About Vitesse Plus
3
LCM connections Quick start
3 4
How to program with a preset configuration
5
Open Port programming
5
How to set up an environment with several LCMs
7
Example behaviour
8
Preset configurations by application
9
Commercial preset configurations Healthcare configurations Education preset configurations
9 9 10
Graduated dimming
10
Perimeter dimming
11
Perimeter switching
11
Room dimming configurations
12
Room switching configurations
12
Windows on 2 sides of room
12
Classroom with store cupboard/WC
12
Scene setting preset configurations Corridor preset configurations Toilet preset configurations
13 13 13
Index
14
Preset configurations by number
19
â–Ş2â–Ş
Vitesse Plus System Manual
ABOUT VITESSE PLUS Vitesse plus is a flexible lighting control system which provides effective power delivery and control for lighting installations in commercial, educational and healthcare buildings. Vitesse Plus is designed for ease of installation: mains input is connected using the spacious wiring compartment; control inputs and outputs are pluggable using industry standard connectors. The Vitesse Plus lighting control module (LCM) has 12 luminaire outputs, which can be configured as seven separate channels if required. All control inputs are SELV and provide a variety of functions such as presence and absence detection, daylight linking and manual dimming.
LCM connections
â–Ş3â–Ş
Vitesse Plus System Manual
Quick start Connect all detectors and switches to the LCM before following this procedure. Refer to the VITP7-MB installation guide for details on how to do this. Use the following procedure with the UNLCDHS handset to get your Vitesse Plus installation up and running:
1
2
Connect the power to the LCM. It then goes through a power-up sequence of 8 seconds, after which all connected lights switch on.
3
and press
Rapid à
.
5
Vitesse Plus
>
Handset Config
>
VITESSE PLUS à
Select LCM and press
or
6
à Program
or
to turn on the programming handset.
>
LCM
Select Program and press
ON/OFF
4
PRODUCT FAMILY
Select Vitesse Plus from the main PRODUCT FAMILY menu
Press
>
Device Info
>
Select Preset and type in the number of the preset.
8 Press
twice to return to the Vitesse Plus menu.
device and press . An LED flashes red/green to acknowledge the command, then green till the preset is programmed.
9
10
VITESSE PLUS
Select Detector and press or
.
à
LCM
>
Detector
>
Scene Panel
>
11
Select Program and press
Select Timeout (mins) and enter the number of minutes to wait (0 - 99) before lights turn off when absence detected.
à Timeout (mins) Light Level (MI) Detection Mode
10 600 No
Select Light Level (MI) and enter the target value (0-999) that daylight linking is to maintain.
14
Point the handset directly at the
Perform this sequence with the centre-biased retractive switch to activate daylight linking:
.
1. 2. 3. 4.
▪4▪
DALI
Detection Mode
Pres
LCM
>
Detector
>
Scene Panel
>
Program
>
User
>
Device Info
>
PROGRAM
13
device and press
Load Type
.
12
PROGRAM
7
DETECTOR à
or
>
VITESSE PLUS à
Point the handset directly at the
>
Scene Panel
à Preset
.
7
>
Detector
PROGRAM
>
Lux Settings
.
LCM
Dim all the way down Dim all the way up Switch off Switch on
Timeout (mins) à
Light Level (MI) Detection Mode
10 600 No
Vitesse Plus System Manual
HOW TO PROGRAM WITH A PRESET CONFIGURATION Use the UNLCDHS handset to send the required preset configuration to the LCM. 1. Select Vitesse Plus from the main PRODUCT FAMILY menu and press 2. Select LCM and press
or
3. Select Program and press
.
. or
.
4. Select Preset and type in the number of the configuration. 5. Point the handset directly at the device and press
.
Open Port programming If the LCM is not in the line of sight of the handset, you can send the preset through a detector if one is connected. 1. Select Vitesse Plus from the main PRODUCT FAMILY menu and press 2. Select Detector and press 3. Select Program and press
or or
. .
4. Select Advanced Config and press 5. Select Open Port and press
.
or
.
to set it to Yes.
6. Point the handset directly at the device and press . The detector's LED flashes to show it has received the command and then stays red. This indicates the port is open and ready to forward settings to the LCM. 7. Press
until you return the to the Detector menu.
8. Select Detector ID and make sure the value is set to 100. Point the handset directly at the device and press
.
9. Select Program and press
or
.
10. Select Preset and type in the number of the configuration. Point the handset directly at the device and press
.
11. Select Advanced Config and press 12. Select Open Port and press
or
.
to set it to No.
13. Point the handset at the detector and press command and then goes off.
. The detector's LED flashes to show it has received the
â–Ş5â–Ş
Vitesse Plus System Manual
Notes
▪6▪
Vitesse Plus System Manual
HOW TO SET UP AN ENVIRONMENT WITH SEVERAL LCMS 1
2
Send the same preset configuration to each LCM.
Connect the LCMs to each other using RJ45 patch leads.
▪7▪
Vitesse Plus System Manual
Example behaviour In this example, configuration N's parameters mean that when the detector detects presence, luminaires connected to channels 1, 2 and 3 dim up to 100%, those connected to channels 4, 5 and 6 dim up to 50%.
a
b
c
As all LCMs are programmed with configuration N, presence detection causes luminaires connected to all instances of channel 1, 2 and 3 to dim up to 100%, whichever LCM they are plugged into.
Because the LCMs are connected to each other, it doesn't matter which detector detects presence. If a different detector picks up presence, the effect on the luminaires is the same.
Plugging a luminaire into a different channel can change how it reacts when presence is detected. In this case, moving the luminaires from the bottom right LCM's channels 4, 5 and 6 to channels 1, 2 and 3 results in them dimming up to 100% instead of the 50% shown in the other scenarios above.
â–Ş8â–Ş
Vitesse Plus System Manual
PRESET CONFIGURATIONS BY APPLICATION Commercial preset configurations Lighting arrangement
2 rows of 5 luminaires
Room setup
Control method
Preset #
See page
4 cellular offices with 1 switch for Daylight linking each office; channel arrangement #1 Daylight switching
1
page 19
2
page 20
4 cellular offices with 1 switch for Daylight linking each office; channel arrangement #2 Daylight switching
63
page 80
64
page 81
Daylight linking
3
page 21
Daylight switching
4
page 22
61
page 78
62
page 79
Daylight linking, only window row dimmable
5
page 23
Daylight switching, only window row dimmable
6
page 24
No dimming luminaires
7
page 25
Daylight linking, all luminaires dimmable
67
page 84
3 cellular offices with 1 switch for Daylight linking each office Daylight switching
65
page 82
66
page 83
Open plan office
68
page 85
Open plan office 3 cellular offices with 1 switch for Daylight linking each office Daylight switching
3 rows of 4 luminaires
2 rows of 6 luminaires
Open plan office
Daylight linking
Healthcare configurations These configurations are for rooms in hospitals and similar buildings where there are two power supplies, one for essential and emergency applications and one for non-essential applications. Daylight dimming Lighting arrangement 2 rows of 7 luminaires 2 rows of 6 luminaires
Room setup
Supply
Preset#
See page
Essential
74
page 91
Non-essential
75
page 91
Essential and non-essential
76
page 92
4 cellular offices 2 cellular offices
▪9▪
Vitesse Plus System Manual
Education preset configurations These configurations are for classrooms with windows on just one side of the room, with the exception of Presets 58-60, 72 and 73.
Graduated dimming Lighting arrangement
Room switches
3 rows of 3 dimmable lights
Preset See page #
Whiteboard switch for 3 lights, 1 per row (2x PIR, 1x microwave)
10
page 28
Whiteboard switch for 1 light (also controlled by row switch)
11
page 29
Whiteboard switch for 1 row of lights
12
page 30
Whiteboard switch for 2 lights within 1 row.
13
page 31
Whiteboard switch for 3 lights, 1 per row.
14
page 32
Whiteboard switch for 1 light
15
page 33
Whiteboard switch for 1 row of lights
16
page 34
Whiteboard switch for 2 lights within 1 row.
17
page 35
3 switches, 1 per row of luminaires (whiteboard lights separate)
Whiteboard switch for 3 separate lights
51
page 68
1 switch for all lights (whiteboard lights separate)
Whiteboard switch for 3 separate lights
52
page 69
82
page 98
3 switches, 1 per row of luminaires
3 rows of 4 dimmable lights
Whiteboard setup
1 switch for all lights
3 switches, 1 per column Whiteboard switch for 3 lights, 1 per of luminaires column
â–Ş 10 â–Ş
Vitesse Plus System Manual
Perimeter dimming Lighting arrangement
Room switches
Preset See page #
Whiteboard switch for 3 lights, 1 per row. 18
page 36
Whiteboard switch for 1 light.
19
page 37
Whiteboard switch for 1 row of lights
20
page 38
Whiteboard switch for 2 lights within 1 row.
21
page 39
Whiteboard switch for 3 lights, 1 per row. 22
page 40
Whiteboard switch for 1 light.
23
page 41
Whiteboard switch for 1 row of lights
24
page 42
Whiteboard switch for 2 lights within 1 row.
25
page 43
3 switches, 1 per row of luminaires (whiteboard lights separate)
Whiteboard switch for 3 separate lights
53
page 70
1 switch for all lights (whiteboard lights separate)
Whiteboard switch for 3 separate lights
54
page 71
3 switches, 1 per row of luminaires.
3 rows of 4 lights, only window row dimmable
Whiteboard setup
1 switch for all lights
Perimeter switching Lighting arrangement
Room switches
3 rows of 3 lights, window row daylight switching
Preset See page #
Whiteboard switch for 3 lights, 1 per row. 26
page 44
Whiteboard switch for 1 light.
27
page 45
Whiteboard switch for 1 row of lights
28
page 46
Whiteboard switch for 2 lights within 1 row.
29
page 47
Whiteboard switch for 3 lights, 1 per row. 30
page 48
Whiteboard switch for 1 light.
31
page 49
Whiteboard switch for 1 row of lights
32
page 50
Whiteboard switch for 2 lights within 1 row.
33
page 51
3 switches, 1 per row of luminaires (whiteboard lights separate)
Whiteboard switch for 3 separate lights
55
page 72
1 switch for all lights (whiteboard lights separate)
Whiteboard switch for 3 separate lights
56
page 73
83
page 99
3 switches, 1 per row of luminaires.
3 rows of 4 lights, window row daylight switching
Whiteboard setup
1 switch for all lights
3 switches, 1 per column Whiteboard switch for 3 lights, 1 per of luminaires column
▪ 11 ▪
Vitesse Plus System Manual
Room dimming configurations Lighting arrangement
Room switches
Whiteboard setup
Preset See page #
3 rows of 4 lights dimming
3 switches, 1 per row of luminaires, whiteboard separate
Whiteboard switch for 1 light
69
page 86
3 rows of 4 lights dimming
3 switches, 1 per row of luminaires, whiteboard separate
Whiteboard switch for 3 lights
71
page 88
3 rows of lights, only those by windows dimmable
3 switches, 1 per row of luminaires
Whiteboard lights also controlled by row switches
72
page 89
Room switching configurations Lighting arrangement
3 rows of 4 lights
Room switches 3 switches, 1 per row of luminaires, whiteboard separate
Whiteboard setup
Whiteboard switch for 1 light
Preset See page # 70
page 87
Windows on 2 sides of room Lighting arrangement
Room switches
Whiteboard setup
Preset See page #
3 switches, 1 per column of 3 rows of lights, only those luminaire by windows daylight 3 switches, 1 per row of switching luminaires
Whiteboard switch for 3 separate lights
57
page 74
Whiteboard switch for 1 light
58
page 75
3 switches, 1 per column of luminaires
Whiteboard switch for 3 separate lights
59
page 76
Whiteboard switch for 1 light
60
page 77
Whiteboard switch for 3 separate lights
73
page 90
3 rows of lights, only those by windows dimmable 3 switches, 1 per row of luminaires
Classroom with store cupboard/WC Lighting arrangement
10 classroom lights, one store cupboard light
Room switches
Dimming luminaire?
Preset See page #
3 switches, 1 per row of All classroom lights dimmable luminaires, plus 1 for whiteboard only Only window row dimmable
77
page 93
78
page 94
All classroom lights dimmable
79
page 95
Only window row dimmable
80
page 96
All classroom lights dimmable
81
page 97
1 switch for all lights, 1 for whiteboard only 7 classroom lights, two WC 1 switch for all lights, 2 for lights whiteboard only
â–Ş 12 â–Ş
Vitesse Plus System Manual
Scene setting preset configurations Lighting arrangement 2 rows of dimmable lights(commercial application)
3 rows of dimmable lights (commercial application)
Room setup
Preset See page #
Scene setting
2 switches, 1 per room
Scenes 1 to 4 = light to dark
34
page 52
4 switches, 1 per room
Scenes 1 to 4 = light to dark
35
page 53
1 switch for all lights, 1 window group
Scene 2 = window row off, others 75%
36
page 54
1 switch for all lights, 2 window groups daylight linked
Scenes 2 and 3 = window row off, others 75%
37
page 55
1 switch for all lights, 2 window groups
Scenes 2 and 3 = window row off, others 75%
38
page 56
Scene 2 = Whiteboard lights off, others 75%
39
page 57
Scene 2 = Centre whiteboard off, others 75%
40
page 58
Scene 2 = Whiteboard row off, others 75%
41
page 59
Scene 2 = Light closest to whiteboard off, others 75%
42
page 60
Scene 2 = Whiteboard lights off, others 75%
43
page 61
Scene 2 = Centre whiteboard off, others 75%
44
page 62
Scene 2 = Whiteboard row off, others 75%
45
page 63
Scene 2 = Light closest to whiteboard off, others 75%
46
page 64
Reserved for future use
47
page 65
Reserved for future use
48
page 65
3 switches, 1 per row of luminaires.
3 rows of dimmable lights (education applications) 1 switch for all lights
Corridor preset configurations Lighting arrangement
Room setup
Control method
1 row of 10 luminaires
Corridor
Detector only
2 rows of 5 luminaires plus corridor
4 classrooms plus corridor
Preset#
See page
50
page 67
Daylight switching
8
page 26
Daylight dimming
9
page 27
Toilet preset configurations Lighting arrangement 3 toilets, 2 or 3 luminaires in each
Room switches
Dimming luminaire?
Preset #
None
None
49
▪ 13 ▪
See page page 66
Vitesse Plus System Manual
INDEX Commercial Preset #
See page
1
4 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 19
2
4 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 20
3
Open plan office working in presence mode with channels 5, 6 and 7 daylight dimming for perimeter rows.
page 21
4
Open plan office working in presence mode with channels 5, 6 and 7 daylight switching for perimeter rows.
page 22
5
Open plan office working in presence mode with channels 1–4 daylight dimming for perimeter rows.
page 23
6
Open plan office working in presence mode with channels 1–4 daylight switching for perimeter rows.
page 24
7
Standard open plan office arrangement, operating in presence mode.
page 25
61
3 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 78
62
3 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 79
63
4 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 80
64
4 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 81
65
3 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 82
66
3 cellular offices individually controlled with a presence detector and/or manual switch in each.
page 83
67
Open plan office with graduated dimming.
page 84
68
Open plan office with graduated dimming.
page 85
Corridor Preset#
See page
8
Corridor with lux switching. Presence mode only.
page 26
9
Corridor with dimming. Presence mode only.
page 27
50
Corridor with 50% of luminaires controlled by a PIR and 50% controlled by switch input.
page 67
▪ 14 ▪
Vitesse Plus System Manual
Education: Graduated dimming Preset #
See page
10
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 28 2 and 3.
11
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
12
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 30 4 and 5.
13
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
page 31
14
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
page 32
15
Classroom with luminaires working in absence mode. Whiteboard on channel 2.
page 33
16
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
page 34
17
Classroom with luminaires working in absence mode. Whiteboard on channel 5.
page 35
51
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 68 2 and 3 switched independently.
52
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
page 69
82
Classroom with 3 columns of luminaires working in absence mode. All fittings dimmable from switches but only window row responsive to lux.
page 98
page 29
Perimeter dimming Preset #
See page
18
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 36 2 and 3.
19
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
20
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 38 4 and 5.
21
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
page 39
22
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
page 40
23
Classroom with luminaires working in absence mode. Whiteboard on channel 2.
page 41
24
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
page 42
25
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
page 43
53
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 70 2 and 3 switched independently.
54
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
page 37
page 71
Perimeter switching Preset #
See page
26
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 44 2 and 3.
27
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
â–Ş 15 â–Ş
page 45
Vitesse Plus System Manual
Preset #
See page
28
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 46 4 and 5.
29
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
page 47
30
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
page 48
31
Classroom with luminaires working in absence mode. Whiteboard on channel 2.
page 49
32
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
page 50
33
Classroom with luminaires working in absence mode. Whiteboard on channel 5.
page 51
55
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 72 2 and 3 switched independently.
56
Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
page 73
83
Classroom with 3 columns of luminaires working in absence mode all fittings switching from switches but only window row responsive to lux.
page 99
Room dimming (all fittings 20%) Preset #
See page
69
Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.
page 86
71
Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1-3 switched separately.
page 88
72
Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1,2 and 3.
page 89
Room switching Preset # 70
See page Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.
page 87
Windows on 2 sides of room Preset #
See page
57
Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.
page 74
58
Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.
page 75
59
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
page 76
60
Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
page 77
73
Classroom with 4 columns of fittings working in absence mode. Whiteboard on channels 1,2 and 3.
page 90
Classroom with store cupboard/WC Preset # 77
See page Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
â–Ş 16 â–Ş
page 93
Vitesse Plus System Manual
Preset #
See page
78
Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
page 94
79
Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
page 95
80
Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
page 96
81
Classroom with luminaires working in absence mode, and store cupboards/ WC working independently in presence mode.
page 97
Scene setting: Commercial applications Preset #
See page
34
Two cellular offices with a detector and scene plate in each. Option for local switch in each office.
page 52
35
4 cellular offices with a scene plate in each. Option for local switch in each office. Detector in each.
page 53
36
Large office/meeting room with detector used for lux and occupancy and scene plate and option for master all on switch 1 scene selection switch.
page 54
37
Large office or meeting room with lux referenced on channels 1-3 only. Detector used for lux and occupancy, 1 scene plate.
page 55
38
Large office or meeting room with detector for occupancy and no lux on any channels. 1 scene plate.
page 56
Education applications Preset #
See page
39
Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1–3. Scene plate by teacher's desk. Detector for lux (scene 1 only) and absence.
page 57
40
Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 2. Scene plate by teacher's desk.
page 58
41
lassroom with 3 rows of fittings switched individually. Whiteboard row on channels 1, 4 and 5. Scene plate by teacher's desk.
page 59
42
Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 5. Scene plate by teacher's desk.
page 60
43
Classroom with 3 rows switched together but with different dimming pre-set levels per row. Whiteboard channels 1–3. Scene plate by teacher's desk.
page 61
44
Classroom with all fittings switched together. Whiteboard on channels 2. Scene plate by teacher's desk.
page 62
45
Classroom with all fittings switched together. Whiteboard on channels 1, 4 and 5. Scene plate by teacher's desk.
page 63
46
Classroom with all fittings switched together. Whiteboard on channel 5. Scene plate by teacher's desk.
page 64
47
Reserved for future use
48
Reserved for future use
▪ 17 ▪
Vitesse Plus System Manual
Toilet Preset # 49
See page 3 toilets each controlled separately in presence mode by a PIR connected to inputs 1, 2 and 3. Channel 1 only responds in presence mode to all 4 detector inputs.
page 66
Healthcare Preset#
See page
74
4 cellular offices individually controlled with a presence detector and/or manual centrebiased retractive switch in each. Dual supply using 2 LCMs
page 91
75
4 cellular offices individually controlled with a presence detector and/or manual centrebiased retractive switch in each. Dual supply using 2 LCMs
page 91
76
2 cellular offices individually controlled with a presence detector and/ or manual centreretractive switch in each. Dual supply (essential and non-essential) using 2 LCMs.
page 92
â–Ş 18 â–Ş
Vitesse Plus System Manual
PRESET CONFIGURATIONS BY NUMBER Preset 1 Available from version 1.00 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
CH6
CH6
CH7
CH1
CH2
CH2
CH3
Windows
CH5
SW1
SW2
CH4
SW3
SW4
E PL
Switch inputs
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable SW1
SW2
SW3
SW4 Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW2: : 3, C,4
SW3: 5-C-6
SW4: 7-C-8
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1
2
3
4
1
2
3
▪ 19 ▪
Vitesse Plus System Manual
Preset 2 Available from version 1.00 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
CH6
CH6
CH7
CH1
CH2
CH2
CH3
Windows
CH5
Windows
SW1
SW2
CH4
SW3
SW4
E PL
Switch inputs
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
SW4 Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
SW4: 7-C-8
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1
2
3
4
1
2
3
▪ 20 ▪
Vitesse Plus System Manual
Preset 3 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 5, 6 and 7 daylight dimming for perimeter rows.
Windows
CH6
CH5 Windows
CH1
CH2
CH4
CH3
CH7
Detector/scene plate inputs
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only dimmable
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20%
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 21 ▪
Vitesse Plus System Manual
Preset 4 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 5, 6 and 7 daylight switching for perimeter rows.
Windows
CH6
CH5 Windows
CH1
CH2
CH3
CH7
CH4
Detector/scene plate inputs
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only daylight switching.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 22 ▪
Vitesse Plus System Manual
Preset 5 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 1–4 daylight dimming for perimeter rows.
Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
CH6
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only dimmable
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20%
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 23 ▪
Vitesse Plus System Manual
Preset 6 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 1–4 daylight switching for perimeter rows.
Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
CH6
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only daylight switching.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 24 ▪
Vitesse Plus System Manual
Preset 7 Available from version 1.00 software onwards. Standard open plan office arrangement, operating in presence mode.
Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
CH6
Upon entering the space luminaires will automatically switch on.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
â–Ş 25 â–Ş
Vitesse Plus System Manual
Preset 8 Available from version 1.00 software onwards. Corridor with lux switching. Presence mode only. The maximum number of LCMs connected together using the corridor hold connections is 20. The CSA of the cable should be 1.50mm and the length of run should not exceed 100m.
Configured for: l Presence detection l Corridor hold = Latching switch (terminal 11) l ELT keyswitch = latching switch (terminal 10) Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
â–Ş 26 â–Ş
Vitesse Plus System Manual
Preset 9 Available from version 1.00 software onwards. Corridor with dimming. Presence mode only. The maximum number of LCMs connected together using the corridor hold connections is 20. The CSA of the cable should be 1.50mm and the length of run should not exceed 100m.
Configured for: l Presence detection l Corridor hold = Latching switch (terminal 11) l ELT keyswitch = latching switch (terminal 10) Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
1-4
1-4
â–Ş 27 â–Ş
Vitesse Plus System Manual
Preset 10 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW2: 3-C-4 Whiteboard: 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
SW1: 1-C-2
SW1: 1, C,2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
â–Ş 28 â–Ş
Vitesse Plus System Manual
Preset 11 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2
2 SW2: 3-C-4 Whiteboard: 7-C-8
3
4
5
6
7
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
â–Ş 29 â–Ş
Vitesse Plus System Manual
Preset 12 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2
3
SW2: 3-C-4
SW3: 5-C-6
4 SW1: 1-C-2 Whiteboard: 7-C-8
5 SW1: 1-C-2 Whiteboard: 7-C-8
6
7
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
â–Ş 30 â–Ş
Vitesse Plus System Manual
Preset 13 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2
Detector input
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
Switch input
â–Ş 31 â–Ş
5
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
100%
60%
20%
SW1: 1-C-2 Whiteboard: 7-C-8
Vitesse Plus System Manual
Preset 14 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires Main Switch
Whiteboard Switch
Emergency Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
Switch input
▪ 32 ▪
Vitesse Plus System Manual
Preset 15 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 Main sw: 5-C-6
2 Main sw: 5-C-6 Whiteboard: 7-C-8
3
4
5
6
7
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
â–Ş 33 â–Ş
Vitesse Plus System Manual
Preset 16 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
Switch input
â–Ş 34 â–Ş
Vitesse Plus System Manual
Preset 17 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Detector input
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
Switch input
â–Ş 35 â–Ş
5
6
7
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
100%
60%
20%
Main sw: 5-C-6 Whiteboard: 7-C-8
Vitesse Plus System Manual
Preset 18 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW2: 3-C-4 Whiteboard: 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
â–Ş 36 â–Ş
Vitesse Plus System Manual
Preset 19 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1 SW1: 1-C-2
2 SW2: 3-C-4 Whiteboard: 7-C-8
3
4
5
6
7
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
â–Ş 37 â–Ş
Vitesse Plus System Manual
Preset 20 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
-
-
20%
-
SW1: 1-C-2 Whiteboard: 7-C-8
4 SW1: 1-C-2 Whiteboard: 7-C-8
â–Ş 38 â–Ş
5
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
-
-
20%
SW1: 1-C-2 Whiteboard: 7-C-8
Vitesse Plus System Manual
Preset 21 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2
1-4
1-4
1-4
1-4
-
-
20%
-
â–Ş 39 â–Ş
5
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
-
-
20%
SW1: 1-C-2 Whiteboard: 7-C-8
Vitesse Plus System Manual
Preset 22 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be
Whiteboard
connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Switch operates luminaires within the same colour dashed line.
Luminaires daylight link – window row only dimmable
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires Main Switch
Whiteboard Switch
Emergency Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8 1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
▪ 40 ▪
Vitesse Plus System Manual
Preset 23 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Main sw: 5-C-6
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
â–Ş 41 â–Ş
Vitesse Plus System Manual
Preset 24 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
Main sw: 5-C-6 Main sw: 5-C-6 Whiteboard: 7-C-8
3
4
5
Main sw: 5C-6
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
6
7
Main sw: 5-C-6 Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
â–Ş 42 â–Ş
Vitesse Plus System Manual
Preset 25 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C6
Main sw: 5-C-6
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
100%
60%
20%
100%
100%
60%
20%
â–Ş 43 â–Ş
Vitesse Plus System Manual
Preset 26 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH6
CH2
E
Switch input
PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
Whiteboard Emergency Switch Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4
3 SW3: 5-C-6 Whiteboard: 7-C-8 1-4
▪ 44 ▪
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
Vitesse Plus System Manual
Preset 27 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH6
CH2
Switch inputs
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
Whiteboard Emergency Switch Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2
1-4
2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4
3
4
5
6
7
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
▪ 45 ▪
Vitesse Plus System Manual
Preset 28 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
Whiteboard Switch
Whiteboard
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH6
CH2
E
Switch inputs
PL
CH7
CH3
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
Whiteboard Emergency Switch Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
2
3
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
4 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
▪ 46 ▪
5 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
Vitesse Plus System Manual
Preset 29 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.
Detector/scene plate inputs SW1
SW2
SW3
CH1
Whiteboard Switch
Whiteboard
CH5
CH4
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH2
CH6
Switch inputs
E PL
CH3
CH7
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
Whiteboard Emergency Switch Lighting Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
4 SW1: 1-C-2
1-4
▪ 47 ▪
5 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
Vitesse Plus System Manual
Preset 30 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 48 ▪
Vitesse Plus System Manual
Preset 31 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 Main sw: 5-C-6
1-4
2 Main sw: 5-C-6 Whiteboard: 7-C-8 1-4
3
4
5
6
7
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
▪ 49 ▪
Vitesse Plus System Manual
Preset 32 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.
Detector/scene plate inputs Whiteboard Switch
Main Switch
CH4
CH1
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs
CH6
CH2
E PL
CH7
CH3
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6 Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 50 ▪
Vitesse Plus System Manual
Preset 33 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 5.
Detector/scene plate inputs Main Switch
Whiteboard Switch
Whiteboard
CH5
CH1
CH4
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs
CH6
CH2
E PL
CH7
CH3
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
▪ 51 ▪
5 Main sw: 5-C-6 Whiteboard: 7-C-8 1-4
6
7
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
Vitesse Plus System Manual
Preset 34 Available from version 1.00 software onwards. Two cellular offices with a detector and scene plate in each. Option for local switch in each office.
Configured for: l l l l
Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
Detector input
1
1
1
1
1
3
3
Scene plate input
2
2
2
2
2
4
4
Scene group
1
1
1
1
1
2
2
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
75%
75%
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
Switch input
Light levels:
â–Ş 52 â–Ş
Vitesse Plus System Manual
Preset 35 Available from version 1.00 software onwards. 4 cellular offices with a scene plate in each. Option for local switch in each office. Detector in each.
Configured for: l l l l
Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW4: 7-C-8
Detector input
1
1
1
2
2
3
4
Scene plate input
1
1
1
2
2
3
4
Scene group
1
2
3
4
1
2
3
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
75%
75%
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
Switch input
Light levels:
â–Ş 53 â–Ş
Vitesse Plus System Manual
Preset 36 Available from version 1.00 software onwards. Large office/meeting room with detector used for lux and occupancy and scene plate and option for master all on switch 1 scene selection switch.
Configured for: l l l l
Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
1
1
1
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
OFF
OFF
OFF
OFF
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
Switch input
Scene group Light levels:
â–Ş 54 â–Ş
Vitesse Plus System Manual
Preset 37 Available from version 1.00 software onwards. Large office or meeting room with lux referenced on channels 1-3 only. Detector used for lux and occupancy, 1 scene plate.
Detector/scene plate inputs
CH1
GROUP 1
GROUP 2
SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 OFF SC3 50% SC4 25%
CH3
CH2
CH4
GROUP 3
Switch inputs
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
E PL
GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%
CH7
CH5
MASTER SWITCH
Master Switch
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Luminaires daylight link – all fittings dimmable
Emergency Lighting Test
Master Switch
Emergency Luminaires
Dimmable Luminaires
Configured for: l l l l
Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
1
2
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
75%
OFF
OFF
OFF
75%
75%
Scene 3
50%
50%
OFF
OFF
OFF
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
Switch input
Scene group Light levels:
▪ 55 ▪
Vitesse Plus System Manual
Preset 38 Available from version 1.00 software onwards. Large office or meeting room with detector for occupancy and no lux on any channels. 1 scene plate.
Detector/scene plate inputs
CH1
GROUP 1
GROUP 2
SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 OFF SC3 50% SC4 25%
CH3
CH2
CH4
GROUP 3
Switch inputs
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
E PL
GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%
CH7
CH5
MASTER SWITCH
Master Switch
Dimmable Luminaires
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Emergency Luminaires
Master Switch
Emergency Lighting Test
Configured for: l l l l
Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
1
2
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
75%
OFF
OFF
OFF
75%
75%
Scene 3
50%
50%
OFF
OFF
OFF
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
Switch input
Scene group Light levels:
▪ 56 ▪
Vitesse Plus System Manual
Preset 39 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1–3. Scene plate by teacher's desk. Detector for lux (scene 1 only) and absence.
Detector/scene plate inputs SW1
SW2
SW3
GROUP 1
GROUP 2
CH4
CH1
CH5
SC1 100% SC2 OFF SC3 50% SC4 25%
SC1 100% SC2 75% SC3 50% SC4 25%
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Whiteboard
GROUP 3
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 4
CH3
CH7
Whiteboard Switch
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
Dimmable Luminaires
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1 SW1: 1-C-2 Whiteboard: 7-C-8
Switch input
2 SW2: 3-C-4 Whiteboard: 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
1
1
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
OFF
OFF
OFF
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Scene group Light levels:
Max dimming level
▪ 57 ▪
Vitesse Plus System Manual
Preset 40 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 2. Scene plate by teacher's desk.
Detector/scene plate inputs SW1
SW2
SW3 GROUP 2
CH4
CH1
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
GROUP 3
GROUP 1
Whiteboard
SC1 100% SC2 75% SC3 50% SC4 25%
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6 SC1 100% SC2 OFF SC3 50% SC4 25%
Switch inputs E PL
GROUP 4
CH3
CH7
Whiteboard Switch
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1 SW1: 1-C-2
Switch input
2 SW2: 3-C-4 Whiteboard: 7-C-8
3
4
5
6
7
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
2
1
4
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
OFF
75%
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Scene group Light levels:
Max dimming level
▪ 58 ▪
Vitesse Plus System Manual
Preset 41 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1, 4 and 5. Scene plate by teacher's desk.
Detector/scene plate inputs SW1
SW2
SW3
Whiteboard Switch
Whiteboard
GROUP 1
CH1
CH4
SC1 100% SC2 OFF SC3 50% SC4 25%
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
GROUP 2
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 3
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Luminaires daylight link – graduated dimming from window row, scene 1 only
Dimmable Luminaires
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2 Whiteboard: 7-C-8
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2 Whiteboard: 7-C-8
SW1: 1-C-2 Whiteboard: 7-C-8
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
2
3
1
1
2
3
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
OFF
75%
75%
OFF
OFF
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Switch input
Scene group Light levels:
Max dimming level
▪ 59 ▪
Vitesse Plus System Manual
Preset 42 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 5. Scene plate by teacher's desk.
Detector/scene plate inputs SW1
SW2
SW3
GROUP 2
Whiteboard Switch
Whiteboard
GROUP 2
GROUP 1
CH5
CH1 SC1 100% SC2 75% SC3 50% SC4 25%
SC1 SC2 SC3 SC4
100% OFF 50% 25%
CH4
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
GROUP 3
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 4
CH3
SC1 100% SC2 75% SC3 50% SC4 25%
CH7
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Luminaires daylight link – graduated dimming from window row, scene 1 only
Dimmable Luminaires
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2
Detector input
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
2
3
Scene 1
100%
Scene 2 Scene 3 Scene 4
Switch input
Scene group
5
6
7
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
4
2
1
3
4
100%
100%
100%
100%
100%
100%
75%
75%
75%
75%
OFF
75%
75%
50%
50%
50%
50%
50%
50%
50%
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
SW1: 1-C-2 Whiteboard: 7-C-8
Light levels:
Max dimming level
▪ 60 ▪
Vitesse Plus System Manual
Preset 43 Available from version 1.00 software onwards. Classroom with 3 rows switched together but with different dimming pre-set levels per row. Whiteboard channels 1– 3. Scene plate by teacher's desk.
Detector/scene plate inputs Main Switch GROUP 1
GROUP 2
CH4
CH1
CH5
SC1 100% SC2 OFF SC3 50% SC4 25%
SC1 100% SC2 75% SC3 50% SC4 25%
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Whiteboard
GROUP 3
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 4
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
Whiteboard Switch Windows
Main Switch
Main Switch
Luminaires daylight link – graduated Dimmable Luminaires dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Main sw: 1-C-2 Whiteboard: 7-C8
Main sw: 1-C-2 Whiteboard: 7-C8
Main sw: 1-C-2 Whiteboard: 7-C8
Main sw: 1-C2
Main sw: 1-C2
Main sw: 1-C2
Main sw: 1-C2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
1
1
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
OFF
OFF
OFF
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Switch input
Scene group Light levels:
Scene 4 Max dimming level
▪ 61 ▪
Vitesse Plus System Manual
Preset 44 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channels 2. Scene plate by teacher's desk.
Detector/scene plate inputs Main Switch GROUP 2
CH4
CH1
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
GROUP 3
Whiteboard
GROUP 1
SC1 100% SC2 75% SC3 50% SC4 25%
CH2 SC1 100% SC2 OFF SC3 50% SC4 25%
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 4
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
Whiteboard Switch Windows
Main Switch
Main Switch
Luminaires daylight link – graduated Dimmable Luminaires dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Main sw: 1-C-2
Main sw: 1-C-2 Whiteboard: 7-C-8
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
2
1
4
2
2
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
OFF
75%
75%
75%
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Switch input
Scene group Light levels:
Max dimming level
▪ 62 ▪
Vitesse Plus System Manual
Preset 45 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channels 1, 4 and 5. Scene plate by teacher's desk.
Detector/scene plate inputs Main Switch
Whiteboard Switch
Whiteboard
GROUP 1
CH4
CH1
SC1 100% SC2 OFF SC3 50% SC4 25%
CH5
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be L connected to Input 1.
GROUP 2
CH2
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
Switch inputs E PL
GROUP 3
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
Main Switch
Luminaires daylight link – graduated dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Main Switch
Dimmable Luminaires
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1
2
3
4
5
6
7
Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
1
2
3
1
1
2
3
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
OFF
75%
75%
OFF
OFF
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Scene group Light levels:
Scene 4 Max dimming level
▪ 63 ▪
Vitesse Plus System Manual
Preset 46 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channel 5. Scene plate by teacher's desk.
Detector/scene plate inputs Main Switch
Whiteboard Switch
Whiteboard
GROUP 2
GROUP 2
GROUP 1
CH1 SC1 100% SC2 75% SC3 50% SC4 25%
CH5
CH4
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
GROUP 3
CH2
SC1100% SC275% SC350% SC425%
CH6
Switch inputs E PL
GROUP 4
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
Main Switch
Luminaires daylight link – graduated dimming from window row, scene 1 only
Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.
Main Switch
Dimmable Luminaires
White- Emergency board Lighting Switch Test
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Configured for: l l l l
Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2
Main sw: 1-C-2 Whiteboard: 7-C-8
Main sw: 1-C-2
Main sw: 1-C-2
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Scene plate input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
2
3
4
2
1
3
4
Scene 1
100%
100%
100%
100%
100%
100%
100%
Scene 2
75%
75%
75%
75%
OFF
75%
75%
Scene 3
50%
50%
50%
50%
50%
50%
50%
Scene 4
25%
25%
25%
25%
25%
25%
25%
100%
60%
20%
100%
100%
60%
20%
Switch input
Scene group Light levels:
Max dimming level
▪ 64 ▪
Vitesse Plus System Manual
Preset 47 - Reserved for future use Preset 48 - Reserved for future use
â–Ş 65 â–Ş
Vitesse Plus System Manual
Preset 49 Available from version 1.00 software onwards. 3 toilets each controlled separately in presence mode by a PIR connected to inputs 1, 2 and 3. Channel 1 only responds in presence mode to all 4 detector inputs.
Detector/scene plate inputs 3 toilets each controlled individually in presence mode, with the option of manual switch for absence if required. PIRs connected to inputs 1,2,3.channel 1 only responds to all 4 detector inputs. This is for water shut-off valve so that if no occupancy is detected the water supply is isolated. CH2
CH3
Upon entering the space luminaires will automatically switch on. CH1
Water shut-off valve Emergency Luminaires
CH6
CH4
CH7
Configured for: l l l
Presence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1
1
1
1
2
3
â–Ş 66 â–Ş
Vitesse Plus System Manual
Preset 50 Available from version 1.03 software onwards. Corridor with 50% of luminaires controlled by a PIR and 50% controlled by switch input.
CH1
CH6
CH2
CH6
CH3
CH6
CH4
CH7
CH5
CH7
Windows
Detector/scene plate inputs
Switch inputs
E PL
Upon entering the space luminaires will automatically switch on.
CH1 CH2 CH3 CH4
Switched by detector only
CH6 CH7
Switched by keyswitch
230v VFC relay unit 230V Live Supply
50% of the LCM is controlled via a mains rated keyswitch and VFC contact relay. this will be switched to ‘on’ during Keyswitch occupancy hours. The VFC contact provides a latching command when energised to switch on the lighting (switch input 11, paralleled with corridor hold input terminal). The rest of the LCM is responsive to PIR inputs only. During out of hours occupancy when the key switch is turned off 50% of the LCM will respond to the PIR input only.
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Detector input
1
2
3
4
5
6
7
1-4
1-4
1-4
1-4
1-4
-
-
▪ 67 ▪
Vitesse Plus System Manual
Preset 51 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
Switch input
▪ 68 ▪
Vitesse Plus System Manual
Preset 52 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
100%
60%
20%
100%
100%
60%
20%
Switch input
▪ 69 ▪
Vitesse Plus System Manual
Preset 53 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – window row only dimmable.
Dimmable Luminaires
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
▪ 70 ▪
Vitesse Plus System Manual
Preset 54 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Switch operates luminaires within the same colour dashed line.
Luminaires daylight link – window row only dimmable.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
▪ 71 ▪
Vitesse Plus System Manual
Preset 55 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs SW1
SW2
SW3
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
-
-
20%
-
-
-
20%
▪ 72 ▪
Vitesse Plus System Manual
Preset 56 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.
Detector/scene plate inputs Main Switch
CH4
CH1
CH5
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH6
CH2
E PL
CH7
CH3
Whiteboard Switch
Windows
Switch operates luminaires within the same colour dashed line.
Luminaires – window row only daylight switching.
Daylight Switching
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Main Switch
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
Main sw: 5-C-6
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 73 ▪
Vitesse Plus System Manual
Preset 57 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.
Detector/scene plate inputs SW1
SW2
SW3
CH1
Whiteboard
Window
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH5
Switch inputs
CH2
E PL
CH6
CH7
CH3
CH4
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires closest to the windows daylight dim
Dimmable Luminaires
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
Whiteboard: 7-C-8
1-4
1-4
1-4
1-4
1-4
1-4
1-4
â–Ş 74 â–Ş
Vitesse Plus System Manual
Preset 58 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.
Detector/scene plate inputs SW1
SW2
SW3
CH1
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
Switch inputs CH5
CH2
E PL
CH4
CH6
CH7
Whiteboard Switch
CH3
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires closest to the windows daylight dim.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
Whiteboard: 7-C-8
1-4
1-4
1-4
1-4
1-4
1-4
1-4
â–Ş 75 â–Ş
Vitesse Plus System Manual
Preset 59 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
Detector/scene plate inputs SW2
SW3
Whiteboard Switch Window
SW1
CH7
CH1
CH6
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH2
Switch inputs E PL
CH4
CH3
Window
CH5
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires closest to the windows daylight switch.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2
1-4
2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4
3
4
5
6
7
SW3: 5-C-6
SW3: 5-C-6
SW3: 5-C-6
SW2: 3-C-4
SW1: 1-C-2
1-4
1-4
1-4
1-4
1-4
â–Ş 76 â–Ş
Vitesse Plus System Manual
Preset 60 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.
Detector/scene plate inputs SW2
SW3
Whiteboard Switch Window
SW1
CH7
CH1
CH6
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH2
Switch inputs E PL
CH4
CH3
Window
CH5
Windows
Each switch operates luminaires within the same colour dashed line.
Luminaires closest to the windows daylight dim.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2
1-4
2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4
3
4
5
6
7
SW3: 5-C-6
SW3: 5-C-6
SW3: 5-C-6
SW2: 3-C-4
SW1: 1-C-2
1-4
1-4
1-4
1-4
1-4
â–Ş 77 â–Ş
Vitesse Plus System Manual
Preset 61 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
CH7
Windows
CH6
CH5
CH1
CH3
CH2
SW1
CH4
SW2
SW3
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable. SW1
SW2
SW3
Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW3: 5-C-6
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
2
2
3
3
1
2
3
20%
20%
20%
20%
20%
20%
20%
▪ 78 ▪
Vitesse Plus System Manual
Preset 62 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
CH7
Windows
CH6
CH5
CH1
CH3
CH2
SW1
CH4
SW2
SW3
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line.
Daylight Switching Emergency Luminaires
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only daylight switching.
SW1
SW2
SW3
Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW3: 5-C-6
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
2
2
3
3
1
2
3
▪ 79 ▪
Vitesse Plus System Manual
Preset 63 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
CH3 Windows
Windows
CH6
Windows
CH5
CH1
CH4
CH2
SW1
SW2
CH7
SW3
SW4
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line.
Dimmable Luminaires – 20% Emergency Luminaires
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only dimmable.
SW1
SW2
SW3
SW4 Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW3: 5-C-6
SW1: 1-C-2
SW2: 3-C-4
SW4: 7-C-8
2
2
3
3
1
2
4
▪ 80 ▪
Vitesse Plus System Manual
Preset 64 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
Windows
CH3
Windows
CH6
Windows
CH5
CH1
CH4
CH2
SW1
SW2
CH7
SW3
SW4
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line.
Daylight Switching Emergency Luminaires
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only daylight switching.
SW1
SW2
SW3
SW4 Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW3: 5-C-6
SW1: 1-C-2
SW2: 3-C-4
SW4: 7-C-8
2
2
3
3
1
2
4
▪ 81 ▪
Vitesse Plus System Manual
Preset 65 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
SW3
Windows
Windows
CH5
CH7
CH1
CH2
CH4
CH3
SW1
CH6
SW3
SW2
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable. SW1
SW2
SW3
Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2
1
2
2
3
2
3
1
20%
20%
20%
20%
20%
20%
20%
▪ 82 ▪
Vitesse Plus System Manual
Preset 66 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.
Windows
Windows
Windows
SW3
Windows
Windows
CH5
CH7
CH1
CH2
CH4
CH3
SW1
CH6
SW3
SW2
E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
Emergency Lighting Test
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW2: 3-C-4
SW3: 5-C-6
SW1: 1-C-2
1
2
2
3
2
3
1
▪ 83 ▪
Vitesse Plus System Manual
Preset 67 Available from version 1.03 software onwards. Open plan office with graduated dimming.
Detector/scene plate inputs Windows
Windows
CH1
CH2
CH3
Switch inputs CH4
CH5
E PL
CH7
CH6
SW1
SW1
SW2
SW2
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires
Emergency Luminaires
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 5-C-6
SW2: 5-C-6
Detector input
1, 2
1, 2
1, 2
1, 2
1, 2
3, 4
3, 4
Dimming level
20%
20%
20%
60%
60%
-
-
Switch input
▪ 84 ▪
Vitesse Plus System Manual
Preset 68 Available from version 1.03 software onwards. Open plan office with graduated dimming.
Windows
CH1
CH2
CH5
SW1
CH3
CH7
CH4
CH6
SW2
E
Detector/scene plate inputs
Switch inputs
PL
Dimmable Luminaires
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Emergency Luminaires
Luminaires daylight link – graduated dimming from window row. SW1
SW2
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 5-C-6
SW2: 5-C-6
Detector input
1, 2
1, 2
1, 2
1, 2
1, 2
3, 4
3, 4
Dimming level
20%
20%
20%
60%
60%
20%
60%
Switch input
▪ 85 ▪
Vitesse Plus System Manual
Preset 69 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.
Detector/scene plate inputs
Whiteboard
SW1
SW2
SW3
CH1
CH4
CH2
CH6
CH5
Switch inputs E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – all luminaires dimmable.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Dimmable Luminaires – 20% Emergency Luminaires
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
SW1: 1-C-2
Whiteboard: 7-C-8
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1
2
4
1
1
3
4
20%
20%
20%
20%
20%
20%
20%
▪ 86 ▪
Vitesse Plus System Manual
Preset 70 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.
Detector/scene plate inputs
Whiteboard
SW1
SW2
SW3
CH1
CH4
CH2
CH6
CH5
Switch inputs E PL
CH7
CH3
Whiteboard Switch
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – all luminaires daylight switch.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Daylight Switching Emergency Luminaires
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input Min dimming level
1
2
3
4
5
6
7
SW1: 1-C-2
Whiteboard: 7-C-8
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1
2
4
1
1
3
4
20%
20%
20%
20%
20%
20%
20%
▪ 87 ▪
Vitesse Plus System Manual
Preset 71 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1-3 switched separately.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2 Whiteboard: 7-C-8 1
2 SW2: 3-C-4 Whiteboard: 7-C-8 2
3 SW3: 5-C-6 Whiteboard: 7-C-8 3
â–Ş 88 â–Ş
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1
1
2
3
Vitesse Plus System Manual
Preset 72 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1,2 and 3.
Detector/scene plate inputs SW1
SW2
SW3
Whiteboard Switch
CH5
CH4
CH1
Windows
Whiteboard
If using 3 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.
CH6
CH2
E PL
CH3
CH7
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – window rows only dimmable.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Dimmable Luminaires – 20% Emergency Luminaires
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4
2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4
3 SW3: 5-C-6 Whiteboard: 7-C-8 1-4
▪ 89 ▪
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
1-4
1-4
1-4
1-4
Vitesse Plus System Manual
Preset 73 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channels 1,2 and 3.
Detector/scene plate inputs SW1
SW2
SW3
Whiteboard Switch
CH1
Windows
Whiteboard
If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be
CH5
CH2
Switch inputs E PL
CH7
CH4
CH6
CH3
Windows
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW1
SW2
SW3
White- Emergency board Lighting Switch Test
Dimmable Luminaires – 20%
Luminaires daylight link – window rows only dimmable.
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
Whiteboard: 7-C-8
Whiteboard: 7-C-8
Whiteboard: 7-C-8
SW3: 5-C-6
SW3: 5-C-6
SW2: 3-C-4
SW1: 1-C-2
1-4
1-4
1-4
1-4
1-4
1-4
1-4
▪ 90 ▪
Vitesse Plus System Manual
Presets 74 and 75 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual centre-biased retractive switch in each. Dual supply using 2 LCMs: l l
Essential LCM = preset 74 Non-essential LCM = preset 75
Windows
CH1
Windows
CH2
Windows
CH4
CH3
SW1
Windows
SW2
CH5
Windows
CH6
SW3
CH7
SW4
Switch inputs
Non Essential preset 75
E PL
Detector/scene plate inputs Essential preset 74
Each switch operates luminaires within the same colour dashed line. Luminaires daylight link- window row only dimmable.
Non Essential preset 75
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Essential preset 74
E
Dimmable Luminaires – 20%
PL
Emergency Luminaires
SW1
SW2
SW3
SW4
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
SW4: 7-C-8
SW4: 7-C-8
SW4: 7-C-8
1
1
2
3
4
4
4
▪ 91 ▪
Vitesse Plus System Manual
Preset 76 Available from version 1.03 software onwards. 2 cellular offices individually controlled with a presence detector and/ or manual centre-retractive switch in each. Dual supply (essential and non-essential) using 2 LCMs.
Windows
Windows
CH1
CH2
Windows
CH3
CH4
Windows
CH5
CH7
CH6
SW1
SW2
SW3
SW4
Switch inputs
Non Essential preset 76
E PL
Detector/scene plate inputs Essential preset 76
Each switch operates luminaires within the same colour dashed line. Luminaires daylight link- window row only dimmable.
Non Essential preset 76
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Essential preset 76
E
Dimmable Luminaires – 20%
PL
Emergency Luminaires
SW1
SW2
SW3
SW4
Configured for: l l l
Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input Detector input
1
2
3
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW2: 3-C-4
SW3: 5-C-6
SW4: 7-C-8
1
1
1
2
2
2
2
▪ 92 ▪
Vitesse Plus System Manual
Preset 77 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
Detector/scene plate inputs Windows
Windows
Windows
SW3
CH5
Whiteboard
CH3
CH7
CH2
Switch inputs E PL
SW1
CH4
CH6
CH1
SW1
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW2
SW3
Whiteboard Switch
Upon entering the space luminaires will automatically switch on – store cupboard only.
SW1
SW2
White- Emergency board Lighting Switch Test
SW3
Luminaires daylight link – graduated dimming from window row. Dimmable Luminaires Emergency Luminaires
Configured for: l l l
Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW2: 3-C-4 Whiteboard: 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
N/A
SW2: 3-C-4
SW1: 1-C-2
SW3: 5-C-6
Detector input
1-3
1-3
1-3
4
1-3
1-3
1-3
Dimming level
100%
60%
20%
-
60%
100%
20%
▪ 93 ▪
Vitesse Plus System Manual
Preset 78 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
Detector/scene plate inputs Windows
Windows
Windows
SW3
CH7
CH5
Whiteboard
CH3
CH2
Switch inputs E PL
SW1
CH4
CH1
CH6
SW1
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
SW2
SW3
Whiteboard Switch
Upon entering the space luminaires will automatically switch on – store cupboard only.
SW2
SW1
White- Emergency board Lighting Switch Test
SW3
Luminaires daylight link – window row only dimmable. Dimmable Luminaires Emergency Luminaires
Configured for: l l l
Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW2: 3-C-4 Whiteboard: 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
N/A
SW2: 3-C-4
SW1: 1-C-2
SW3: 5-C-6
Detector input
1-3
1-3
1-3
4
1-3
1-3
1-3
Dimming level
-
-
20%
-
-
-
20%
▪ 94 ▪
Vitesse Plus System Manual
Preset 79 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
Detector/scene plate inputs Windows
Windows
Windows
SW1
CH5
Whiteboard
CH3
CH7
CH2
Switch inputs E PL
CH4
CH6
CH1
SW1
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Whiteboard Switch
Upon entering the space luminaires will automatically switch on – store cupboard only.
SW1
Whiteboard Switch
Luminaires daylight link – graduated dimming from window row.
Emergency Lighting Test
Dimmable Luminaires Emergency Luminaires
Configured for: l l l
Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW1: 1-C-2 Whiteboard: 7-C-8
3 SW1: 1-C-2 Whiteboard: 7-C-8
4
5
6
7
N/A
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1-3
1-3
1-3
4
1-3
1-3
1-3
Dimming level
100%
60%
20%
-
60%
100%
20%
▪ 95 ▪
Vitesse Plus System Manual
Preset 80 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.
Detector/scene plate inputs Windows
Windows
Windows
SW1
CH5
Whiteboard
CH3
CH7
CH2
Switch inputs E PL
CH6
CH4
CH1
SW1
Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Whiteboard Switch
Upon entering the space luminaires will automatically switch on – store cupboard only.
Whiteboard Switch
SW1
Luminaires daylight link – window row only dimmable.
Emergency Lighting Test
Dimmable Luminaires Emergency Luminaires
Configured for: l l l
Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard: 7-C-8
2 SW1: 1-C-2 Whiteboard: 7-C-8
3 SW1: 1-C-2 Whiteboard: 7-C-8
4
5
6
7
N/A
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1-3
1-3
1-3
4
1-3
1-3
1-3
Dimming level
-
-
20%
-
-
-
20%
▪ 96 ▪
Vitesse Plus System Manual
Preset 81 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode, and store cupboards/ WC working independently in presence mode.
Detector/scene plate inputs Windows
Windows
Windows
SW1
CH2 Whiteboard
CH7
Switch inputs E
CH5
CH3
CH4
CH1
SW1
Whiteboard Switch
PL
Whiteboard Switch
Each switch operates luminaires within the same colour dashed line.
Upon entering the space luminaires will automatically switch on – toilets only.
Switches and dims the whiteboard luminaires independently within the same colour dashed line.
Luminaires daylight link – window row only dimmable.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires
SW1
Whiteboard Switch
Whiteboard Switch
Emergency Lighting Test
Emergency Luminaires
Configured for: l l l
Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 Whiteboard 1: 3-C-4 Whiteboard 2: 7-C-8
2 SW1: 1-C-2 Whiteboard 1: 3-C-4 Whiteboard 2: 7-C-8
3
4
5
6
7
N/A
N/A
SW1: 1-C-2
SW1: 1-C-2
SW1: 1-C-2
Detector input
1, 2
1, 2
3
4
1, 2
1, 2
1, 2
Dimming level
-
20%
-
-
-
-
20%
▪ 97 ▪
Vitesse Plus System Manual
Preset 82 Available from version 1.04 software onwards. Classroom with 3 columns of luminaires working in absence mode. All fittings dimmable from switches but only window row responsive to lux.
Detector/scene plate inputs Windows
Windows
SW2 SW4
CH1
SW3
CH2
CH3
Switch inputs E
CH4
PL
CH5
CH6
SW1
SW2
CH7
SW3
SW4
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – window row only dimmable.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20%
SW1
SW2
SW4
SW3
Emergency Lighting Test
Emergency Luminaires
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel Switch input
1 SW1: 1-C-2 SW4: 7-C-8
2 SW2: 3-C-4 Whiteboard: : 7-C-8
3 SW3: 5-C-6 Whiteboard: 7-C-8
4
5
6
7
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
20%
20%
20%
-
-
-
-
▪ 98 ▪
Vitesse Plus System Manual
Preset 83 Available from version 1.04 software onwards. Classroom with 3 columns of luminaires working in absence mode all fittings switching from switches but only window row responsive to lux.
Detector/scene plate inputs Windows
Windows
SW2 SW4
CH1
SW3
CH2
CH3
Switch inputs E
CH4
PL
CH5
CH6
SW1
SW2
CH7
SW3
SW4
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – window row only daylight switching.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching
SW1
SW2
SW4
SW3
Emergency Lighting Test
Emergency Luminaires
Configured for: l l l
Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)
Channel
1
2
3
4
5
6
7
SW1: 1-C-2 SW4: 7-C-8
SW2: 3-C-4 SW4: 7-C-8
SW3: 5-C-6
SW1: 1-C-2
SW1: 1-C-2
SW2: 3-C-4
SW3: 5-C-6
Detector input
1-4
1-4
1-4
1-4
1-4
1-4
1-4
Dimming level
20%
20%
20%
-
-
-
-
Switch input
▪ 99 ▪
CP Electronics - a business unit of Legrand Electric Limited Brent Crescent, London NW10 7XR UK www.cpelectronics.co.uk enquiry@cpelectronics.co.uk Tel: +44 (0)333 900 0671 Fax: +44 (0)333 900 0674 Due to our policy of continual product improvement, CPÂ Electronics reserves the right to alter the specification of this product without prior notice. Ref WD817 issue 3.1