CP Electronics - Recommended Cable Types for Networks - Issue 2

Page 1

RECOMMENDED CABLE TYPES FOR NETWORKS

Please note that these recommendations are for the Rapid lighting control system only. It is always the electrical installer's responsibility to ensure that the control system is installed in a safe manner using suitable equipment in line with the latest edition of the electrical regulations.

These cable types have been tested and approved for use with Rapid systems. Should any other nonapproved cable type be used then CP Electronics will not accept responsibility for non-functioning systems.

If the chosen cable is to be installed within the same compartment as mains cable, then ensure they are appropriately rated to the latest regulations. Otherwise, they may need to be installed in a separate containment rated appropriately for extra low voltage cables

Basic Backbone Connection Between Area Controllers

Preferred cable types Network connection cores Suitable to run with mains?

CAT5e UTP (NOT CAT6a) CAN A = white/blue + blue CAN B = white/orange + orange

= white/green + green

Integrating Front End Supervisor via Ethernet

Preferred cable types Network connection cores Suitable to run with mains? Client’s preference Example: CAT6 UTP (RJ45)

Floor network cables to Lighting Control Modules (LCM’s)

Preferred cable types Network connection cores Suitable to run with mains? CAT5e UTP (NOT CAT6a) CAN A = white/blue + blue CAN B = white/orange + orange

= white/green + green

DALI network cables (for daisy-chain between each DALI device)

Preferred cable types Distance Network connection cores Suitable to run with mains?

twisted pair 600v cable

1
No
0v
TIA
No
/ EIA T568b standard, RJ45 connector
No
0v
Generic
1.5 sq mm 1.0 sq mm 0.5 sq mm 300m 150m 100m Da or D+ = core 1 Da or D- = core 2 Yes Ref: WD997 issue 2

Basic Backbone Connection Details

The basic backbone network connects area controllers together using 3 pairs of an unscreened twisted pair (UTP) data cable Preferred cable options listed below

See subsequent section when integrating this further with the front end supervisor.

Preferred cable types Network connection cores

CAT5e UTP

Pair 1 CAN A = white/blue + blue

Pair 2 CAN B = white/orange + orange

Pair 3 0v = white/green + green

CAT6 UTP (NOT CAT6a) Pair 1 CAN A = white/blue + blue

Pair 2 CAN B = white/orange + orange

Pair 3 0v = white/green + green

Basic backbone network diagram

Backbone network

3 pairs (A, B, 0v)

Suitable to run with mains?

Lighting control module

Lighting control module

Lighting control module

2
No
No
Area Controller Area Controller Area Controller

Integrating Front End Supervisor via Ethernet

When integrating a supervisor front end to the system, add to the basic backbone network Ethernet network connections as shown below to connect the area controllers to the front end supervisor.

Preferred cable types Network connection cores

Client’s preference

Example: CAT6 UTP (RJ45)

Suitable to run with mains?

TIA / EIA T568b standard, RJ45 connector No

Front end Supervisor

Ethernet router

CAT6 (RJ45)

Lighting control module

Backbone network

3 pairs (A, B, 0v)

Lighting control module

Lighting control module

3
Area Controller Area Controller Area Controller

Floor network cable options

Preferred cable types

CAT5e UTP (NOT CAT6a)

600v rated STP screened twisted pair data

cable with drain wire

Core size : ≤16 AWG (≥1.3 sq mm)

Resistance conductor : ≤15 ohm/km

Capacitance conductors : ≤75 pF/m

CAT5e UTP network connection details

Recommended Cable RAPID network connection cores

Pair 1 CAN A = white/blue + blue

CAT5e UTP (NOT CAT6a)

Network connection cores

CAN A = white/blue + blue

Suitable to run with mains?

0v = white/green + green No

CAN B = white/orange + orange

CAN A = colour 1

CAN B = colour 2

0v = drain wire (screen) Yes

Suitable to run with mains?

Pair 3 0v = white/green + green NO

Pair 2 CAN B = white/orange + orange

4
A, B, 0v LCM8, LCM10, LCM12 and LCM-
with 0v terminal Area Controller To other Area Controllers To other Area Controllers A B 0v
DALIG64

Screened Twisted Pair STP Connection Details

Recommended Cable RAPID network connection cores Suitable to run with mains?

600v rated STP screened twisted pair data cable with drain wire

Black wire – CAN B

White wire – CAN A

Drain wire – 0v

Example: Belden 8719 YES

To other Area Controllers

LCM8, LCM10, LCM12 and LCMDALIG64 with 0v terminal

To other Area Controllers

5
A, B, 0v
Area Controller
6
Suitable to run with mains? CAT5e UTP (NOT CAT6a)
RJ45 plug connector colour scheme differs to that of hardwired. NO Ports 2 & 3
Floor network bus details – CAT5e patch cabling details Recommended Cable RAPID network connection cores
Warning!

DALI network cable connection details (between DALI devices)

DALI bus is intended to be installed within mains rated containments and MUST therefore be given the same insulation safety considerations against electric shocks as that of mains cable.

If the cable has a screen and drain wire, the drain wire must be connected throughout in order to make the screen continuous. This can be done with the use of a connector block. The screen drain wire must be grounded to earth at the gateway ONLY and all other points must be isolated from earth.

7
Preferred cable types Distance Network connection cores Suitable to run with mains? Generic twisted pair 600v cable 1.5 sq mm 1.0 sq mm 0.5 sq mm 300m 150m 100m Da or D+ = core 1 Da or D- = core 2 Yes FS Cable 1601PUYL 16 AWG (1.3 sq mm) 200m Da or D - = black Da or D+ = white Yes

Connection of Legacy Units

8
Backbone network CAN Bus details – CAT5e cabling Recommended Cable RAPID network connection cores Suitable to run with mains? CAT5e UTP (NOT CAT6a) Pair 1 CAN A = white/blue + blue Pair 2 CAN B = white/orange + orange Pair 3 0v = white/green + green NO A B 0v

Backbone CANBus Options

The backbone network connects area controllers together to the Rapid CFE Front End supervisor. The backbone network can use the CANBus connection for legacy installations only

Backbone by CANBus CAT5e Cabling

A, B, 0v 3 pairs

9
Backbone network

Early Release Legacy Systems

Older legacy products can be distinguished as they have hardware build version numbers (or earlier) below:

Floor network bus details for Early Release Legacy Products

10
Stock code description Version . Release AP-EBR-LCM3-1DD RAPiD Pluggable 1DD 1ch LCM 1 07 AP-EBR-LCM8-8DD RAPiD Pluggable 8DD 8ch LCM 1 08 AP-EBR-LCM8-8AD RAPiD Pluggable 8AD 8ch LCM 1 05 AP-EBR-LCM10-10DD RAPiD Pluggable 10DD 10ch LCM 1 08 AP-EBR-LCM10-10AD RAPiD Pluggable 10AD 10ch LCM 1 08 AP-EBR-LCM12-12DD RAPiD Pluggable 12DD 12ch LCM 1 . 08 AP-EBR-LCM12-12AD RAPiD Pluggable 12AD 12ch LCM 1 05 AP-EBR-LCM-DALIG64 RAPiD Pluggable DALI LCM 1 07
- Belden cabling Recommended Cable RAPID network connection cores Suitable to run with mains? Belden 8719 YES Drain wire – 0v White wire – CAN A Black wire – CAN B A, B, 0v 3 pairs A, B, 0v Area Controller Belden 8719 To other Area Controllers To other Area Controllers LCM3,8,10,12, DALIG64
0v
wires
terminal block
0v terminal is missing from the LCM.
Connect through
connection by joining the drain
via
when
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.