FAS Track 1000 Fluted Deck Details For 1* and 2 Hour Fire Ratings Additional joint systems can be found @ www.cemcosteel.com
FAS STRAP
HW-D-0524 MIN. #6 FRAMING SCREW BY DESIGN FILLED WITH CONCRETE FLUTED METAL DECK
3/4" JOINT PROTECTION #8 x 1/2" FRAMING SCREW
CEMCO FAS STRAP
1/2" to 1 1/4" intumescent strip
TYPICAL STEEL FASTENERS BY DESIGN
CEMCO FAS TRACK 1000
10 3/6"
DRYWALL SCREW 1" LOWER THAN TRACK LEG METAL STUD BY DESIGN 5/8" TYPE "X" DRYWALL
Standard Wall, Parallel & Directly Under Deck Flute Assembly Rating 2 Hours
HW-D-0553
HW-D-0551 FLUTED METAL DECK WITH CONCRETE FILL
MINERAL WOOL
FLUTED METAL DECK WITH CONCRETE FILL
FIRE PROOFING OR MINERAL WOOL
3/4" JOINT PROTECTION STEEL BEAM TYPICAL STEEL FASTENERS BY DESIGN
1/2" x 20 GA. Z-BAR OR 16 GA. CRC BY DESIGN.
DRYWALL SCREW 1" LOWER THAN TRACK LEG
#8 x 1/2" FRAMING
DRYWALL SCREW 1" LOWER THAN TRACK LEG
5/8" TYPE "X" DRYWALL
STRUCTURAL STEEL FIREPROOFING (THICKNESS BY OTHERS)
3/4" JOINT PROTECTION CEMCO FAS TRACK 1000
#8 x 1/2" FRAMING SCREW
METAL STUD SPACING BY DESIGN
METAL STUD BY DESIGN 5/8" TYPE "X" DRYWALL
Standard Wall, Centered Directly Under Beam Assembly Rating 2 Hours
Standard Chase Wall, Perpendicular To Fluted Deck Assembly Rating 2 Hours
HW-D-0623 I-Beam Penetration at Shaft Wall
HW-D-0573 CEMCO FAS TRACK 1000
DRYWALL CUT AROUND I-BEAM WITH 2" GAP
MINERAL WOOL STUFFED BETWEEN FRAMING AND FIREPROOFING 50% COMPRESSED I-BEAM
CEMCO FAS J-TRACK
DRYWALL CUT AROUND I-BEAM WITH 2" GAP
METAL STUD (2) LAYERS DRYWALL
CEMCO FAS TRACK 1000
Z-CLIP
Standard Wall, @ Fluted Deck Beam Penetration Assembly Rating 2 Hours
*Single Layer of 5/8” type “X” Gypsum Panel For 1 Hour Fire Rating
MINERAL WOOL STUFFED BETWEEN FRAMING AND FIREPROOFING 50% COMPRESSED I-BEAM CH STUD
(2) LAYERS DRYWALL
Z-CLIP 3 8" NOMINAL GAP (3 4" JOINT PROTECTION)
SCREW
CEMCO FAS TRACK 1000 (TAPE ON FINISH SIDE ONLY)
3
8" NOMINAL GAP (3 4" JOINT PROTECTION)
Shaft Wall, @ Fluted Deck Beam Penetration Assembly Rating 2 Hours
CEMCO FAS J-TRACK