081892

Page 3

VIKING RECOMMENDED MATERIAL & COATING USED WITH FOAM SYSTEM PIPING AND VALVE COMPONENTS Base Material

VF3AFFF-MS / VF3AFFF

Coating NONE Ductile GALV. Iron JO1 65-45-12 NI1 & Cast JO6 Iron NI2 SA-278-30 QO3 QO6 Bronze/ Brass NONE C83600 JO1 Steel NONE Mild 1010 GALV. Copper C11000 NONE Stainless Steel Type 316 NONE

VF3ARC Concentrate *D *D *D - Note 2 *D - Note 2 *B *D *D A

3% Solution *B *C *D - Note 1 *D - Note 1 *B - Note 1 *C - Note 1 *D - Note 1 A - Note 1

A A B *D

*A A *B *C

A A D *D

A A B *C

B A D D

A

A

B

A

B

A

A

A

A

A

ACCEPTANCE DESIGNATION

3% Solution *B *C *D - Note 1 *D - Note 1 *B - Note 1 *D - Note 1 *D - Note 1 A - Note 1

Salt Water Solution & Salt Water D D Note 3 Note 3 B Note 3 B A

Concentrate *D D *D *D *B *C *D A

COATING DESIGNATION

A -

No effect during testing. Recommended use.

JO1

-

.7-1.0 Mil Electroless Nickel Plate

B -

Minor effect of pitting during test. Periodic inspection required.

JO6

-

2-3 Mil Electroless Nickel Plate

C -

Minor pitting. Sludge build-up due to chemical reaction. Requires annual flushing and inspection.

NI1

-

.7-1.0 Mil Electroless Nickel Plate w/ CU under

NI2

-

2-3 Mil Electroless Nickel Plate w/ CU under

D -

Severe corrosion and foam contamination. UNSATISFACTORY. Note 1 - Tested with concentrate. Testing in solution not necessary. Note 2 - Tested with FC600/FC600F

QO3 -

6-8 Mil Epoxy Powder Coat

QO6 -

8-10 Mil Halar Powder Coat

Galv. -

Standard Galvanized Pipe and Fittings

Note 3 - No test data available * -

Actual test performed by Viking at 150째F (65째C), observing physical damage after 1000 hour immersion in liquid and vapor

All other data determined from 3M Data given and Standard ASTM Corrosion Resistance Material Charts


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.