Selection and Erection – Equipment

Supply

Sinusoidal A.C.

Form of Residual Current

Recommended type of symbol AC B A

Suddenly applied

Slowly rising

Pulsating D.C.

Suddenly applied

Slowly rising

Smooth D.C.

Figure D 7.2  RCD d.c. selection criteria.

In a TT installation, where a single RCD protects the whole installation, it is essential that the device is placed at the origin of the installation (i.e. adjacent to the electricity meter). The connections and any switchgear between the RCD and the electricity supplier’s meter is required to meet the requirements for protection by the use of Class II equipment or equivalent insulation (531.4.1).