Table of Contents
Disconnect Switches
Technical Information
Technical Data Rated data
H212
H216
H220
H226
H233
H263
H406
H408
H410
H412
K616
K830
A
20
20
25
32
40
63
63
80
100
125
160
315
220 – 500 V 660 – 690 V
A A
20 16
20 16
25 20
32 32
40 40
63 63
63 63
80 80
100 100
125 100
160 125
315 125
AC-23A (cos φ = 0.65) 400 V
A
10
12
16
24
32
47
47
65
80
97
120
285
UL / CSA General Use
A A
15 15
20 20
25 25
30 30
40 40
60 60
63 63
80 80
100 100
100 100
175 175
240 240
3 5.5 5.5 5.5
3 5.5 5.5 5.5
4 7.5 7.5 7.5
5.5 11 11 11
7.5 15 15 15
15 22 22 22
15 22 22 22
18.5 30 30 30
22 37 37 37
30 45 45 37
37 75 90 55
75 132 132 55
Operational current Ie AC-21A AC-22A
300 V AC 600 V AC
Operational power at 50 – 60 Hz, 3 phase AC-23A 220 – 240 V kW 380 – 440 V kW 500 V kW 660 – 690 V kW AC-3
220 – 240 V 380 – 440 V 500 V 660 – 690 V
kW kW kW kW
2.2 3.7 3.7 3.7
2.2 3.7 3.7 3.7
3 5.5 5.5 5.5
4 7.5 7.5 7.5
5.5 11 11 11
11 18.5 18.5 18.5
11 18.5 18.5 18.5
15 22 30 22
22 30 37 30
30 37 45 37
22 45 45 45
37 55 55 55
UL / CSA 110 – 120 V AC 208 V AC 220 – 240 V AC 440 – 480 V AC 550 – 600 V AC
HP HP HP HP HP
1 2 2 3 5
1 2 2 3 5
1.5 3 3 5 5
2 5 5 10 10
3 7.5 7.5 15 15
5 10 15 30 40
5 10 15 30 30
7.5 10 20 30 30
10 15 25 30 30
15 15 30 40 40
15 15 15 40 50
25 30 30 50 50
V AC
—
500
500
500
500
500
500
500
500
500
500
500
Uninterrupted current Iu / Ith / Ithe
A
—
10
10
10
10
16
16
16
16
16
20
20
Operational current Ie AC-21A
A
—
10
10
10
10
10
10
10
10
10
20
20
110 – 240 V 380 – 440 V 500 V
A A A
— — —
2.5 1.5 1
2.5 1.5 1
2.5 1.5 1
2.5 1.5 1
6 4 1.5
6 4 1.5
6 4 1.5
6 4 1.5
6 4 1.5
6 4 2
6 4 2
600 V AC
A
—
10
10
10
10
10
10
10
10
10
20
20
—
A600
A600
A600
A600
A600
A600
A600
A600
A600
A600
A600
Rated data (auxiliary contacts) Operational voltage Ue
AC-15
UL / CSA General Use Heavy Pilot Duty
Short-circuit rating Max. fuse
gL
—
10
10
10
10
16
16
16
16
16
20
20
Conditional shortcircuit current
kAeff
—
3
3
3
3
3
3
3
3
3
10
10
mm2 mm2
— —
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
1 2.5
AWG
—
14
14
14
14
14
14
14
14
14
12
12
Terminal capacity flexible or multiwire including ferrule American Wire Gauge
min max
Conformity The Disconnect Switches H and K conform to the regulations of the EC guideline 73/23 EEC ‘Electrical equipment for application within certain voltage limits’ – specified as directive for low voltage devices.
The CE marking on all our products prove the conformity to the directives.
The conformity is proved by the complete compliance of the harmonized European standards – – – –
EN 60947-1 EN 60947-3 EN 60947-5-1 EN 60204-1.
The Disconnect Switches H and K are approved according to UL 508 and CSA 22.2, No. 14.
Salzer Electric products are developed, manufactured and tested according to these standards.
Switch Catalogue