Ask the Archivist By Erik Robinson
Q: Why didn’t the elevator in the new 1949 Supreme Court Building work properly?
A:
In addition to stains on the limestone walls of the rotunda, blocked drains, and several other problems, the elevator in the brand-new building was not working properly. Senior Justice Armstead Brown even had a diary entry about the problems, specifically criticizing the one elevator originally installed in the new building. Three elevators were specified in the building plan, but the legislative appropriation for construction did not match the
cost. The architect, James Gamble Rogers II, got around the problem by constructing all three elevator shafts, but installing only one until a future legislative session approved the extra spending. Use of the elevator was especially heavy at the opening and closing of business and during lunch hour. The elevator manufacturer, J. W. Bryce of Jacksonville, went to investigate at the urging of Rogers. The typed letter from Mr. Bryce of August 5, 1949 tells the story of what he found.
TRANSCRIPTION Mr. James Gamble Rogers, II Post Office Building Winter Park, Florida Dear Mr. Rogers:
August 5, 1949
Subject: Florida Supreme Court Tallahassee, Florida
I think I have finally determined what has been causing the trouble with our elevator in the Supreme Court Building. You will recall, the complaints were that at times the elevator was sluggish in operation and especially so during peak periods of traffic such as early morning, noon and late afternoon. On Monday, I examined the elevator and it was running satisfactorily. I returned on Tuesday and found the elevator doors were just creeping to their open and closed position. We immediately put a volt meter on the city power supply feeder lines in the elevator pent house and found the voltage was dovm to 185 volts and it should have been 208 volts. Naturally with such low voltage, the motor on the car that operates the doors looses torque, which effects the operation of the doors. Of course, the elevator will not run until the doors are closed. We also learned that they were having trouble with low voltage at the Florida State University in connection with the proper functioning of air conditioning equipment. I then visited the city manager's office and was told that they have been expierencing trouble with low voltage for quiet some time and that they have had complaints about its effect on operation of elevator am other equipment. Naturally when all the elevators in Tallahassee are operating under peak conditions, the voltage will drop to its lowest point. Also, on a cloudy day, the electric light load will pull down the voltage. Of course, the proper solution falls on the city's electrical distributive system and undoubtedly they are doing all they can to have it corrected by the company from whom they buy their power. We are going to try to find out what we can regarding the relief of this power smtuation.
JWB:jej CC: Yonge & Hart, Tallahassee, Florida
Yours very truly, BRYCE ELEVATOR COMPANY J. W. Bryce