Low-Voltage Electrical Service Standard E.21-10

Page 169

Tables

Table 6

Last span of overhead service entrance This table is based on clearances in CAN/CSA-C22.3 No. 1. Type of line Voltage

Conductor type

Maximum length of span nearest to line (m)

Single-phase 120 V**

Duplex 4 NS75 (NS1) NS75 FT1 (NSF2)

38 38

Single-phase 120/240 V

Triplex 2 NS75 (NS1) NS75 FT1 (NSF2)

30 30

Triplex 2/0 NS75 (NS1) NS75 FT1 (NSF2)

25 25

Triplex 4/0 NS75 (NS1) NS75 FT1 (NSF2)

25 21

3 separate conductors No. 477 covered

Must be guyed (max. 6 m unguyed if max. tension = 100 N or 10 kg)*

Quadruplex 2 NS75 (NS1) NS75 FT1 (NSF2)

30 28

Quadruplex 4/0 (NS1) NS75 FT1 (NSF2)

21 18

4 separate conductors No. 477 covered

Must be guyed (max. 6 m unguyed if max. tension = 100 N or 10 kg)*

Three-phase 347/600 V and 600 V

* The maximum 6-m span nearest the line must not be taut (maximum: 100 N or 10 kg). ** For public lighting only Ref.: Sections 2.6.2, 2.7.2.5, 4.2 e) and Figure 2.17 Note: Parallel conductors are allowed provided that they are installed as specified in the Code.