WD817 - VITP7 system manual (EN)

Page 1

Vitesse Plus - System Manual © C P Electronics 2018 Issue 3.1


Vitesse Plus System Manual

CONTENTS Contents

2

About Vitesse Plus

3

LCM connections Quick start

3 4

How to program with a preset configuration

5

Open Port programming

5

How to set up an environment with several LCMs

7

Example behaviour

8

Preset configurations by application

9

Commercial preset configurations Healthcare configurations Education preset configurations

9 9 10

Graduated dimming

10

Perimeter dimming

11

Perimeter switching

11

Room dimming configurations

12

Room switching configurations

12

Windows on 2 sides of room

12

Classroom with store cupboard/WC

12

Scene setting preset configurations Corridor preset configurations Toilet preset configurations

13 13 13

Index

14

Preset configurations by number

19

â–Ş2â–Ş


Vitesse Plus System Manual

ABOUT VITESSE PLUS Vitesse plus is a flexible lighting control system which provides effective power delivery and control for lighting installations in commercial, educational and healthcare buildings. Vitesse Plus is designed for ease of installation: mains input is connected using the spacious wiring compartment; control inputs and outputs are pluggable using industry standard connectors. The Vitesse Plus lighting control module (LCM) has 12 luminaire outputs, which can be configured as seven separate channels if required. All control inputs are SELV and provide a variety of functions such as presence and absence detection, daylight linking and manual dimming.

LCM connections

â–Ş3â–Ş


Vitesse Plus System Manual

Quick start Connect all detectors and switches to the LCM before following this procedure. Refer to the VITP7-MB installation guide for details on how to do this. Use the following procedure with the UNLCDHS handset to get your Vitesse Plus installation up and running:

1

2

Connect the power to the LCM. It then goes through a power-up sequence of 8 seconds, after which all connected lights switch on.

3

and press

Rapid à

.

5

Vitesse Plus

>

Handset Config

>

VITESSE PLUS à

Select LCM and press

or

6

à Program

or

to turn on the programming handset.

>

LCM

Select Program and press

ON/OFF

4

PRODUCT FAMILY

Select Vitesse Plus from the main PRODUCT FAMILY menu

Press

>

Device Info

>

Select Preset and type in the number of the preset.

8 Press

twice to return to the Vitesse Plus menu.

device and press . An LED flashes red/green to acknowledge the command, then green till the preset is programmed.

9

10

VITESSE PLUS

Select Detector and press or

.

à

LCM

>

Detector

>

Scene Panel

>

11

Select Program and press

Select Timeout (mins) and enter the number of minutes to wait (0 - 99) before lights turn off when absence detected.

à Timeout (mins) Light Level (MI) Detection Mode

10 600 No

Select Light Level (MI) and enter the target value (0-999) that daylight linking is to maintain.

14

Point the handset directly at the

Perform this sequence with the centre-biased retractive switch to activate daylight linking:

.

1. 2. 3. 4.

▪4▪

DALI

Detection Mode

Pres

LCM

>

Detector

>

Scene Panel

>

Program

>

User

>

Device Info

>

PROGRAM

13

device and press

Load Type

.

12

PROGRAM

7

DETECTOR à

or

>

VITESSE PLUS à

Point the handset directly at the

>

Scene Panel

à Preset

.

7

>

Detector

PROGRAM

>

Lux Settings

.

LCM

Dim all the way down Dim all the way up Switch off Switch on

Timeout (mins) à

Light Level (MI) Detection Mode

10 600 No


Vitesse Plus System Manual

HOW TO PROGRAM WITH A PRESET CONFIGURATION Use the UNLCDHS handset to send the required preset configuration to the LCM. 1. Select Vitesse Plus from the main PRODUCT FAMILY menu and press 2. Select LCM and press

or

3. Select Program and press

.

. or

.

4. Select Preset and type in the number of the configuration. 5. Point the handset directly at the device and press

.

Open Port programming If the LCM is not in the line of sight of the handset, you can send the preset through a detector if one is connected. 1. Select Vitesse Plus from the main PRODUCT FAMILY menu and press 2. Select Detector and press 3. Select Program and press

or or

. .

4. Select Advanced Config and press 5. Select Open Port and press

.

or

.

to set it to Yes.

6. Point the handset directly at the device and press . The detector's LED flashes to show it has received the command and then stays red. This indicates the port is open and ready to forward settings to the LCM. 7. Press

until you return the to the Detector menu.

8. Select Detector ID and make sure the value is set to 100. Point the handset directly at the device and press

.

9. Select Program and press

or

.

10. Select Preset and type in the number of the configuration. Point the handset directly at the device and press

.

11. Select Advanced Config and press 12. Select Open Port and press

or

.

to set it to No.

13. Point the handset at the detector and press command and then goes off.

. The detector's LED flashes to show it has received the

â–Ş5â–Ş


Vitesse Plus System Manual

Notes

▪6▪


Vitesse Plus System Manual

HOW TO SET UP AN ENVIRONMENT WITH SEVERAL LCMS 1

2

Send the same preset configuration to each LCM.

Connect the LCMs to each other using RJ45 patch leads.

▪7▪


Vitesse Plus System Manual

Example behaviour In this example, configuration N's parameters mean that when the detector detects presence, luminaires connected to channels 1, 2 and 3 dim up to 100%, those connected to channels 4, 5 and 6 dim up to 50%.

a

b

c

As all LCMs are programmed with configuration N, presence detection causes luminaires connected to all instances of channel 1, 2 and 3 to dim up to 100%, whichever LCM they are plugged into.

Because the LCMs are connected to each other, it doesn't matter which detector detects presence. If a different detector picks up presence, the effect on the luminaires is the same.

Plugging a luminaire into a different channel can change how it reacts when presence is detected. In this case, moving the luminaires from the bottom right LCM's channels 4, 5 and 6 to channels 1, 2 and 3 results in them dimming up to 100% instead of the 50% shown in the other scenarios above.

â–Ş8â–Ş


Vitesse Plus System Manual

PRESET CONFIGURATIONS BY APPLICATION Commercial preset configurations Lighting arrangement

2 rows of 5 luminaires

Room setup

Control method

Preset #

See page

4 cellular offices with 1 switch for Daylight linking each office; channel arrangement #1 Daylight switching

1

page 19

2

page 20

4 cellular offices with 1 switch for Daylight linking each office; channel arrangement #2 Daylight switching

63

page 80

64

page 81

Daylight linking

3

page 21

Daylight switching

4

page 22

61

page 78

62

page 79

Daylight linking, only window row dimmable

5

page 23

Daylight switching, only window row dimmable

6

page 24

No dimming luminaires

7

page 25

Daylight linking, all luminaires dimmable

67

page 84

3 cellular offices with 1 switch for Daylight linking each office Daylight switching

65

page 82

66

page 83

Open plan office

68

page 85

Open plan office 3 cellular offices with 1 switch for Daylight linking each office Daylight switching

3 rows of 4 luminaires

2 rows of 6 luminaires

Open plan office

Daylight linking

Healthcare configurations These configurations are for rooms in hospitals and similar buildings where there are two power supplies, one for essential and emergency applications and one for non-essential applications. Daylight dimming Lighting arrangement 2 rows of 7 luminaires 2 rows of 6 luminaires

Room setup

Supply

Preset#

See page

Essential

74

page 91

Non-essential

75

page 91

Essential and non-essential

76

page 92

4 cellular offices 2 cellular offices

▪9▪


Vitesse Plus System Manual

Education preset configurations These configurations are for classrooms with windows on just one side of the room, with the exception of Presets 58-60, 72 and 73.

Graduated dimming Lighting arrangement

Room switches

3 rows of 3 dimmable lights

Preset See page #

Whiteboard switch for 3 lights, 1 per row (2x PIR, 1x microwave)

10

page 28

Whiteboard switch for 1 light (also controlled by row switch)

11

page 29

Whiteboard switch for 1 row of lights

12

page 30

Whiteboard switch for 2 lights within 1 row.

13

page 31

Whiteboard switch for 3 lights, 1 per row.

14

page 32

Whiteboard switch for 1 light

15

page 33

Whiteboard switch for 1 row of lights

16

page 34

Whiteboard switch for 2 lights within 1 row.

17

page 35

3 switches, 1 per row of luminaires (whiteboard lights separate)

Whiteboard switch for 3 separate lights

51

page 68

1 switch for all lights (whiteboard lights separate)

Whiteboard switch for 3 separate lights

52

page 69

82

page 98

3 switches, 1 per row of luminaires

3 rows of 4 dimmable lights

Whiteboard setup

1 switch for all lights

3 switches, 1 per column Whiteboard switch for 3 lights, 1 per of luminaires column

â–Ş 10 â–Ş


Vitesse Plus System Manual

Perimeter dimming Lighting arrangement

Room switches

Preset See page #

Whiteboard switch for 3 lights, 1 per row. 18

page 36

Whiteboard switch for 1 light.

19

page 37

Whiteboard switch for 1 row of lights

20

page 38

Whiteboard switch for 2 lights within 1 row.

21

page 39

Whiteboard switch for 3 lights, 1 per row. 22

page 40

Whiteboard switch for 1 light.

23

page 41

Whiteboard switch for 1 row of lights

24

page 42

Whiteboard switch for 2 lights within 1 row.

25

page 43

3 switches, 1 per row of luminaires (whiteboard lights separate)

Whiteboard switch for 3 separate lights

53

page 70

1 switch for all lights (whiteboard lights separate)

Whiteboard switch for 3 separate lights

54

page 71

3 switches, 1 per row of luminaires.

3 rows of 4 lights, only window row dimmable

Whiteboard setup

1 switch for all lights

Perimeter switching Lighting arrangement

Room switches

3 rows of 3 lights, window row daylight switching

Preset See page #

Whiteboard switch for 3 lights, 1 per row. 26

page 44

Whiteboard switch for 1 light.

27

page 45

Whiteboard switch for 1 row of lights

28

page 46

Whiteboard switch for 2 lights within 1 row.

29

page 47

Whiteboard switch for 3 lights, 1 per row. 30

page 48

Whiteboard switch for 1 light.

31

page 49

Whiteboard switch for 1 row of lights

32

page 50

Whiteboard switch for 2 lights within 1 row.

33

page 51

3 switches, 1 per row of luminaires (whiteboard lights separate)

Whiteboard switch for 3 separate lights

55

page 72

1 switch for all lights (whiteboard lights separate)

Whiteboard switch for 3 separate lights

56

page 73

83

page 99

3 switches, 1 per row of luminaires.

3 rows of 4 lights, window row daylight switching

Whiteboard setup

1 switch for all lights

3 switches, 1 per column Whiteboard switch for 3 lights, 1 per of luminaires column

▪ 11 ▪


Vitesse Plus System Manual

Room dimming configurations Lighting arrangement

Room switches

Whiteboard setup

Preset See page #

3 rows of 4 lights dimming

3 switches, 1 per row of luminaires, whiteboard separate

Whiteboard switch for 1 light

69

page 86

3 rows of 4 lights dimming

3 switches, 1 per row of luminaires, whiteboard separate

Whiteboard switch for 3 lights

71

page 88

3 rows of lights, only those by windows dimmable

3 switches, 1 per row of luminaires

Whiteboard lights also controlled by row switches

72

page 89

Room switching configurations Lighting arrangement

3 rows of 4 lights

Room switches 3 switches, 1 per row of luminaires, whiteboard separate

Whiteboard setup

Whiteboard switch for 1 light

Preset See page # 70

page 87

Windows on 2 sides of room Lighting arrangement

Room switches

Whiteboard setup

Preset See page #

3 switches, 1 per column of 3 rows of lights, only those luminaire by windows daylight 3 switches, 1 per row of switching luminaires

Whiteboard switch for 3 separate lights

57

page 74

Whiteboard switch for 1 light

58

page 75

3 switches, 1 per column of luminaires

Whiteboard switch for 3 separate lights

59

page 76

Whiteboard switch for 1 light

60

page 77

Whiteboard switch for 3 separate lights

73

page 90

3 rows of lights, only those by windows dimmable 3 switches, 1 per row of luminaires

Classroom with store cupboard/WC Lighting arrangement

10 classroom lights, one store cupboard light

Room switches

Dimming luminaire?

Preset See page #

3 switches, 1 per row of All classroom lights dimmable luminaires, plus 1 for whiteboard only Only window row dimmable

77

page 93

78

page 94

All classroom lights dimmable

79

page 95

Only window row dimmable

80

page 96

All classroom lights dimmable

81

page 97

1 switch for all lights, 1 for whiteboard only 7 classroom lights, two WC 1 switch for all lights, 2 for lights whiteboard only

â–Ş 12 â–Ş


Vitesse Plus System Manual

Scene setting preset configurations Lighting arrangement 2 rows of dimmable lights(commercial application)

3 rows of dimmable lights (commercial application)

Room setup

Preset See page #

Scene setting

2 switches, 1 per room

Scenes 1 to 4 = light to dark

34

page 52

4 switches, 1 per room

Scenes 1 to 4 = light to dark

35

page 53

1 switch for all lights, 1 window group

Scene 2 = window row off, others 75%

36

page 54

1 switch for all lights, 2 window groups daylight linked

Scenes 2 and 3 = window row off, others 75%

37

page 55

1 switch for all lights, 2 window groups

Scenes 2 and 3 = window row off, others 75%

38

page 56

Scene 2 = Whiteboard lights off, others 75%

39

page 57

Scene 2 = Centre whiteboard off, others 75%

40

page 58

Scene 2 = Whiteboard row off, others 75%

41

page 59

Scene 2 = Light closest to whiteboard off, others 75%

42

page 60

Scene 2 = Whiteboard lights off, others 75%

43

page 61

Scene 2 = Centre whiteboard off, others 75%

44

page 62

Scene 2 = Whiteboard row off, others 75%

45

page 63

Scene 2 = Light closest to whiteboard off, others 75%

46

page 64

Reserved for future use

47

page 65

Reserved for future use

48

page 65

3 switches, 1 per row of luminaires.

3 rows of dimmable lights (education applications) 1 switch for all lights

Corridor preset configurations Lighting arrangement

Room setup

Control method

1 row of 10 luminaires

Corridor

Detector only

2 rows of 5 luminaires plus corridor

4 classrooms plus corridor

Preset#

See page

50

page 67

Daylight switching

8

page 26

Daylight dimming

9

page 27

Toilet preset configurations Lighting arrangement 3 toilets, 2 or 3 luminaires in each

Room switches

Dimming luminaire?

Preset #

None

None

49

▪ 13 ▪

See page page 66


Vitesse Plus System Manual

INDEX Commercial Preset #

See page

1

4 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 19

2

4 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 20

3

Open plan office working in presence mode with channels 5, 6 and 7 daylight dimming for perimeter rows.

page 21

4

Open plan office working in presence mode with channels 5, 6 and 7 daylight switching for perimeter rows.

page 22

5

Open plan office working in presence mode with channels 1–4 daylight dimming for perimeter rows.

page 23

6

Open plan office working in presence mode with channels 1–4 daylight switching for perimeter rows.

page 24

7

Standard open plan office arrangement, operating in presence mode.

page 25

61

3 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 78

62

3 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 79

63

4 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 80

64

4 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 81

65

3 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 82

66

3 cellular offices individually controlled with a presence detector and/or manual switch in each.

page 83

67

Open plan office with graduated dimming.

page 84

68

Open plan office with graduated dimming.

page 85

Corridor Preset#

See page

8

Corridor with lux switching. Presence mode only.

page 26

9

Corridor with dimming. Presence mode only.

page 27

50

Corridor with 50% of luminaires controlled by a PIR and 50% controlled by switch input.

page 67

▪ 14 ▪


Vitesse Plus System Manual

Education: Graduated dimming Preset #

See page

10

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 28 2 and 3.

11

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

12

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 30 4 and 5.

13

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

page 31

14

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

page 32

15

Classroom with luminaires working in absence mode. Whiteboard on channel 2.

page 33

16

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

page 34

17

Classroom with luminaires working in absence mode. Whiteboard on channel 5.

page 35

51

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 68 2 and 3 switched independently.

52

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

page 69

82

Classroom with 3 columns of luminaires working in absence mode. All fittings dimmable from switches but only window row responsive to lux.

page 98

page 29

Perimeter dimming Preset #

See page

18

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 36 2 and 3.

19

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

20

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 38 4 and 5.

21

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

page 39

22

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

page 40

23

Classroom with luminaires working in absence mode. Whiteboard on channel 2.

page 41

24

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

page 42

25

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

page 43

53

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 70 2 and 3 switched independently.

54

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

page 37

page 71

Perimeter switching Preset #

See page

26

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 44 2 and 3.

27

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

â–Ş 15 â–Ş

page 45


Vitesse Plus System Manual

Preset #

See page

28

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 46 4 and 5.

29

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

page 47

30

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

page 48

31

Classroom with luminaires working in absence mode. Whiteboard on channel 2.

page 49

32

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

page 50

33

Classroom with luminaires working in absence mode. Whiteboard on channel 5.

page 51

55

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, page 72 2 and 3 switched independently.

56

Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

page 73

83

Classroom with 3 columns of luminaires working in absence mode all fittings switching from switches but only window row responsive to lux.

page 99

Room dimming (all fittings 20%) Preset #

See page

69

Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.

page 86

71

Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1-3 switched separately.

page 88

72

Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1,2 and 3.

page 89

Room switching Preset # 70

See page Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.

page 87

Windows on 2 sides of room Preset #

See page

57

Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.

page 74

58

Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.

page 75

59

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

page 76

60

Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

page 77

73

Classroom with 4 columns of fittings working in absence mode. Whiteboard on channels 1,2 and 3.

page 90

Classroom with store cupboard/WC Preset # 77

See page Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

â–Ş 16 â–Ş

page 93


Vitesse Plus System Manual

Preset #

See page

78

Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

page 94

79

Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

page 95

80

Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

page 96

81

Classroom with luminaires working in absence mode, and store cupboards/ WC working independently in presence mode.

page 97

Scene setting: Commercial applications Preset #

See page

34

Two cellular offices with a detector and scene plate in each. Option for local switch in each office.

page 52

35

4 cellular offices with a scene plate in each. Option for local switch in each office. Detector in each.

page 53

36

Large office/meeting room with detector used for lux and occupancy and scene plate and option for master all on switch 1 scene selection switch.

page 54

37

Large office or meeting room with lux referenced on channels 1-3 only. Detector used for lux and occupancy, 1 scene plate.

page 55

38

Large office or meeting room with detector for occupancy and no lux on any channels. 1 scene plate.

page 56

Education applications Preset #

See page

39

Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1–3. Scene plate by teacher's desk. Detector for lux (scene 1 only) and absence.

page 57

40

Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 2. Scene plate by teacher's desk.

page 58

41

lassroom with 3 rows of fittings switched individually. Whiteboard row on channels 1, 4 and 5. Scene plate by teacher's desk.

page 59

42

Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 5. Scene plate by teacher's desk.

page 60

43

Classroom with 3 rows switched together but with different dimming pre-set levels per row. Whiteboard channels 1–3. Scene plate by teacher's desk.

page 61

44

Classroom with all fittings switched together. Whiteboard on channels 2. Scene plate by teacher's desk.

page 62

45

Classroom with all fittings switched together. Whiteboard on channels 1, 4 and 5. Scene plate by teacher's desk.

page 63

46

Classroom with all fittings switched together. Whiteboard on channel 5. Scene plate by teacher's desk.

page 64

47

Reserved for future use

48

Reserved for future use

▪ 17 ▪


Vitesse Plus System Manual

Toilet Preset # 49

See page 3 toilets each controlled separately in presence mode by a PIR connected to inputs 1, 2 and 3. Channel 1 only responds in presence mode to all 4 detector inputs.

page 66

Healthcare Preset#

See page

74

4 cellular offices individually controlled with a presence detector and/or manual centrebiased retractive switch in each. Dual supply using 2 LCMs

page 91

75

4 cellular offices individually controlled with a presence detector and/or manual centrebiased retractive switch in each. Dual supply using 2 LCMs

page 91

76

2 cellular offices individually controlled with a presence detector and/ or manual centreretractive switch in each. Dual supply (essential and non-essential) using 2 LCMs.

page 92

â–Ş 18 â–Ş


Vitesse Plus System Manual

PRESET CONFIGURATIONS BY NUMBER Preset 1 Available from version 1.00 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

CH6

CH6

CH7

CH1

CH2

CH2

CH3

Windows

CH5

SW1

SW2

CH4

SW3

SW4

E PL

Switch inputs

Detector/scene plate inputs

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20% Emergency Luminaires

Luminaires daylight link – window row only dimmable SW1

SW2

SW3

SW4 Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW2: : 3, C,4

SW3: 5-C-6

SW4: 7-C-8

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1

2

3

4

1

2

3

▪ 19 ▪


Vitesse Plus System Manual

Preset 2 Available from version 1.00 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

CH6

CH6

CH7

CH1

CH2

CH2

CH3

Windows

CH5

Windows

SW1

SW2

CH4

SW3

SW4

E PL

Switch inputs

Detector/scene plate inputs

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching Emergency Luminaires

Luminaires daylight link – window row only daylight switching. SW1

SW2

SW3

SW4 Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

SW4: 7-C-8

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1

2

3

4

1

2

3

▪ 20 ▪


Vitesse Plus System Manual

Preset 3 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 5, 6 and 7 daylight dimming for perimeter rows.

Windows

CH6

CH5 Windows

CH1

CH2

CH4

CH3

CH7

Detector/scene plate inputs

Upon entering the space luminaires will automatically switch on.

Luminaires daylight link – window row only dimmable

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20%

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 21 ▪


Vitesse Plus System Manual

Preset 4 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 5, 6 and 7 daylight switching for perimeter rows.

Windows

CH6

CH5 Windows

CH1

CH2

CH3

CH7

CH4

Detector/scene plate inputs

Upon entering the space luminaires will automatically switch on.

Luminaires daylight link – window row only daylight switching.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 22 ▪


Vitesse Plus System Manual

Preset 5 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 1–4 daylight dimming for perimeter rows.

Detector/scene plate inputs Windows

CH1

CH2

CH3

CH4

CH5

CH7

CH6

Upon entering the space luminaires will automatically switch on.

Luminaires daylight link – window row only dimmable

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20%

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 23 ▪


Vitesse Plus System Manual

Preset 6 Available from version 1.00 software onwards. Open plan office working in presence mode with channels 1–4 daylight switching for perimeter rows.

Detector/scene plate inputs Windows

CH1

CH2

CH3

CH4

CH5

CH7

CH6

Upon entering the space luminaires will automatically switch on.

Luminaires daylight link – window row only daylight switching.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 24 ▪


Vitesse Plus System Manual

Preset 7 Available from version 1.00 software onwards. Standard open plan office arrangement, operating in presence mode.

Detector/scene plate inputs Windows

CH1

CH2

CH3

CH4

CH5

CH7

CH6

Upon entering the space luminaires will automatically switch on.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

â–Ş 25 â–Ş


Vitesse Plus System Manual

Preset 8 Available from version 1.00 software onwards. Corridor with lux switching. Presence mode only. The maximum number of LCMs connected together using the corridor hold connections is 20. The CSA of the cable should be 1.50mm and the length of run should not exceed 100m.

Configured for: l Presence detection l Corridor hold = Latching switch (terminal 11) l ELT keyswitch = latching switch (terminal 10) Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

â–Ş 26 â–Ş


Vitesse Plus System Manual

Preset 9 Available from version 1.00 software onwards. Corridor with dimming. Presence mode only. The maximum number of LCMs connected together using the corridor hold connections is 20. The CSA of the cable should be 1.50mm and the length of run should not exceed 100m.

Configured for: l Presence detection l Corridor hold = Latching switch (terminal 11) l ELT keyswitch = latching switch (terminal 10) Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

1-4

1-4

â–Ş 27 â–Ş


Vitesse Plus System Manual

Preset 10 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW2: 3-C-4 Whiteboard: 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

SW1: 1-C-2

SW1: 1, C,2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

â–Ş 28 â–Ş


Vitesse Plus System Manual

Preset 11 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2

2 SW2: 3-C-4 Whiteboard: 7-C-8

3

4

5

6

7

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

â–Ş 29 â–Ş


Vitesse Plus System Manual

Preset 12 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2

3

SW2: 3-C-4

SW3: 5-C-6

4 SW1: 1-C-2 Whiteboard: 7-C-8

5 SW1: 1-C-2 Whiteboard: 7-C-8

6

7

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

â–Ş 30 â–Ş


Vitesse Plus System Manual

Preset 13 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2

Detector input

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

Switch input

â–Ş 31 â–Ş

5

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

100%

60%

20%

SW1: 1-C-2 Whiteboard: 7-C-8


Vitesse Plus System Manual

Preset 14 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires Main Switch

Whiteboard Switch

Emergency Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

Switch input

▪ 32 ▪


Vitesse Plus System Manual

Preset 15 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 Main sw: 5-C-6

2 Main sw: 5-C-6 Whiteboard: 7-C-8

3

4

5

6

7

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

â–Ş 33 â–Ş


Vitesse Plus System Manual

Preset 16 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

Switch input

â–Ş 34 â–Ş


Vitesse Plus System Manual

Preset 17 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Detector input

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

Switch input

â–Ş 35 â–Ş

5

6

7

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

100%

60%

20%

Main sw: 5-C-6 Whiteboard: 7-C-8


Vitesse Plus System Manual

Preset 18 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW2: 3-C-4 Whiteboard: 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

â–Ş 36 â–Ş


Vitesse Plus System Manual

Preset 19 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1 SW1: 1-C-2

2 SW2: 3-C-4 Whiteboard: 7-C-8

3

4

5

6

7

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

â–Ş 37 â–Ş


Vitesse Plus System Manual

Preset 20 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

-

-

20%

-

SW1: 1-C-2 Whiteboard: 7-C-8

4 SW1: 1-C-2 Whiteboard: 7-C-8

â–Ş 38 â–Ş

5

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

-

-

20%

SW1: 1-C-2 Whiteboard: 7-C-8


Vitesse Plus System Manual

Preset 21 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2

1-4

1-4

1-4

1-4

-

-

20%

-

â–Ş 39 â–Ş

5

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

-

-

20%

SW1: 1-C-2 Whiteboard: 7-C-8


Vitesse Plus System Manual

Preset 22 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be

Whiteboard

connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Switch operates luminaires within the same colour dashed line.

Luminaires daylight link – window row only dimmable

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires Main Switch

Whiteboard Switch

Emergency Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8 1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

▪ 40 ▪


Vitesse Plus System Manual

Preset 23 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Main sw: 5-C-6

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

â–Ş 41 â–Ş


Vitesse Plus System Manual

Preset 24 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

Main sw: 5-C-6 Main sw: 5-C-6 Whiteboard: 7-C-8

3

4

5

Main sw: 5C-6

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

6

7

Main sw: 5-C-6 Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

â–Ş 42 â–Ş


Vitesse Plus System Manual

Preset 25 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C6

Main sw: 5-C-6

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

100%

60%

20%

100%

100%

60%

20%

â–Ş 43 â–Ş


Vitesse Plus System Manual

Preset 26 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH6

CH2

E

Switch input

PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

Whiteboard Emergency Switch Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4

3 SW3: 5-C-6 Whiteboard: 7-C-8 1-4

▪ 44 ▪

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4


Vitesse Plus System Manual

Preset 27 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH6

CH2

Switch inputs

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

Whiteboard Emergency Switch Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2

1-4

2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4

3

4

5

6

7

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

▪ 45 ▪


Vitesse Plus System Manual

Preset 28 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

Whiteboard Switch

Whiteboard

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH6

CH2

E

Switch inputs

PL

CH7

CH3

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

Whiteboard Emergency Switch Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

2

3

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

4 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

▪ 46 ▪

5 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4


Vitesse Plus System Manual

Preset 29 Available from version 1.00 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs SW1

SW2

SW3

CH1

Whiteboard Switch

Whiteboard

CH5

CH4

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH2

CH6

Switch inputs

E PL

CH3

CH7

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

Whiteboard Emergency Switch Lighting Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

4 SW1: 1-C-2

1-4

▪ 47 ▪

5 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4


Vitesse Plus System Manual

Preset 30 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 48 ▪


Vitesse Plus System Manual

Preset 31 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 Main sw: 5-C-6

1-4

2 Main sw: 5-C-6 Whiteboard: 7-C-8 1-4

3

4

5

6

7

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

▪ 49 ▪


Vitesse Plus System Manual

Preset 32 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 4 and 5.

Detector/scene plate inputs Whiteboard Switch

Main Switch

CH4

CH1

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs

CH6

CH2

E PL

CH7

CH3

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6 Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 50 ▪


Vitesse Plus System Manual

Preset 33 Available from version 1.00 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channel 5.

Detector/scene plate inputs Main Switch

Whiteboard Switch

Whiteboard

CH5

CH1

CH4

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs

CH6

CH2

E PL

CH7

CH3

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

▪ 51 ▪

5 Main sw: 5-C-6 Whiteboard: 7-C-8 1-4

6

7

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4


Vitesse Plus System Manual

Preset 34 Available from version 1.00 software onwards. Two cellular offices with a detector and scene plate in each. Option for local switch in each office.

Configured for: l l l l

Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

Detector input

1

1

1

1

1

3

3

Scene plate input

2

2

2

2

2

4

4

Scene group

1

1

1

1

1

2

2

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

75%

75%

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

Switch input

Light levels:

â–Ş 52 â–Ş


Vitesse Plus System Manual

Preset 35 Available from version 1.00 software onwards. 4 cellular offices with a scene plate in each. Option for local switch in each office. Detector in each.

Configured for: l l l l

Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW4: 7-C-8

Detector input

1

1

1

2

2

3

4

Scene plate input

1

1

1

2

2

3

4

Scene group

1

2

3

4

1

2

3

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

75%

75%

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

Switch input

Light levels:

â–Ş 53 â–Ş


Vitesse Plus System Manual

Preset 36 Available from version 1.00 software onwards. Large office/meeting room with detector used for lux and occupancy and scene plate and option for master all on switch 1 scene selection switch.

Configured for: l l l l

Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

1

1

1

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

OFF

OFF

OFF

OFF

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

Switch input

Scene group Light levels:

â–Ş 54 â–Ş


Vitesse Plus System Manual

Preset 37 Available from version 1.00 software onwards. Large office or meeting room with lux referenced on channels 1-3 only. Detector used for lux and occupancy, 1 scene plate.

Detector/scene plate inputs

CH1

GROUP 1

GROUP 2

SC1 100% SC2 75% SC3 50% SC4 25%

SC1 100% SC2 OFF SC3 50% SC4 25%

CH3

CH2

CH4

GROUP 3

Switch inputs

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

E PL

GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%

CH7

CH5

MASTER SWITCH

Master Switch

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Luminaires daylight link – all fittings dimmable

Emergency Lighting Test

Master Switch

Emergency Luminaires

Dimmable Luminaires

Configured for: l l l l

Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

1

2

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

75%

OFF

OFF

OFF

75%

75%

Scene 3

50%

50%

OFF

OFF

OFF

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

Switch input

Scene group Light levels:

▪ 55 ▪


Vitesse Plus System Manual

Preset 38 Available from version 1.00 software onwards. Large office or meeting room with detector for occupancy and no lux on any channels. 1 scene plate.

Detector/scene plate inputs

CH1

GROUP 1

GROUP 2

SC1 100% SC2 75% SC3 50% SC4 25%

SC1 100% SC2 OFF SC3 50% SC4 25%

CH3

CH2

CH4

GROUP 3

Switch inputs

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

E PL

GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%

CH7

CH5

MASTER SWITCH

Master Switch

Dimmable Luminaires

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Emergency Luminaires

Master Switch

Emergency Lighting Test

Configured for: l l l l

Presence detection Scene selection switch Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

1

2

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

75%

OFF

OFF

OFF

75%

75%

Scene 3

50%

50%

OFF

OFF

OFF

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

Switch input

Scene group Light levels:

▪ 56 ▪


Vitesse Plus System Manual

Preset 39 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1–3. Scene plate by teacher's desk. Detector for lux (scene 1 only) and absence.

Detector/scene plate inputs SW1

SW2

SW3

GROUP 1

GROUP 2

CH4

CH1

CH5

SC1 100% SC2 OFF SC3 50% SC4 25%

SC1 100% SC2 75% SC3 50% SC4 25%

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Whiteboard

GROUP 3

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 4

CH3

CH7

Whiteboard Switch

SC1 100% SC2 75% SC3 50% SC4 25%

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

Dimmable Luminaires

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1 SW1: 1-C-2 Whiteboard: 7-C-8

Switch input

2 SW2: 3-C-4 Whiteboard: 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

1

1

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

OFF

OFF

OFF

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Scene group Light levels:

Max dimming level

▪ 57 ▪


Vitesse Plus System Manual

Preset 40 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 2. Scene plate by teacher's desk.

Detector/scene plate inputs SW1

SW2

SW3 GROUP 2

CH4

CH1

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

GROUP 3

GROUP 1

Whiteboard

SC1 100% SC2 75% SC3 50% SC4 25%

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6 SC1 100% SC2 OFF SC3 50% SC4 25%

Switch inputs E PL

GROUP 4

CH3

CH7

Whiteboard Switch

SC1 100% SC2 75% SC3 50% SC4 25%

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1 SW1: 1-C-2

Switch input

2 SW2: 3-C-4 Whiteboard: 7-C-8

3

4

5

6

7

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

2

1

4

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

OFF

75%

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Scene group Light levels:

Max dimming level

▪ 58 ▪


Vitesse Plus System Manual

Preset 41 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channels 1, 4 and 5. Scene plate by teacher's desk.

Detector/scene plate inputs SW1

SW2

SW3

Whiteboard Switch

Whiteboard

GROUP 1

CH1

CH4

SC1 100% SC2 OFF SC3 50% SC4 25%

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

GROUP 2

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 3

CH3

CH7

SC1 100% SC2 75% SC3 50% SC4 25%

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Luminaires daylight link – graduated dimming from window row, scene 1 only

Dimmable Luminaires

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2 Whiteboard: 7-C-8

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2 Whiteboard: 7-C-8

SW1: 1-C-2 Whiteboard: 7-C-8

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

2

3

1

1

2

3

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

OFF

75%

75%

OFF

OFF

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Switch input

Scene group Light levels:

Max dimming level

▪ 59 ▪


Vitesse Plus System Manual

Preset 42 Available from version 1.00 software onwards. Classroom with 3 rows of fittings switched individually. Whiteboard row on channel 5. Scene plate by teacher's desk.

Detector/scene plate inputs SW1

SW2

SW3

GROUP 2

Whiteboard Switch

Whiteboard

GROUP 2

GROUP 1

CH5

CH1 SC1 100% SC2 75% SC3 50% SC4 25%

SC1 SC2 SC3 SC4

100% OFF 50% 25%

CH4

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

GROUP 3

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 4

CH3

SC1 100% SC2 75% SC3 50% SC4 25%

CH7

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Luminaires daylight link – graduated dimming from window row, scene 1 only

Dimmable Luminaires

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2

Detector input

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

2

3

Scene 1

100%

Scene 2 Scene 3 Scene 4

Switch input

Scene group

5

6

7

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

4

2

1

3

4

100%

100%

100%

100%

100%

100%

75%

75%

75%

75%

OFF

75%

75%

50%

50%

50%

50%

50%

50%

50%

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

SW1: 1-C-2 Whiteboard: 7-C-8

Light levels:

Max dimming level

▪ 60 ▪


Vitesse Plus System Manual

Preset 43 Available from version 1.00 software onwards. Classroom with 3 rows switched together but with different dimming pre-set levels per row. Whiteboard channels 1– 3. Scene plate by teacher's desk.

Detector/scene plate inputs Main Switch GROUP 1

GROUP 2

CH4

CH1

CH5

SC1 100% SC2 OFF SC3 50% SC4 25%

SC1 100% SC2 75% SC3 50% SC4 25%

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Whiteboard

GROUP 3

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 4

CH3

CH7

SC1 100% SC2 75% SC3 50% SC4 25%

Whiteboard Switch Windows

Main Switch

Main Switch

Luminaires daylight link – graduated Dimmable Luminaires dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Main sw: 1-C-2 Whiteboard: 7-C8

Main sw: 1-C-2 Whiteboard: 7-C8

Main sw: 1-C-2 Whiteboard: 7-C8

Main sw: 1-C2

Main sw: 1-C2

Main sw: 1-C2

Main sw: 1-C2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

1

1

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

OFF

OFF

OFF

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Switch input

Scene group Light levels:

Scene 4 Max dimming level

▪ 61 ▪


Vitesse Plus System Manual

Preset 44 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channels 2. Scene plate by teacher's desk.

Detector/scene plate inputs Main Switch GROUP 2

CH4

CH1

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

GROUP 3

Whiteboard

GROUP 1

SC1 100% SC2 75% SC3 50% SC4 25%

CH2 SC1 100% SC2 OFF SC3 50% SC4 25%

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 4

CH3

CH7

SC1 100% SC2 75% SC3 50% SC4 25%

Whiteboard Switch Windows

Main Switch

Main Switch

Luminaires daylight link – graduated Dimmable Luminaires dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Main sw: 1-C-2

Main sw: 1-C-2 Whiteboard: 7-C-8

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

2

1

4

2

2

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

OFF

75%

75%

75%

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Switch input

Scene group Light levels:

Max dimming level

▪ 62 ▪


Vitesse Plus System Manual

Preset 45 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channels 1, 4 and 5. Scene plate by teacher's desk.

Detector/scene plate inputs Main Switch

Whiteboard Switch

Whiteboard

GROUP 1

CH4

CH1

SC1 100% SC2 OFF SC3 50% SC4 25%

CH5

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be L connected to Input 1.

GROUP 2

CH2

SC1 100% SC2 75% SC3 50% SC4 25%

CH6

Switch inputs E PL

GROUP 3

CH3

CH7

SC1 100% SC2 75% SC3 50% SC4 25%

Windows

Main Switch

Luminaires daylight link – graduated dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Main Switch

Dimmable Luminaires

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1

2

3

4

5

6

7

Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Main sw: 1-C-2 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

1

2

3

1

1

2

3

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

OFF

75%

75%

OFF

OFF

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Scene group Light levels:

Scene 4 Max dimming level

▪ 63 ▪


Vitesse Plus System Manual

Preset 46 Available from version 1.00 software onwards. Classroom with all fittings switched together. Whiteboard on channel 5. Scene plate by teacher's desk.

Detector/scene plate inputs Main Switch

Whiteboard Switch

Whiteboard

GROUP 2

GROUP 2

GROUP 1

CH1 SC1 100% SC2 75% SC3 50% SC4 25%

CH5

CH4

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

GROUP 3

CH2

SC1100% SC275% SC350% SC425%

CH6

Switch inputs E PL

GROUP 4

CH3

CH7

SC1 100% SC2 75% SC3 50% SC4 25%

Windows

Main Switch

Luminaires daylight link – graduated dimming from window row, scene 1 only

Switches and dims the whiteboard luminaires independently. Scene 2 = Whiteboard fittings off.

Main Switch

Dimmable Luminaires

White- Emergency board Lighting Switch Test

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Configured for: l l l l

Absence detection Scene selection switch Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2

Main sw: 1-C-2 Whiteboard: 7-C-8

Main sw: 1-C-2

Main sw: 1-C-2

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Scene plate input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

2

3

4

2

1

3

4

Scene 1

100%

100%

100%

100%

100%

100%

100%

Scene 2

75%

75%

75%

75%

OFF

75%

75%

Scene 3

50%

50%

50%

50%

50%

50%

50%

Scene 4

25%

25%

25%

25%

25%

25%

25%

100%

60%

20%

100%

100%

60%

20%

Switch input

Scene group Light levels:

Max dimming level

▪ 64 ▪


Vitesse Plus System Manual

Preset 47 - Reserved for future use Preset 48 - Reserved for future use

â–Ş 65 â–Ş


Vitesse Plus System Manual

Preset 49 Available from version 1.00 software onwards. 3 toilets each controlled separately in presence mode by a PIR connected to inputs 1, 2 and 3. Channel 1 only responds in presence mode to all 4 detector inputs.

Detector/scene plate inputs 3 toilets each controlled individually in presence mode, with the option of manual switch for absence if required. PIRs connected to inputs 1,2,3.channel 1 only responds to all 4 detector inputs. This is for water shut-off valve so that if no occupancy is detected the water supply is isolated. CH2

CH3

Upon entering the space luminaires will automatically switch on. CH1

Water shut-off valve Emergency Luminaires

CH6

CH4

CH7

Configured for: l l l

Presence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1

1

1

1

2

3

â–Ş 66 â–Ş


Vitesse Plus System Manual

Preset 50 Available from version 1.03 software onwards. Corridor with 50% of luminaires controlled by a PIR and 50% controlled by switch input.

CH1

CH6

CH2

CH6

CH3

CH6

CH4

CH7

CH5

CH7

Windows

Detector/scene plate inputs

Switch inputs

E PL

Upon entering the space luminaires will automatically switch on.

CH1 CH2 CH3 CH4

Switched by detector only

CH6 CH7

Switched by keyswitch

230v VFC relay unit 230V Live Supply

50% of the LCM is controlled via a mains rated keyswitch and VFC contact relay. this will be switched to ‘on’ during Keyswitch occupancy hours. The VFC contact provides a latching command when energised to switch on the lighting (switch input 11, paralleled with corridor hold input terminal). The rest of the LCM is responsive to PIR inputs only. During out of hours occupancy when the key switch is turned off 50% of the LCM will respond to the PIR input only.

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Detector input

1

2

3

4

5

6

7

1-4

1-4

1-4

1-4

1-4

-

-

▪ 67 ▪


Vitesse Plus System Manual

Preset 51 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

Switch input

▪ 68 ▪


Vitesse Plus System Manual

Preset 52 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

100%

60%

20%

100%

100%

60%

20%

Switch input

▪ 69 ▪


Vitesse Plus System Manual

Preset 53 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – window row only dimmable.

Dimmable Luminaires

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

▪ 70 ▪


Vitesse Plus System Manual

Preset 54 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Switch operates luminaires within the same colour dashed line.

Luminaires daylight link – window row only dimmable.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Whiteboard: 7-C-8 Whiteboard: 7-C-8 Whiteboard: 7-C-8 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 Main sw: 5-C-6 1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

▪ 71 ▪


Vitesse Plus System Manual

Preset 55 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs SW1

SW2

SW3

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

-

-

20%

-

-

-

20%

▪ 72 ▪


Vitesse Plus System Manual

Preset 56 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode. Whiteboard on channels 1, 2 and 3 switched independently.

Detector/scene plate inputs Main Switch

CH4

CH1

CH5

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH6

CH2

E PL

CH7

CH3

Whiteboard Switch

Windows

Switch operates luminaires within the same colour dashed line.

Luminaires – window row only daylight switching.

Daylight Switching

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Main Switch

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

Main sw: 5-C-6

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 73 ▪


Vitesse Plus System Manual

Preset 57 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.

Detector/scene plate inputs SW1

SW2

SW3

CH1

Whiteboard

Window

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH5

Switch inputs

CH2

E PL

CH6

CH7

CH3

CH4

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires closest to the windows daylight dim

Dimmable Luminaires

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

Whiteboard: 7-C-8

1-4

1-4

1-4

1-4

1-4

1-4

1-4

â–Ş 74 â–Ş


Vitesse Plus System Manual

Preset 58 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channel 7 switched independently.

Detector/scene plate inputs SW1

SW2

SW3

CH1

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

Switch inputs CH5

CH2

E PL

CH4

CH6

CH7

Whiteboard Switch

CH3

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires closest to the windows daylight dim.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

Whiteboard: 7-C-8

1-4

1-4

1-4

1-4

1-4

1-4

1-4

â–Ş 75 â–Ş


Vitesse Plus System Manual

Preset 59 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs SW2

SW3

Whiteboard Switch Window

SW1

CH7

CH1

CH6

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH2

Switch inputs E PL

CH4

CH3

Window

CH5

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires closest to the windows daylight switch.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2

1-4

2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4

3

4

5

6

7

SW3: 5-C-6

SW3: 5-C-6

SW3: 5-C-6

SW2: 3-C-4

SW1: 1-C-2

1-4

1-4

1-4

1-4

1-4

â–Ş 76 â–Ş


Vitesse Plus System Manual

Preset 60 Available from version 1.03 software onwards. Classroom with 3 rows of luminaires working in absence mode. Whiteboard on channel 2.

Detector/scene plate inputs SW2

SW3

Whiteboard Switch Window

SW1

CH7

CH1

CH6

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH2

Switch inputs E PL

CH4

CH3

Window

CH5

Windows

Each switch operates luminaires within the same colour dashed line.

Luminaires closest to the windows daylight dim.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2

1-4

2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4

3

4

5

6

7

SW3: 5-C-6

SW3: 5-C-6

SW3: 5-C-6

SW2: 3-C-4

SW1: 1-C-2

1-4

1-4

1-4

1-4

1-4

â–Ş 77 â–Ş


Vitesse Plus System Manual

Preset 61 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

CH7

Windows

CH6

CH5

CH1

CH3

CH2

SW1

CH4

SW2

SW3

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20% Emergency Luminaires

Luminaires daylight link – window row only dimmable. SW1

SW2

SW3

Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW3: 5-C-6

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

2

2

3

3

1

2

3

20%

20%

20%

20%

20%

20%

20%

▪ 78 ▪


Vitesse Plus System Manual

Preset 62 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

CH7

Windows

CH6

CH5

CH1

CH3

CH2

SW1

CH4

SW2

SW3

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line.

Daylight Switching Emergency Luminaires

Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only daylight switching.

SW1

SW2

SW3

Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW3: 5-C-6

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

2

2

3

3

1

2

3

▪ 79 ▪


Vitesse Plus System Manual

Preset 63 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

CH3 Windows

Windows

CH6

Windows

CH5

CH1

CH4

CH2

SW1

SW2

CH7

SW3

SW4

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line.

Dimmable Luminaires – 20% Emergency Luminaires

Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only dimmable.

SW1

SW2

SW3

SW4 Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW3: 5-C-6

SW1: 1-C-2

SW2: 3-C-4

SW4: 7-C-8

2

2

3

3

1

2

4

▪ 80 ▪


Vitesse Plus System Manual

Preset 64 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

Windows

CH3

Windows

CH6

Windows

CH5

CH1

CH4

CH2

SW1

SW2

CH7

SW3

SW4

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line.

Daylight Switching Emergency Luminaires

Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Luminaires daylight link – window row only daylight switching.

SW1

SW2

SW3

SW4 Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW3: 5-C-6

SW1: 1-C-2

SW2: 3-C-4

SW4: 7-C-8

2

2

3

3

1

2

4

▪ 81 ▪


Vitesse Plus System Manual

Preset 65 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

SW3

Windows

Windows

CH5

CH7

CH1

CH2

CH4

CH3

SW1

CH6

SW3

SW2

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20% Emergency Luminaires

Luminaires daylight link – window row only dimmable. SW1

SW2

SW3

Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2

1

2

2

3

2

3

1

20%

20%

20%

20%

20%

20%

20%

▪ 82 ▪


Vitesse Plus System Manual

Preset 66 Available from version 1.03 software onwards. 3 cellular offices individually controlled with a presence detector and/or manual switch in each.

Windows

Windows

Windows

SW3

Windows

Windows

CH5

CH7

CH1

CH2

CH4

CH3

SW1

CH6

SW3

SW2

E

Detector/scene plate inputs

PL

Switch inputs

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching Emergency Luminaires

Luminaires daylight link – window row only daylight switching. SW1

SW2

SW3

Emergency Lighting Test

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW2: 3-C-4

SW3: 5-C-6

SW1: 1-C-2

1

2

2

3

2

3

1

▪ 83 ▪


Vitesse Plus System Manual

Preset 67 Available from version 1.03 software onwards. Open plan office with graduated dimming.

Detector/scene plate inputs Windows

Windows

CH1

CH2

CH3

Switch inputs CH4

CH5

E PL

CH7

CH6

SW1

SW1

SW2

SW2

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – graduated dimming from window row.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires

Emergency Luminaires

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 5-C-6

SW2: 5-C-6

Detector input

1, 2

1, 2

1, 2

1, 2

1, 2

3, 4

3, 4

Dimming level

20%

20%

20%

60%

60%

-

-

Switch input

▪ 84 ▪


Vitesse Plus System Manual

Preset 68 Available from version 1.03 software onwards. Open plan office with graduated dimming.

Windows

CH1

CH2

CH5

SW1

CH3

CH7

CH4

CH6

SW2

E

Detector/scene plate inputs

Switch inputs

PL

Dimmable Luminaires

Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Emergency Luminaires

Luminaires daylight link – graduated dimming from window row. SW1

SW2

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 5-C-6

SW2: 5-C-6

Detector input

1, 2

1, 2

1, 2

1, 2

1, 2

3, 4

3, 4

Dimming level

20%

20%

20%

60%

60%

20%

60%

Switch input

▪ 85 ▪


Vitesse Plus System Manual

Preset 69 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.

Detector/scene plate inputs

Whiteboard

SW1

SW2

SW3

CH1

CH4

CH2

CH6

CH5

Switch inputs E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – all luminaires dimmable.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Dimmable Luminaires – 20% Emergency Luminaires

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

SW1: 1-C-2

Whiteboard: 7-C-8

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1

2

4

1

1

3

4

20%

20%

20%

20%

20%

20%

20%

▪ 86 ▪


Vitesse Plus System Manual

Preset 70 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channel 2 switched separately.

Detector/scene plate inputs

Whiteboard

SW1

SW2

SW3

CH1

CH4

CH2

CH6

CH5

Switch inputs E PL

CH7

CH3

Whiteboard Switch

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – all luminaires daylight switch.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Daylight Switching Emergency Luminaires

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input Min dimming level

1

2

3

4

5

6

7

SW1: 1-C-2

Whiteboard: 7-C-8

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1

2

4

1

1

3

4

20%

20%

20%

20%

20%

20%

20%

▪ 87 ▪


Vitesse Plus System Manual

Preset 71 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1-3 switched separately.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2 Whiteboard: 7-C-8 1

2 SW2: 3-C-4 Whiteboard: 7-C-8 2

3 SW3: 5-C-6 Whiteboard: 7-C-8 3

â–Ş 88 â–Ş

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1

1

2

3


Vitesse Plus System Manual

Preset 72 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode. Whiteboard on channels 1,2 and 3.

Detector/scene plate inputs SW1

SW2

SW3

Whiteboard Switch

CH5

CH4

CH1

Windows

Whiteboard

If using 3 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be connected to Input 1.

CH6

CH2

E PL

CH3

CH7

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Luminaires daylight link – window rows only dimmable.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Dimmable Luminaires – 20% Emergency Luminaires

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1 SW1: 1-C-2 Whiteboard: 7-C-8 1-4

2 SW2: 3-C-4 Whiteboard: 7-C-8 1-4

3 SW3: 5-C-6 Whiteboard: 7-C-8 1-4

▪ 89 ▪

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

1-4

1-4

1-4

1-4


Vitesse Plus System Manual

Preset 73 Available from version 1.03 software onwards. Classroom with 4 columns of fittings working in absence mode. Whiteboard on channels 1,2 and 3.

Detector/scene plate inputs SW1

SW2

SW3

Whiteboard Switch

CH1

Windows

Whiteboard

If using 2 PIRs instead of a microwave detector, the PIR closest to the window will reference lux and should be

CH5

CH2

Switch inputs E PL

CH7

CH4

CH6

CH3

Windows

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW1

SW2

SW3

White- Emergency board Lighting Switch Test

Dimmable Luminaires – 20%

Luminaires daylight link – window rows only dimmable.

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

Whiteboard: 7-C-8

Whiteboard: 7-C-8

Whiteboard: 7-C-8

SW3: 5-C-6

SW3: 5-C-6

SW2: 3-C-4

SW1: 1-C-2

1-4

1-4

1-4

1-4

1-4

1-4

1-4

▪ 90 ▪


Vitesse Plus System Manual

Presets 74 and 75 Available from version 1.03 software onwards. 4 cellular offices individually controlled with a presence detector and/or manual centre-biased retractive switch in each. Dual supply using 2 LCMs: l l

Essential LCM = preset 74 Non-essential LCM = preset 75

Windows

CH1

Windows

CH2

Windows

CH4

CH3

SW1

Windows

SW2

CH5

Windows

CH6

SW3

CH7

SW4

Switch inputs

Non Essential preset 75

E PL

Detector/scene plate inputs Essential preset 74

Each switch operates luminaires within the same colour dashed line. Luminaires daylight link- window row only dimmable.

Non Essential preset 75

Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Essential preset 74

E

Dimmable Luminaires – 20%

PL

Emergency Luminaires

SW1

SW2

SW3

SW4

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

SW4: 7-C-8

SW4: 7-C-8

SW4: 7-C-8

1

1

2

3

4

4

4

▪ 91 ▪


Vitesse Plus System Manual

Preset 76 Available from version 1.03 software onwards. 2 cellular offices individually controlled with a presence detector and/ or manual centre-retractive switch in each. Dual supply (essential and non-essential) using 2 LCMs.

Windows

Windows

CH1

CH2

Windows

CH3

CH4

Windows

CH5

CH7

CH6

SW1

SW2

SW3

SW4

Switch inputs

Non Essential preset 76

E PL

Detector/scene plate inputs Essential preset 76

Each switch operates luminaires within the same colour dashed line. Luminaires daylight link- window row only dimmable.

Non Essential preset 76

Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Essential preset 76

E

Dimmable Luminaires – 20%

PL

Emergency Luminaires

SW1

SW2

SW3

SW4

Configured for: l l l

Presence detection Corridor hold = Latching switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input Detector input

1

2

3

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW2: 3-C-4

SW3: 5-C-6

SW4: 7-C-8

1

1

1

2

2

2

2

▪ 92 ▪


Vitesse Plus System Manual

Preset 77 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

Detector/scene plate inputs Windows

Windows

Windows

SW3

CH5

Whiteboard

CH3

CH7

CH2

Switch inputs E PL

SW1

CH4

CH6

CH1

SW1

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW2

SW3

Whiteboard Switch

Upon entering the space luminaires will automatically switch on – store cupboard only.

SW1

SW2

White- Emergency board Lighting Switch Test

SW3

Luminaires daylight link – graduated dimming from window row. Dimmable Luminaires Emergency Luminaires

Configured for: l l l

Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW2: 3-C-4 Whiteboard: 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

N/A

SW2: 3-C-4

SW1: 1-C-2

SW3: 5-C-6

Detector input

1-3

1-3

1-3

4

1-3

1-3

1-3

Dimming level

100%

60%

20%

-

60%

100%

20%

▪ 93 ▪


Vitesse Plus System Manual

Preset 78 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

Detector/scene plate inputs Windows

Windows

Windows

SW3

CH7

CH5

Whiteboard

CH3

CH2

Switch inputs E PL

SW1

CH4

CH1

CH6

SW1

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

SW2

SW3

Whiteboard Switch

Upon entering the space luminaires will automatically switch on – store cupboard only.

SW2

SW1

White- Emergency board Lighting Switch Test

SW3

Luminaires daylight link – window row only dimmable. Dimmable Luminaires Emergency Luminaires

Configured for: l l l

Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW2: 3-C-4 Whiteboard: 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

N/A

SW2: 3-C-4

SW1: 1-C-2

SW3: 5-C-6

Detector input

1-3

1-3

1-3

4

1-3

1-3

1-3

Dimming level

-

-

20%

-

-

-

20%

▪ 94 ▪


Vitesse Plus System Manual

Preset 79 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

Detector/scene plate inputs Windows

Windows

Windows

SW1

CH5

Whiteboard

CH3

CH7

CH2

Switch inputs E PL

CH4

CH6

CH1

SW1

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Whiteboard Switch

Upon entering the space luminaires will automatically switch on – store cupboard only.

SW1

Whiteboard Switch

Luminaires daylight link – graduated dimming from window row.

Emergency Lighting Test

Dimmable Luminaires Emergency Luminaires

Configured for: l l l

Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW1: 1-C-2 Whiteboard: 7-C-8

3 SW1: 1-C-2 Whiteboard: 7-C-8

4

5

6

7

N/A

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1-3

1-3

1-3

4

1-3

1-3

1-3

Dimming level

100%

60%

20%

-

60%

100%

20%

▪ 95 ▪


Vitesse Plus System Manual

Preset 80 Available from version 1.03 software onwards. Classroom with 3 rows of fittings working in absence mode, and a store cupboard working independently in presence mode.

Detector/scene plate inputs Windows

Windows

Windows

SW1

CH5

Whiteboard

CH3

CH7

CH2

Switch inputs E PL

CH6

CH4

CH1

SW1

Each switch operates luminaires within the same colour dashed line. Switches and dims the whiteboard luminaires independently within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Whiteboard Switch

Upon entering the space luminaires will automatically switch on – store cupboard only.

Whiteboard Switch

SW1

Luminaires daylight link – window row only dimmable.

Emergency Lighting Test

Dimmable Luminaires Emergency Luminaires

Configured for: l l l

Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard: 7-C-8

2 SW1: 1-C-2 Whiteboard: 7-C-8

3 SW1: 1-C-2 Whiteboard: 7-C-8

4

5

6

7

N/A

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1-3

1-3

1-3

4

1-3

1-3

1-3

Dimming level

-

-

20%

-

-

-

20%

▪ 96 ▪


Vitesse Plus System Manual

Preset 81 Available from version 1.03 software onwards. Classroom with luminaires working in absence mode, and store cupboards/ WC working independently in presence mode.

Detector/scene plate inputs Windows

Windows

Windows

SW1

CH2 Whiteboard

CH7

Switch inputs E

CH5

CH3

CH4

CH1

SW1

Whiteboard Switch

PL

Whiteboard Switch

Each switch operates luminaires within the same colour dashed line.

Upon entering the space luminaires will automatically switch on – toilets only.

Switches and dims the whiteboard luminaires independently within the same colour dashed line.

Luminaires daylight link – window row only dimmable.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires

SW1

Whiteboard Switch

Whiteboard Switch

Emergency Lighting Test

Emergency Luminaires

Configured for: l l l

Absence detection (except channel 4) Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 Whiteboard 1: 3-C-4 Whiteboard 2: 7-C-8

2 SW1: 1-C-2 Whiteboard 1: 3-C-4 Whiteboard 2: 7-C-8

3

4

5

6

7

N/A

N/A

SW1: 1-C-2

SW1: 1-C-2

SW1: 1-C-2

Detector input

1, 2

1, 2

3

4

1, 2

1, 2

1, 2

Dimming level

-

20%

-

-

-

-

20%

▪ 97 ▪


Vitesse Plus System Manual

Preset 82 Available from version 1.04 software onwards. Classroom with 3 columns of luminaires working in absence mode. All fittings dimmable from switches but only window row responsive to lux.

Detector/scene plate inputs Windows

Windows

SW2 SW4

CH1

SW3

CH2

CH3

Switch inputs E

CH4

PL

CH5

CH6

SW1

SW2

CH7

SW3

SW4

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – window row only dimmable.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Dimmable Luminaires – 20%

SW1

SW2

SW4

SW3

Emergency Lighting Test

Emergency Luminaires

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel Switch input

1 SW1: 1-C-2 SW4: 7-C-8

2 SW2: 3-C-4 Whiteboard: : 7-C-8

3 SW3: 5-C-6 Whiteboard: 7-C-8

4

5

6

7

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

20%

20%

20%

-

-

-

-

▪ 98 ▪


Vitesse Plus System Manual

Preset 83 Available from version 1.04 software onwards. Classroom with 3 columns of luminaires working in absence mode all fittings switching from switches but only window row responsive to lux.

Detector/scene plate inputs Windows

Windows

SW2 SW4

CH1

SW3

CH2

CH3

Switch inputs E

CH4

PL

CH5

CH6

SW1

SW2

CH7

SW3

SW4

Each switch operates luminaires within the same colour dashed line.

Luminaires daylight link – window row only daylight switching.

Upon exiting the space any luminaires left on will switch off after an adjustable time out period.

Daylight Switching

SW1

SW2

SW4

SW3

Emergency Lighting Test

Emergency Luminaires

Configured for: l l l

Absence detection Master ON switch for all channels = momentary switch (terminal 11) ELT keyswitch = latching switch (terminal 10)

Channel

1

2

3

4

5

6

7

SW1: 1-C-2 SW4: 7-C-8

SW2: 3-C-4 SW4: 7-C-8

SW3: 5-C-6

SW1: 1-C-2

SW1: 1-C-2

SW2: 3-C-4

SW3: 5-C-6

Detector input

1-4

1-4

1-4

1-4

1-4

1-4

1-4

Dimming level

20%

20%

20%

-

-

-

-

Switch input

▪ 99 ▪


CP Electronics - a business unit of Legrand Electric Limited Brent Crescent, London NW10 7XR UK www.cpelectronics.co.uk enquiry@cpelectronics.co.uk Tel: +44 (0)333 900 0671 Fax: +44 (0)333 900 0674 Due to our policy of continual product improvement, CPÂ Electronics reserves the right to alter the specification of this product without prior notice. Ref WD817 issue 3.1


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.