Hanger Options
HANGER OPTIONS Min. one #5 rebar top course (typ.)
LGU/MGU/HGU/HHGU/LGUM/HGUM
Typical Concealed Flange HGUM Installation at End of Wall
See Hanger Options General Notes. CONCEALED FLANGE • LGU, MGU, HGU, HHGU and HGUM hangers are available with one flange concealed. Specify flange to conceal. • Allowable Loads for one flange-concealed option: LGU 1.00 of published load MGU 0.88 of published load HGU 0.75 of published load HHGU 0.75 of published load HGUM see table below • LGU with W 3 1⁄4" or less, MGU with W 4" or less and HGU with W 4 11⁄16" or less, flanges cannot be concealed.
Min. one #5 rebar in top course
Vertical rebar per Designer Min. one block return
Typical MGU Installation with Right Flange Concealed
Typical Concealed Flange HGUM Right Installation at Outside Corner
Concealed Flange – Allowable Loads with One Flange Concealed Fasteners Model No.
HGUM
W (in)
H (in)
5 1⁄4 to 9 11 to 30
End of Wall
CMU/ Concrete
Joist
Titen HD Anchors
SDS Screws
8-5⁄8"x5"
24-1⁄4"x2 1⁄2"
®
Outside corner
CMU Wall DF/SP/SCL Beam Uplift Download (160)
Concrete Wall CMU/Concrete Wall DF/SP/SCL Beam DF/SP/SCL Beam Uplift Uplift Download Download (160) (160)
1285
3150
5750
7025
3150
3" min. to top of wall (typ.)
7555
SKEWED • LGU, MGU, HGU, LGUM and HGUM hangers are available skewed up to 45°. • Apply the following reduction factors to published loads: Reduction Factors for Skewed LGU, MGU, HGU Model
Beam Cut Square Cut Bevel Cut Square Cut MGU/HGU less than 6" wide Bevel Cut MGU/HGU Bevel Cut 6" and wider LGU
Download 0.90 0.90 0.75 0.80
Uplift 0.60 0.60 0.65 0.65
0.80
0.55
Shaded cells grouted and reinforced per Designer (min.)
• For LGUM and HGUM see table below. • Concealed flanges are not available with skewed models. LGUM/HGUM Allowable Loads for Skewed (L/R) Applications
LGUM26-2X LGUM26-3X LGUM26-4X LGUM46X LGUM28-2X LGUM28-3X LGUM28-4X LGUM48X LGUM210-2X LGUM210-3X LGUM210-4X LGUM410X HGUM5.25X HGUM5.50X HGUM7.00X HGUM7.25X HGUM9.00X
Fasteners CMU/Concrete Joist Titen HD® SDS Anchors Screws
Allowable Loads CMU/Concrete (DFL, SP, LVL, PSL, LSL) Uplift Download (160) (100/115/125)
4- 3⁄8"x4"
4- 1⁄4"x2 1⁄2"
565
1965
6- 3⁄8"x4"
6- 1⁄4"x2 1⁄2"
1085
3080
8- 3⁄8"x4"
8- 1⁄4"x2 1⁄2"
1605
4190
8- 5⁄8"x5"
8- 1⁄4"x2 1⁄2"
1430
6455
8- 5⁄8"x5"
8- 1⁄4"x2 1⁄2"
1440
5820
8- ⁄8"x5"
8- ⁄4"x2 ⁄2"
1445
5185
5
1
1
15" min. to end of wall
Top View HGUM Skewed Right Bevel Cut 0°
Specify angle ° 45°
12" min. to end of wall
Top View LGUM Skewed Right Square Cut 0°
Specify angle ° 45°
Hanger Options
C-C-2015 © 2015 SIMPSON STRONG-TIE COMPANY INC. PRINTED 12/14
Model No.
Typical Concealed Flange HGUM Installation at Outside Corner (Concealed right shown)
Typical Skewed MGU Installation (Skewed left shown)
MBHA See Hanger Options General Notes. SKEWED SEAT • Seat can be skewed at 45° only. The maximum allowable download is 3495 lbs. and 1585 lbs. uplift for Height 7 1⁄4". For all other models, use the table listed download and uplift of 2390 lbs. • Order MBHAR for skew right and MBHAL for skew left.
Typical MBHA Skewed Right Installation 243