Siemens Brake-module Siemens SINAMICS V20 - 6SL3201-2AD20-8VA0 (VFD) | Instronline

Page 262

Parameter list 7.2 Parameter list

Parameter

Dependency: Note:

Function

Range

Factory default

Can be changed

Scaling

3

End quick commissioning only for motor data

Data set

Data type

Acc. Level

Changeable only when P0010 = 1 (quick commissioning). P3900 = 1: When setting 1 is selected, only the parameter settings carried out via the commissioning menu "Quick commissioning" are retained; all other parameter changes, including the I/O settings, are lost. Motor calculations are also performed. P3900 = 2: When setting 2 is selected, only those parameters, which depend on the parameters in the commissioning menu "Quick commissioning" (P0010 = 1) are calculated. The I/O settings are also reset to default and the motor calculations performed. P3900 = 3: When setting 3 is selected, only the motor and controller calculations are performed. Exiting quick commissioning with this setting saves time (for example, if only motor rating plate data have been changed). Calculates a variety of motor parameters, overwriting previous values. These include P0344 (motor weight), P0350 (stator resistance), P2000 (reference frequency), P2002 (reference current). When transferring P3900, the inverter uses its processor to carry out internal calculations. Communications - both via USS as well as via the Fieldbus - are interrupted for the time that it takes to make these calculations. This can result in the following error messages at the connected SIMATIC S7 control (communications via Fieldbus):

r3930[0...4]

Parameter fault 30

Inverter fault 70

Inverter fault 75

Inverter data version

-

-

-

-

-

U16

3

-

-

U16

4

Displays the A5E number and the inverter data versions. Index:

P3950

[0]

A5E 1st 4 digits

[1]

A5E 2nd 4 digits

[2]

Logistic Version

[3]

Fixed Data Version

[4]

Calib Data Version

Access of hidden parameters

0 - 255

0

U, T

Accesses special parameters for development (expert only) and factory functionality (calibration parameter). r3954[0...12]

CM info and GUI ID

Index:

[0]

-

-

-

-

-

U16

4

-

-

U16

4

Used to classify firmware (only for SIEMENS internal purposes).

r3978

CM label (increment / branch)

[1]

CM label (counter)

[2]

CM label

[3...10]

GUI ID

[11]

GUI ID major release

[12]

GUI ID minor release

BICO counter

-

-

-

Counts the number of changed BICO links.

SINAMICS V20 Inverter

262

Operating Instructions, 11/2012, A5E03728167


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
Siemens Brake-module Siemens SINAMICS V20 - 6SL3201-2AD20-8VA0 (VFD) | Instronline by Instronline Instrumentation - Issuu