Switching Devices Switches — Rotary Disconnect February 2007
Flange Mounted — Variable Depth
Product Description
Complete Operating Mechanism — C361NE1
8-95
Technical Data and Specifications
Handle Only — C361H1
8
Type C361 Disconnect Switches are suitable for installation in control enclosures having a right-hand flange. Fusible disconnect switches will accept R fuses as standard. Field installable rejection kits are supplied as standard on 100 and 200 ampere clips. For 30 and 60 ampere rejection clips, see footnote . The switch is UL component recognized for use on systems with up to 200,000 rms symmetrical amperes available fault current when Class R clips are supplied.
Standards and Certifications ■
UL — Component File E55492 ■ CSA — LR353-439
Figure 8-38. Mounting Dimension Requirements Table 8-146. Mounting Dimension Requirements in Inches (mm) Disconnect Switch Type 30 A and 60 A Non-fusible 30 A and 60 A Fusible
A
B
C
D
E
F
See Dimensions Below
See Dimensions Below
1.56 (39.6) 1.56 (39.6) 1.75 (44.5)
.96 (24.4) .96 (24.4) 1.10 (27.9)
4.00 (101.6) 4.00 (101.6) 5.50 (139.7)
3.50 7.12 (88.9) (180.8) 3.50 9.75 (88.9) (247.7) 3.38 7.12 (85.9) (180.8)
1.75 (44.5) 3.34 (84.8)
1.10 (27.9) 0.63 (16.0)
5.50 (139.7) 8.50 (215.9)
3.38 (85.9) 1.84 (46.7)
100 A Non-fusible 100 A Fusible 200 A Non-fusible and Fusible
Table 8-147. Line Lug Data
CA08101001E
Disconnect Switch Size
Wire Size
30 Ampere 60 Ampere 100 Ampere 200 Ampere
#2 – 14 Cu/Al #2 – 14 Cu/Al 1/0 – 14 Cu/Al 250 kcmil – #6 Cu/Al
For more information visit: www.eaton.com
G
11.88 (301.8) 15.50 (393.7)
Dimension A = The required wire bending spacing selected from Article 430-10 of the National Electrical Code. Dimension B = Minimum or maximum depth from inside of flange holding operating handle to panel where Disconnect Switch is mounted. (Variable 7 to 16 inches.)