Catalogue pneumatique KMC Controls

Page 181

Pneumatic Products

TTC-1000 Series One-Pipe Pneumatic Temperature Transmitter Rigid Bulb

Specifications Action Output Supply Pressure

Air Consumption Connection Material Weight Temperature Limits Operating Shipping

Direct acting, proportional 3 to 15 psig (21 to 103.5 kPa) 20 psig (138 kPa); supplied through a 28.8 scim (7.87 mL/s) restrictor (HFO0022 or 0023 ordered separately), 30 psig (207 kPa) maximum 28.8 scim (7.87 mL/s) 1/8" FPT Zinc case, brass and stainless-steel mechanism, copper element 1.5 pounds (68 kg) 40 to 120° F (4 to 49° C) –40 to 140° F (–40 to 60° C)

Models

The TTC-1000 series are designed to sense air or fluid temperatures and transmit a fixed span 3–15 psig signal to controlling and indicating devices. These include receiver controllers, receiver gauges, relays and pressure switches. These devices are rigid stem versions and may be mounted directly into the airstream or in a well for water or steam applications. These one-pipe transmitters require a restrictor T and a constant air source. Available in several ranges for most control system applications.

TTC-1507 One-Pipe Pneumatic Temperature Transmitter Remote Bulb

TTC-1003 TTC-1004 TTC-1005 TTC-1006

0 to 100° F (–18 to 38° C) range, 6" stem 50 to 150° F (10 to 66° C) range, 6" stem 50 to 100° F (10 to 38° C) range, 8" stem 40 to 240° F (4 to 116° C) range, 4" stem

Accessories HFO-0022 HFO-0023 HMO-4503 HMO-4515 HMO-4504

Restrictor T, 28.8 scim (1 scfh), 3/16" nipples for 1/4" OD poly tubing, gray Restrictor insert, converts standard 1/4" compression fitting to 28.8 scim (1 scfh) restrictor TTC-1000 series wells, bronze. TTC-1000 series wells, stainless steel. TTC-1000/1500/2000 series duct bracket for mounting on ductwork

Specifications Action Range Output Supply Pressure Air Consumption Connection Material Temperature Limits Operating Shipping

The TTC-1507 is designed to sense outside air temperature and transmit a fixed signal to controlling and indicating devices such as receiver controllers and gauges, relays and pressure switches. It may be mounted directly into the airstream or the sensing bulb may be fed outside through an outside wall to sense temperature. It is a onepipe transmitter requiring a restrictor as well as a constant air source.

Electronic and Pneumatic Controls

Direct acting, proportional –40 to 160° F (–40 to 71° C) 3 to 15 psig (21 to 103.5 kPa) 20 psig (138 kPa); supplied through a 28.8 scim (7.87 mL/s) restrictor (HFO‑0022 or 0023) ordered separately 30 psig (207 kPa) maximum 28.8 scim (7.87 mL/s) 1/8" FPT Zinc case, brass and stainless-steel mechanism, copper element 40 to 120° F (4 to 49° C) –40 to 140° F (–40 to 60° C)

Accessories HFO-0022 HFO-0023 HMO-4523

Restrictor T, 28.8 scim (1 scfh), 3/16" nipples for 1/4" OD poly tubing, gray Restrictor insert, converts standard 1/4" compression fitting to 28.8 scim (1 scfh) restrictor Capillary clip

179