RECOMMENDED CABLE TYPES FOR NETWORKS
Please note that these recommendations are for the Rapid lighting control system only. It is always the electrical installer's responsibility to ensure that the control system is installed in a safe manner using suitable equipment in line with the latest edition of the electrical regulations.
These cable types have been tested and approved for use with Rapid systems. Should any other nonapproved cable type be used then CP Electronics will not accept responsibility for non-functioning systems.
If the chosen cable is to be installed within the same compartment as mains cable, then ensure they are appropriately rated to the latest regulations. Otherwise, they may need to be installed in a separate containment rated appropriately for extra low voltage cables
Basic Backbone Connection Between Area Controllers
Preferred cable types Network connection cores Suitable to run with mains?
CAT5e UTP (NOT CAT6a) CAN A = white/blue + blue CAN B = white/orange + orange
= white/green + green
Integrating Front End Supervisor via Ethernet
Preferred cable types Network connection cores Suitable to run with mains? Client’s preference Example: CAT6 UTP (RJ45)
Floor network cables to Lighting Control Modules (LCM’s)
Preferred cable types Network connection cores Suitable to run with mains? CAT5e UTP (NOT CAT6a) CAN A = white/blue + blue CAN B = white/orange + orange
= white/green + green
DALI network cables (for daisy-chain between each DALI device)
Preferred cable types Distance Network connection cores Suitable to run with mains?
twisted pair 600v cable
Basic Backbone Connection Details
The basic backbone network connects area controllers together using 3 pairs of an unscreened twisted pair (UTP) data cable Preferred cable options listed below
See subsequent section when integrating this further with the front end supervisor.
Preferred cable types Network connection cores
CAT5e UTP
Pair 1 CAN A = white/blue + blue
Pair 2 CAN B = white/orange + orange
Pair 3 0v = white/green + green
CAT6 UTP (NOT CAT6a) Pair 1 CAN A = white/blue + blue
Pair 2 CAN B = white/orange + orange
Pair 3 0v = white/green + green
Basic backbone network diagram
Backbone network
3 pairs (A, B, 0v)
Suitable to run with mains?
Lighting control module
Lighting control module
Lighting control module
Integrating Front End Supervisor via Ethernet
When integrating a supervisor front end to the system, add to the basic backbone network Ethernet network connections as shown below to connect the area controllers to the front end supervisor.
Preferred cable types Network connection cores
Client’s preference
Example: CAT6 UTP (RJ45)
Suitable to run with mains?
TIA / EIA T568b standard, RJ45 connector No
Front end Supervisor
Ethernet router
CAT6 (RJ45)
Lighting control module
Backbone network
3 pairs (A, B, 0v)
Lighting control module
Lighting control module
Floor network cable options
Preferred cable types
CAT5e UTP (NOT CAT6a)
600v rated STP screened twisted pair data
cable with drain wire
Core size : ≤16 AWG (≥1.3 sq mm)
Resistance conductor : ≤15 ohm/km
Capacitance conductors : ≤75 pF/m
CAT5e UTP network connection details
Recommended Cable RAPID network connection cores
Pair 1 CAN A = white/blue + blue
CAT5e UTP (NOT CAT6a)
Network connection cores
CAN A = white/blue + blue
Suitable to run with mains?
0v = white/green + green No
CAN B = white/orange + orange
CAN A = colour 1
CAN B = colour 2
0v = drain wire (screen) Yes
Suitable to run with mains?
Pair 3 0v = white/green + green NO
Pair 2 CAN B = white/orange + orange
Screened Twisted Pair STP Connection Details
Recommended Cable RAPID network connection cores Suitable to run with mains?
600v rated STP screened twisted pair data cable with drain wire
Black wire – CAN B
White wire – CAN A
Drain wire – 0v
Example: Belden 8719 YES
To other Area Controllers
LCM8, LCM10, LCM12 and LCMDALIG64 with 0v terminal
To other Area Controllers
DALI network cable connection details (between DALI devices)
DALI bus is intended to be installed within mains rated containments and MUST therefore be given the same insulation safety considerations against electric shocks as that of mains cable.
If the cable has a screen and drain wire, the drain wire must be connected throughout in order to make the screen continuous. This can be done with the use of a connector block. The screen drain wire must be grounded to earth at the gateway ONLY and all other points must be isolated from earth.