / 036 / 042 / 048

RAAB 060 / 072 W

W

W D D

D PLAN PLAN PLAN

H H H

ELEVATION

ELEVATION

ELEVATION

RILE 018 A / 024 A / 030 A

RILE 036 A / 042 A / 048 A / 060 A / 072 A

CONTROL BOX (RILE 018 A & 024 A)

WIDTH

A

DEPTH

HEIGHT

B

DRAIN

A

DEPTH

C1

CONTROL BOX

HEIGHT

C1 (RILE 030 A)

B

C2 WIDTH (30 A)

WIDTH (18 A & 24 A ONLY)

C2

DRAIN

C3

FRONT VIEW

SIDE VIEW

CONDENSING UNITS

FRONT VIEW

SIDE VIEW

AIR HANDLING UNITS C3

RAAB 018 RAAB 024 RAAB 030 RAAB 036 RAAB 042 RAAB 048 RAAB 060 RAAB 072 SARB 060 SARB 072

21.0 21.0 21.0 27.0 27.0 27.0 50.0 50.0 32.0 32.0

13.0 13.0 13.0 16.0 16.0 16.0 16.0 16.0 30.0 30.0

33.0 33.0 33.0 40.0 40.0 40.0 40.0 40.0 44.0 44.0

RILE 018 A RILE 024 A RILE 030 A RILE 036 A RILE 042 A RILE 048 A RILE 060 A RILE 072 A RILE 060 A RILE 072 A

11.0 11.0 12.0 15.0 17.5 17.5 19.0 19.0 19.0 19.0

21.0 21.0 26.5 34.0 34.0 34.0 33.0 37.0 33.0 37.0

47.0 47.0 41.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0

33.0 33.0 34.0 10.6 13.5 13.5 12.6 13.5 12.6 13.5

4.7 4.7 6.6 9.6 11.0 11.0 11.8 12.5 11.8 12.5

1.40 1.40 1.40 1.25 1.00 1.00 0.73 3.75 0.73 3.75

1.00 1.00 1.00 1.25 1.60 1.60 2.00 2.00 2.00 2.00

---5.60 4.40 4.40 4.90 2.65 4.90 2.65

65 66 68 85 90 90 110 115 110 115


EVAPORATOR AIR ENTERING TEMP

AMBIENT TEMP : 115 deg F

15.26 11.83 12.86

11.57 13.50 10.29 11.38 9.88

SMBH TMBH SMBH TMBH SMBH

Note:

FULL LOAD CURRENT

CIRCUIT BREAKER SIZE

134

65 LBS

AIR HANDLING UNIT CONDENSING UNIT

1

2

AIR HANDLING UNIT

NOS.

CONDENSING UNIT CONDENSING UNIT

3.1x1.5R

1.5

AIR HANDLING UNIT SQ.FT

7.6

CONDENSING UNIT

AMPS

20 1.3

CONDENSING UNIT AIR HANDLING UNIT

15 AMPS

1.6

AIR HANDLING UNIT

134

66

1

2

3.1x1.5R

1.8

7.6

1.3

20

15

1.6

AIR HANDLING UNIT CONDENSING UNIT

0.26

0.26 KW

1-50-220

1-50-220

1-50-220

1-50-220

CONDENSING UNIT

* For shipping weight, add 10 Lbs to net weight ** Power supply : 1-50-220/240 & 3-50-380/415

NET WEIGHT (Lbs)*

NUMBER OF FANS

COIL FACE AREA

ELECTRICAL DATA

POWER INPUT

**POWER SUPPLY

AIR HANDLING UNIT

NUMBER OF CIRCUITS FOR THE AIR HANDLING UNIT

EXPANSION DEVICE

1

1

NUMBER OF COMPRESSORS

46

1

45

143

66

1

2

3.1x1.5R

1.8

10.5

1.3

20

15

2

0.26

1-50-220

1-50-220

1

1

48

46

150

68

1

2

3.1x2R

2.4

12.8

1.3

25

15

2.4

0.26

1-50-220

1-50-220

1

1

49

47

150

85

1

1

3.1x2R

2.4

12.9

2.0

25

15

2.4

0.4

1-50-220

1-50-220

1

1

50

48

179

85

1

1

6.2x1.5R

2.4

15.6

2.0

30

15

2.8

0.4

1-50-220

1-50-220

CAPILLARY

1

1

50

48

179

90

1

1

6.2x1.5R

4.7

15.8

2.5

30

15

183

90

1

1

6.2x2R

4.7

17.4

2.5

30

15

3.9

0.5

0.5 2.8

1-50-220

1-50-220

1

1

51

49

1-50-220

1-50-220

1

1

51

49

183

90

1

1

6.2x2R

4.7

17.8

2.5

30

15

3.9

0.5

1-50-220

1-50-220

1

1

53

51

185

90

1

1

6.2x2R

4.7

10.2

2.5

15

15

4.4

0.5

3-50-380

1-50-220

1

1

53

51

240/243

110

2

1

12.9x1.5R

7.5

11.7

2.5

15

15

5.2

0.5

3-50-380

1-50-220

1

1

55

53

51

0.2 49

0.2 49

0.2 47

0.2 47

0.2 46

0.10

46

0.10

45

0.10

44

0.10

44

0.10

43

0.10

1930 2000

1600

1441

1865

31.84

41.65

37.90

46.80

35.65

47.17

42.43

53.00

244/247

115

2

1

12.9x2R

7.5

12.7

5

20

15

6.5

1.1

3-50-380

1-50-220

ORIFICE

1

1

58

56

53

0.2

2400

2335

2223

40.07

49.47

45.10

55.40

42.35

55.96

50.15

62.70

RAAB 060/ RAAB 072/ SARB 060 SARB 072

1600

1441

1265

25.65

33.55

30.53

37.70

28.23

37.38

33.60

42.00

RAAB 048

1380

1265

1265

24.79

31.88

29.52

35.82

27.83

36.21

33.12

40.68

RAAB 042

1380

1265

1112

21.56

28.21

25.67

31.70

24.20

32.04

28.80

36.00

RAAB 042

1200

1088

1112

21.13

27.15

25.15

30.51

23.69

30.77

28.21

34.58

RAAB 036

1200

1088

1029

18.37

24.03

21.87

27.00

20.60

27.23

24.53

30.60

RAAB 036

1000

905

1029

17.84

22.92

21.24

25.03

19.78

25.64

23.55

28.82

RAAB 030

800

724

835

15.51

20.28

18.47

22.15

17.20

22.69

20.48

25.50

RAAB 030

800

724

665

12.25

16.02

14.57

18.00

13.83

18.24

16.46

20.50

RAAB 024

600

559

665

1

PH-HZ-VOLTS

dbA

INCHES OF WC

CFM

13.31

13.61

TMBH

523

14.75 15.38

12.83

SMBH

11.36

17.29

15.30

TMBH

48

HIGH

MEDIUM

LOW

HIGH

MEDIUM

LOW

76DB / 63 WB Deg F

80DB / 67 WB Deg F

76DB / 63 WB Deg F

RAAB 018

RAAB 018

RILE 018A RILE 024A RILE 024A RILE 030A RILE 036A RILE 036A RILE 042A RILE 042A RILE 048A RILE 048A RILE 060A RILE 072A

47

NOISE LEVEL(AHU)

ESP

AIR FLOW PERFORMANCE

EVAPORATOR AIR ENTERING TEMP

AMBIENT TEMP : 95 deg F

80DB / 67 WB Deg F

CONDENSING UNIT MODEL

AIR HANDLING MODEL

TABLE FOR TECHNICAL DATA


System Model Numbers

018

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

024

030

036

042

048

060/072

5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.

" In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice. "


FORM NO. R/Z1-0601

SPLIT SYSTEM RIZE - RAAB SERIES RIZE - SARB SERIES DUCTED SPLIT SYSTEM AIR CONDITIONERS HEAVY DUTY 50 HERTZ

The RIZE Series is the latest introduction in the range of

• FILTERS - Woven synthetic, permanent washable filters are

RHEEM split airconditioners with the most reliable unit design

standard on all units. Optional - half inch aluminium washable

available. All air handler models are only 11 - 18 inches high.

filters.

These units can be matched with all the RHEEM's condensing units.

Engineering Features Air Handler

• CABINET - Powder coat painted. Matching discharge plenums and decorative supply and return air grilles are available optionally for use when units are to be installed

• INSULATION - 5mm thick irradiated grade EPE, fire retardent. • EVAPORATOR COIL - Coils are constructed with inner grooved copper tubes and aluminium fins mechanically bonded to the tubes for maximum heat transfer capabilities.

• REFRIGERANT

CONNECTIONS

-

Field

piping

connections, sweat type, are made through side of the unit.

within conditioned space.

• DRAIN PAN - Insulated galvanized steel drain pan is • MOTOR - Inherently protected, mounted on resilient

designed to trap condensate drain. The drain connections are

neoprene rubber mountings, to reduce noise level.

on two sides of the unit to facilitate the site conditions for the

• BLOWER - Centrifugal, forward curved, double inlet double

convenience of installation.

width type, made from heavy duty aluminium sheet.

• SERVICE ACCESS - Removable panels at the bottom of

• LOW PROFILE - Allow for horizontal installation in most

the unit, can be easily removed for access to motor & blowers.

standard drop ceiling application, and the movement of units

The entire fan and motor section can be separated from the

through most standard doorways for addition or replacement

coil section for servicing and maintenace.

work.

• TESTING - All units are run tested at the factory prior to

• EXPANSION DEVICE - Capillary

shipment.


• New design SARB version of low height condensing units for models 060 and 072 allow installation of units in the upper area of a balcony in any apartment. This gives clear space for normal use of the balcony.

Engineering Features Condensing Units • Compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor winding . It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise.

• Cabinet is constructed of galvanised steel with polyester powder coating for U.V radiation protection. • Internally Grooved Copper Tube (IGT) - Aluminium Fin coils are used on all models.

• Compressor has an internal pressure - relief assembly to protect against excessive pressure differential.

• The compressor and the control box is located in separate compartment of the cabinet providing for easy access through service panels.

• Condenser fan motor, inherently protected and permanently lubricated type. • Metallic Condenser fan blades ensure safety & durability. • All refrigerant connection are on the exterior of the units, located close to the ground for neat appearing installation.

• Service valves are standard on all models.

• HP and LP controls are a standard feature on all the models

• Heat Pump Optional, available under 'RPAB' Model number.

• Every unit is factory charged and tested.

DIMENSIONS AND OPERATING WEIGHT RAAB 018 / 024 / 030 / 036 / 042 / 048

SARB 060 / 072

RAAB 060 / 072

W

W

W

D D

D

PLAN PLAN PLAN

H

H H ELEVATION

CONDENSING UNITS Model RAAB 018 RAAB 024 RAAB 030 RAAB 036 RAAB 042 RAAB 048 RAAB 060 RAAB 072 SARB 060 SARB 072

Height 'H' (Inches) 21 21 21 27 27 27 50 50 32 32

ELEVATION

Depth 'D' (Inches) 13 13 13 16 16 16 16 16 30 30

Width 'W' (Inches) 33 33 33 40 40 40 40 40 44 44

Weight (Lbs) 134 143 150 179 183 185 240 244 243 247

C E

AUXILIARY DRAIN PIPE

DRAIN PIPE G D

ELEVATION

AIR HANDLING UNITS Model RIZE RIZE RIZE RIZE RIZE RIZE RIZE RIZE

018 024 030 036 042 048 060 A 072 A

A

B

C

D

E

F

G

(Inches) (Inches) (Inches) (Inches) (Inches) (Inches) (Inches)

35.9 35.9 35.9 42.6 42.6 42.6 44.0 44.0

10.9 10.9 10.9 15.0 15.0 15.0 18.0 18.0

24.7 24.7 24.7 28.9 28.9 28.9 28.9 30.9

34.8 34.8 34.8 41.4 41.4 41.4 42.8 42.8

9.7 9.7 9.7 10.4 10.4 10.4 10.4 10.4

7.5 7.5 7.5 9.4 9.4 9.4 9.4 9.4

33.3 33.3 33.3 40.1 40.1 40.1 41.1 41.1

Weight (Lbs) 49 50 51 92 95 97 113 114

REFRIGERANT PIPE CONNECTIONS

PLAN

A

RIZE 018/024/030/036/042/048/060A/072A

F

ELEVATION

B

R H SIDE VIEW


EVAPORATOR ENTERING AIR TEMP.

AMBIENT TEMP. 115 F

FULL LOAD CURRENT

CIRCUIT BREAKER SIZE

1.5

1.5

2

2

AIRHANDLING UNIT

CONDENSING UNIT

LBS 134

** Power Supply : 1-50-220/240 & 3-50-380/415

134

1

50

1

49

CONDENSING UNIT

AIRHANDLING UNIT

NOS.

3.1x1R

3.1x1R

CONDENSING UNIT

SQ. FT

AIRHANDLING UNIT

0.6

0.6 7.6

20

20

15

1.60

7.6

AMPS.

AMPS.

15

1.60

CONDENSING UNIT

AIRHANDLING UNIT

CONDENSING UNIT

AIRHANDLING UNIT

CONDENSING UNIT

0.12

0.12

KW

1-50-220

1-50-220

CONDENSING UNIT

1-50-220

AIRHANDLING UNIT

PH - HZ - VOLTS

1-50-220

1

1

45

41

0.1

800

724

665

10.45

12.49

10.89

14.82

12.24

14.94

44

* Refer to installations and operation instructions for the full Air Flow Performance Data

NET WEIGHT ****

NUMBER OF FANS

COIL FACE AREA ***

DATA

ELECTRICAL

POWER INPUT

** POWER SUPPLY

AIRHANDLING UNIT

16.79 13.43

43

1

EXPANSION DEVICE

RIZE 024

RAAB 018

42

40

0.1

600

559

523

9.09

NUMBER OF CIRCUITS FOR THE AIRHANDLING UNIT

dbA

INCHES WC.

CFM

SMBH

9.47 11.15

TMBH

13.23

TMBH

SMBH

10.64

SMBH

13.34

TMBH

14.99 11.66

TMBH

SMBH

1

HIGH

MEDIUM

LOW

SELECTED

HIGH

MEDIUM

LOW

76DB / 63WB F

80DB / 67WB F

76DB / 63WB F

80DB / 67WB F

NUMBER OF COMPRESSORS

NOISE LEVEL (AHU)

EXTERNAL STATIC PRESSURE

*AIR FLOW PERFORMANCE

EVAPORATOR ENTERING AIR TEMP.

CONDENSING UNIT MODEL

AMBIENT TEMP. 95 F

RIZE 018

RAAB 018

AIR HANDLING UNIT MODEL RIZE 030

150

51

1

2

3.1x2R

1.8

12.8

0.6

25

15

2.40

0.12

1-50-220

1-50-220

1

1

46

44

42

0.1

1000

905

835

14.27

19.87

16.99

21.71

15.82

22.24

18.64

24.99

RAAB 030

RIZE 036

6.2x2R

2.9

12.9

2.0

25

15

2.40

0.40

1-50-220

150

92

1

2

RIZE 036

179

92

1

2

6.2x2R

2.9

15.6

2.0

30

15

2.80

0.40

1-50-220

1-50-220

1

1

47

45

43

0.1

1200

1088

1029

16.90

23.55

20.12

26.46

18.95

26.69

22.32

29.99

RAAB 036

CAPILLARY 1-50-220

1

1

47

45

43

0.1

1200

1088

1029

16.41

22.26

19.54

24.31

18.20

24.90

21.43

27.99

RAAB 030

*** Condr. Coil face area = 1R/1.5R/2R=No of rows

143

50

1

2

3.1x1.5R

1.5

10.5

0.6

20

15

2.00

0.12

1-50-220

1-50-220

1

1

45

43

41

0.1

800

724

665

11.27

15.70

13.40

17.64

12.72

17.88

14.98

20.09

RAAB 024

RIZE 024

TABLE FOR TECHNICAL DATA RIZE 042

179

95

1

2

6.2x2R

3.1

15.9

2.4

30

15

2.80

0.48

1-50-220

1-50-220

1

1

48

46

44

0.2

1350

1265

1112

19.44

26.38

23.14

29.64

21.79

29.89

25.67

33.59

RAAB 036

RIZE 042

183

95

1

2

6.2x2R

3.1

17.4

2.4

30

15

3.90

0.48

1-50-220

1-50-220

1

1

48

46

44

0.2

1350

1265

1112

19.84

27.65

23.62

31.07

22.26

31.40

26.21

35.28

RAAB 042

RIZE 048

RIZE 048

185

97

1

2

6.2x2R

3.5

10.2

2.6

15

15

4.40

0.52

3-50-380

1-50-220

1

1

50

48

46

0.2

1650

1585

1490

23.60

32.88

28.09

36.95

25.97

36.63

30.58

41.16

RAAB 048

240/243

113

2

2

12.9x1.5R

4.3

12.7

3.0

15

15

5.20

0.62

3-50-380

1-50-220

1

1

52

50

48

0.2

2018

1930

1865

29.29

40.82

34.87

45.86

32.80

46.23

38.61

51.94

244/247

114

2

2

12.9x2R

4.8

11.7

3.0

20

15

6.50

0.62

3-50-380

1-50-220

1

1

55

53

49

0.2

2420

2335

2223

38.85

48.51

41.57

54.32

39.07

54.87

45.76

61.48

RIZE 072 A

RAAB 072 / SARB 072

RIZE 060 A

RAAB 060 / SARB 060

**** For Shipping weight, add 10 lbs to the net weight

183

97

1

2

6.2x2R

3.5

17.8

2.6

30

15

3.90

0.52

1-50-220

1-50-220

1

1

50

48

46

0.2

1650

1585

1490

22.81

30.96

27.16

34.79

25.60

35.17

30.14

39.51

RAAB 042


Condensing Unit Refrigerant Line Size Information System

Line

Model

Size

Numbers

(inch O.D.)

018 018 024 024

Liquid Line Size Outdoor Unit Below Indoor Coil

Total Length - Feet (m) 25 [7.26]

50 [15.24]

25 [7.62]

50 [15.24]

25 [7.62]

50 [15.24]

[mm]

RAAB/SARB

Liquid Line Size Outdoor Unit Above Indoor Coil

75 [22.86]

5/16 [7.94] 1/4* [6.35]

030

1/4* [6.35]

030

5/16 [7.94]

50 [15.24]

25 [7.62]

23 [7.01]

36 [10.97] 42 [12.80]

25 [7.62]

23 [7.01]

24 [7.32] 25 [7.62]

5/16* [7.94]

34 [10.36] 44 [13.41]

54 [16.46] 64 [19.51]

33 [10.06] 47 [14.33]

61 [18.59]

25 [7.62]

50 [15.24]

50 [15.24]

048 048

3/8* [9.53]

060

3/8* [9.53]

072

1/2* [12.7]

32 [9.75] 44 [13.41]

53 [16.15] 61 [18.59]

25 [7.62]

48 [14.63]

61 [18.59] 72 [21.95]

1/2 [12.7]

18 [5.49]

38 [11.58]

28 [8.53]

18 [5.49]

8 [2.44]

39 [11.89]

25 [7.62]

11 [3.35]

70 [21.34]

38 [11.58]

9 [2.74] 38 [11.58]

32 [9.75]

26 [7.92]

20 [6.10]

40 [12.19] 33 [10.66]

26 [7.92]

19 [5.79]

23 [7.01]

46 [14.02] 53 [16.15]

37 [11.28]

35 [10.67]

24 [7.32]

23 [7.01]

46 [14.02] 52 [15.85] 25 [7.62]

25 [7.62]

30 [9.14]

57 [17.37] 25 [7.62]

39 [11.89]

36 [10.97]

15 [4.57]

75 [22.86]

3/8 [9.53]

8[2.44]

23 [7.01] 50 [15.24]

70 [21.34] 34 [10.36] 40 [12.19]

25 [7.62]

48 [14.63] 25 [7.62]

11 [3.35]

3/8 [9.53] 5/16* [7.94]

48 [14.63] 54 [16.46]

50 [15.24] 19 [5.79]

75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]

Vertical Separation - Feet [m]

70 [21.34]

3/8 [9.53]

042 042

25 [7.62]

Vertical Separation - Feet [m]

1/4* [6.35]

5/16 [7.94]

036 036

Total Length - Feet (m)

100 [30.48] 125 [38.10] 150 [45.72]

9 [2.74]

25 [7.62]

28 [8.53]

19 [5.79]

11 [3.35]

25 [7.62]

23 [7.01]

11 [3.35]

3 [.91]

39 [11.89]

3 [.91] 35 [10.67] 33 [10.06]

41 [12.50]

37 [11.28] 34 [10.36] 31 [9.45]

*Standard line size

NOTES :

NOTES :

1. This chart is applicable for condensing units. Example 1:A 2.5 ton [8.79kW] condensing unit with a total line length of 75 feet [22.86m] with a vertical separation of 30 feet [9.14m] requires a liquid line size of 5/16 [7.94mm]. 2. This chart may also be used to size horizontal runs. Example 2: A 5 ton [17.58kW] condensing unit may have a total horizontal run of 100 feet [30.48m] if using the 3/8 [9.53mm] liquid line. The total horizontal run of using 1/2 [12.7mm] liquid line size will be 150 feet [45.72m]. 3. Do not exceed vertical separation as indicated on the chart. 4. Always use the smallest liquid line possible to minimize system charge.

1. This chart is applicable for condensing units. 2. Do not exceed 120 feet [36.58m] maximum vertical separation, 3. No changes are required for expansion valve coils. 4. Do not exceed table values for capillary tube coils. 5. Always use the smallest liquid line possible to minimize system charge. 6. Chart may be used to size horizontal runs.

Vapor Line Length / Size versus Capacity Multiplier RAAB/SARB

018

024

-5/ ' 8

Vapor Line Run-feet [m]

25 ' [7.62]

50 ' [15.24]

100' [30.48]

150 ' [45.72]

Optional Standard Optional Optional Standard Optional Optional Standard Optional Optional Standard Optional

[15.88 mm] O.D. Standard 3/ ' [19.05mm] 4 O.D. Optional 1.00 1.01 .98 1.00 .96 .99 .97 .98

.98 1.00 1.01 .96 .99 1.00 .93 .98 .99 .97 .98

030

036

042

048

060/072

5/ ' 8

[15.88mm] O.D Optional

7/ ' 8

[22.23 mm] O.D. Optional

3/ ' 4

[19.05mm] O.D. Standard

11 / ' 8

[28.58mm] O.D. Standard

7/ ' 8

[22.23 mm] O.D. Optional

13/ ' 8

[34.94mm] O.D. Optional

1.00 1.01 .99 1.00 .97 .99 .95 .97

NOTES: Capacity Multiplier x Rated Capacity = Actual Capacity.

1.00 1.01 .98 1.00 .96 .99 .93 .97

1.00 1.01 .97 1.00 .94 .98 .90 .96

.99 1.00 1.01 .97 1.00 1.01 .96 .99 1.00 .93 .99 1.00

.98 1.00 1.01 .97 .99 1.01 .95 .99 1.00 .91 .98 .99

[ ] Designates Metric Conversions

Additional compressor oil is not required for runs up to 150 feet [45.72 m]. Oil traps in vertical runs are not required for any height up to 100 feet [30.48 m]. See Liquid Line chart for Vertical Separat ion Requirements and Limitations.

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

RHEEM AIRCONDITIONING DIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A.

' In Keeping with its policy of continuous progress and product improvement, RHEEM reserves the right to make changes without notice'


FORM NO. R-OS 9-05-A1

SPLIT SYSTEM RITD-OS,RAAB-OS SERIES 50 HERTZ DUCTED SPLIT SYSTEM AIR CONDITIONERS WITH CENTRIFUGAL OIL SEPARATOR

Engineering Features Condensing Units

Fan grille is steel reinforced for extra strength. Cabinet is powder painted for all-weather protection.

Copper Tube - Aluminium Fin coils are used on all models.

All controls are accessible by removing one service panel. Removable top grille provides access to the condenser fan motor and condenser coil.

Optional-Condenser coil fins from aluminium precoated corrosion resistant hydrophilic blue colour material for long life of condenser coil.

Single speed motor is designed for low speed, quiet energy-saving operation.

All refrigerant connections are on the exterior of the units, located close to the ground for neat appearing installations.

Compressor have an internal pressure-relief assembly to protect against excessive pressure differential. Compressor is hermetically sealed and incorporates internal high temperature motor overload protecion, and durable insulation on the motor windings. It is internally spring mounted and externally mounted on rubber grommets to reduce vibration and noise

Oil Separator

Services valves are standard on all models. Controls, HP cutout & LP cutouts are standard features. Power and control wiring are kept separate. Every unit is factory charged and tested.

Integral part of unit to suit high rise application

High efficiency (95%) centrifugal separation.

Internal oil collection screen.

Maximum working pressure, 450 psig

Hermetic welded or accessible bolted flange construction.

U.L. listed (file #5168)

Solid copper connection. Corrosion resistant paint.

C.S.A. listed (LR 100624)


Rated Capacity AIR HANDLING UNIT MODEL

RIZE*

018

CONDENSING UNIT MODEL RITD-OS/RAAB-OS O

AMBIENT AIR EVAPORATOR AIR ENTERING TEMP. O TEMP. 95 F

80DB / 67WB F O

76DB / 63 WB F O

AMBIENT AIR EVAPORATOR AIR ENTERING TEMP. O TEMP. 115 F

80DB / 67 WB F O

76DB / 63 WB F

TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH

018 14.99 11.66 13.34 10.64 13.23 9.47 11.15 9.09

030

024 024 20.09 14.98 17.88 12.72 17.64 13.40 15.70 11.27

030 24.99 18.64 22.24 15.82 21.71 16.99 19.87 14.27

036

042

042

048

042

048

060

072

081

094

036 33.59 25.67 29.89 21.79 29.64 23.14 26.38 19.44

042

042 39.51 30.14 35.17 25.60 34.79 27.16 30.96 22.81

048 40.13 29.82 35.71 25.32 36.03 27.39 32.06 23.01

048 41.16 30.58 36.63 25.97 36.95 28.09 32.88 23.60

060 51.94 38.61 46.23 32.80 45.86 34.87 40.82 29.29

072 61.48 45.76 54.87 39.07 54.32 41.57 48.51 38.85

081 69.17 51.48 61.73 43.95 61.11 46.77 54.57 43.71

094 80.27 59.74 71.64 51.01 70.92 54.27 63.33 50.72

036

030 27.99 21.43 24.90 18.20 24.31 19.54 22.26 16.41

036 29.99 22.32 26.69 18.95 26.46 20.12 23.55 16.90

35.28 26.21 31.40 22.26 31.07 23.62 27.65 19.84

Condensing Unit Refrigerant Line Size Information System Model Numbers RITD-OS/RAAB-OS

50ft [15.24m] SL LL

Vapor line (SL) Size & Liquid Line (LL) Size 100ft [30.48m] 150ft [45.72m] 200ft [60.9m] SL LL SL LL SL LL

3/8"

5/8"

3/8"

3/4"

3/8"

3/4"

250ft [76.2m] SL LL

1/2"

7/8"

1/2"

300ft [91.44m] SL LL

018

5/8"

7/8"

1/2"

024

5/8"

3/8"

5/8"

3/8"

3/4"

3/8"

3/4"

1/2"

7/8"

1/2"

7/8"

1/2"

030

5/8"

3/8"

5/8"

3/8"

7/8"

3/8"

7/8"

1/2"

1 1/8"

1/2"

1 1/8"

1/2"

036

5/8"

3/8"

5/8"

3/8"

7/8"

3/8"

7/8"

1/2"

1 1/8"

1/2"

1 1/8"

1/2"

042

3/4"

3/8"

3/4"

3/8"

1 1/8"

5 /8"

1 1/8"

5/8"

1 1/8"

5/8"

1 1/8"

5/8"

048

7/8"

3/8"

7/8"

3/8"

1 1/8"

5 /8"

1 1/8"

5/8"

1 3/8"

5/8"

1 3/8"

5/8"

060

7/8"

3/8"

7/8"

3/8"

1 1/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

072

7/8"

3/8"

7/8"

3/8"

1 1/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

081

7/8"

5/8"

7/8"

5/8"

1 1/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

1 3/8"

3/4"

094

1 1/8"

3/4"

1 1/8"

3/4"

1 3/8"

3/4"

1 5/8"

3/4"

1 5/8"

3/4"

1 5/8"

3/4"

Capacity Multiplier 0.98

018 024

0.97 0.98 0.97 0.97 0.97 0.97 0.97

030 036 042 048

0.97 0.98 0.97 0.97 0.98 0.99

0.98 0.97 0.97 0.97 0.98 0.99

0.98 0.97 0.98 0.97 0.97 0.97

0.97 0.97 0.98 0.98 0.97 0.97

0.98 0.98 0.98 0.98

0.99 0.99 0.99 0.99

0.97 0.97 0.97 0.97

0.97 0.97 0.97 0.97

0.97 0.97 0.98 0.97 0.97 0.97

0.97 0.97 0.97 0.97 081 0.97 094 0.97 1. For condensing unit below the air handling unit, provide one inverted 'U' trap at the evaporator outlet in order to prevent liquid refrigerant going back to compressor during off cycle. 2. However it is recommended to provide 'U' trap after every 10 meter of pipe rise in case of condensing unit is above the evaporator 3. In case any pipe size not available it is recommended to use next higher pipe size. 060 072

DIMENSIONS AND OPERATING WEIGHT

H

W

CONDENSING UNITS RAAB-OS

CONDENSING UNITS RITD-OS

Model W Weight H D RAAB-OS (Inches) (Inches) (Inches) (Lbs)

Weight Model D W H RITD-OS (Inches) (Inches) (Inches) (Lbs.)

018 024 030 036 042 048 060 072

21 21 21 27 27 27 50 50

D

13 13 13 16 16 16 16 16

33 33 33 40 40 40 40 40

144 153 160 189 195 297 255 259

018 024 030 036 042 048 060 072 081 094

25.7 25.7 25.7 27.7 27.7 27.7 29.7 29.7 31.7 31.7

22.5 22.5 22.5 22.5 22.5 22.5 30.0 30.0 30.0 30.0

22.5 22.5 22.5 22.5 22.5 22.5 30.0 30.0 30.0 30.0

125 125 127 142 165 165 199 205 218 248

H

D

W

NOTES: Other air handlers RILE, RICD and SBHC can be used with these condensing units Capacity Multiplier x Rated Capacity = Actual Capacity.

Before proceeding with installation, refer RHEEM to installation instructions packaged with AIRCONDITIONING each model, as well as complying with DIVISION all Federal, State, Provincial, and Local codes, regulations, and practices. 5600 Old Greenwood Road, Fort Smith, Arkansas 72906, U.S.A. " In Keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice"


















Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.