A WOMEN’S LOCKER | A-3/S-2 ASSEMBLY/STORAGE AREA: 273 SQFT 50 GROSS | TOTAL OCCUPANCY: 6

CODE REVIEW According to IBC Table 503 there is no limitation on floor area for buildings of occupancy group A-3 and construction type 1-B. The building has 3 floors and one mezzanine, falling within the 11 story limitation.

LOCKER | A-3/S-2 B MEN’S ASSEMBLY/STORAGE AREA: 721 SQFT 50 GROSS | TOTAL OCCUPANCY: 15

C STORAGE | S-2

9

NON HAZARDOUS STORAGE AREA: 175 SQFT 300 GROSS | TOTAL OCCUPANCY: 1

Based off of imagery it is understood that all structure and bearing walls are made of non combustible materials. The wood flooring falls within the 2 hour fire resistance requirement of IBC Table 601 for construction type 1-B buildings.

12

D LOGGIA | A-3

UNCONCENTRATED SEATING AREA: 6175 SQFT 15 NET | TOTAL OCCUPANCY: 412

13

E WAITING ROOM | A-3 UNCONCENTRATED SEATING AREA: 544 SQFT 15 NET | TOTAL OCCUPANCY: 36

F DOCTOR’S OFFICE | B BUSINESS AREA: 533 SQFT 100 GROSS | TOTAL OCCUPANCY: 6

Based on IBC 903.1.2.6 this building must be equipped with an automatic sprinkler system, reducing required egress widths.

G B

A

C

D

MISC OFFICES | B

E

F

This building satisfies the exit distance requirements as stated in IBC section 1016. These are further reduced by the added egress paths.

BUSINESS AREA: 1080 SQFT 100 GROSS | TOTAL OCCUPANCY: 11

According to table 1017.1 corridors have a required fire resistance rating of 0 with a sprinkler system. The ground floor corridor meets the prescribed width requirement. According to IBC section 1020.1.7.1 this building does not require smokeproof exits Ramp has been extended to ADA compliant slopes, and landings have been added at the appropriate intervals. GROUND FLOOR PLAN 1’ = 1/32”

The existing stairs have been brought up to code in width, and had gaurd and hand rails added as per IBC sections 1012 and 1013. The spiral stair has been removed.

C

M

Y

The restroom count does not satisfy the guidlines in IBC section 403. Additional restrooms have been added, and made ADA compliant.

CM

MY

CY

CMY

K

H VERANDA | A-3

EXTERIOR UNCONCONCENTRATED SEATING AREA: 5521 SQFT 15 NET | TOTAL OCCUPANCY: 368

I DANCING AREA | A-2

The perimiter railings of the building have been enclosed to satisfy IBC section 1013.

J DINING | A-2

And exit corridor has been provided to the office spaces below, creating a safe path to the exterior.

STANDING AREA: 364 SQFT 5 NET | TOTAL OCCUPANCY: 73

UNCONCENTRATED SEATING AREA: 4074 SQFT 15 NET | TOTAL OCCUPANCY: 279

K KITCHEN | F-1

KITCHEN AREA: 698 SQFT 200 GROSS | TOTAL OCCUPANCY: 4

1

L LOUNGE | A-3

UNCONCENTRATED SEATING AREA: 3297 SQFT 15 NET | TOTAL OCCUPANCY: 220

2

M MEZZANINE | A-3 UNCONCENTRATED SEATING AREA: 1993 SQFT 15 NET | TOTAL OCCUPANCY: 133

3

11

H

12 H

13 H

J

I

L M

MEANS OF EGRESS (STAIRS AND RAMPS)

K

ASSIGNMENT 2 PAGE: 1 OF 4 48-215 MATERIALS & ASSEMBLY SPRING 2018 INSTRUCTOR: DAMIANI FIRST FLOOR PLAN 1’ = 1/32”

CHRISTOPH ECKRICH


48215_eckrich_christoph_assignment2_p2_150.pdf 1 3/23/2018 1:09:06 PM

N SUN DECK | A-3

CODE ANNOTATION KEY

BATHING DECK AREA: 6370 SQFT 15 GROSS | TOTAL OCCUPANCY: 420

1. TABLE 1016.1 REQUIRES THAT THE MAXIMUM EXIT TRAVEL DISTANCE FOR A BUILDING EQUIPPED WITH AUTOMATIC SPRINKLERS BE LESS THAN 250 FEET. MAXIMUM TRAVEL DISTANCE IN BUILDING IS 84 FEET.

2 3 6

7

11

2. AREAS OF REGUGE AS REQIURED IN IBC SECTION 1007 3. UPON CHANGE OF DIRECTION A LANDING MUST BE PROVIDED AND BE AT LEAST THE DIMESIONS OF THE PATH OF EGRESS.

N

4. EGRESS CORRIDORS MUST HAVE AT LEAST 80” OF HEAD ROOM AS PER IBC SECTION 1009 5. EGRESS STAIRS MUST MEET HEIGHT, WIDTH, NOSING AND EDGE REQUIREMENTS OUTLINED IN IBC SECTION 1009 6. RAMPS CANNOT EXTEND MORE THAN 30’ WITHOUT PROVIDING A LANDING OF ADEQUATE SIZE 7. RAMPS CANNOT EXCEED 12% GRADE 8. HANDRAILS AND GUARDS MUST BE COMPLIANT WITH IBC SECTION 1012 AND 1013. 9. THE OFFICES HAVE BEEN GIVEN A FIRE RATED EXIT CORRIDOR TO THE EXTERIOR OF THE BUILDING

ROOF LEVEL PLAN 1’ = 1/32”

10. HANDRAILS MUST EXTEND 12” BEYOND THE LAST STEP AND MUST RETURN TO THE WALKING SURFACE AS PER IBC SECTION 1012.5

C

M

11. GUARDS MUST BE PLACED AT ANY EDGE WITH A DROP FO MORE THAN 30” AS REQUIRED BY IBC SECTION 1013.

Y

CM

MY

CY

12. RESTROOMS SERVICE THE FLOORS ABOVE AND BELOW. THE NUMBER OF FACILITIES HAS BEEN MADE COMPLIANT WITH IBC SECTION 400.

CMY

K

13. RESTROOMS HAVE BEEN MADE COMPLIANT WITH ADA ACCESSIBILITY STANDARDS AS OUTLINED IN SECTION 604. 14. SECTION 1020 REQUIRES THAT 50% OF INTERIOR EGRESS MUST BE ENCLOSE WITH FIRE BARRIORS CONTRUCTED AS PER THE REQUIREMENTS IN SECTION 709

MEANS OF EGRESS (STAIRS AND RAMPS)

ASSIGNMENT 2 PAGE: 2 OF 4

FRONT ELEVATION 1’ = 1/32” LOOKING NORTH

3 6 8 9 11

7

48-215 MATERIALS & ASSEMBLY SPRING 2018 INSTRUCTOR: DAMIANI CHRISTOPH ECKRICH


48215_eckrich_christoph_assignment2_p3_150.pdf 1 3/23/2018 1:10:16 PM

CODE ANNOTATION KEY

2

6

5

5

1. TABLE 1016.1 REQUIRES THAT THE MAXIMUM EXIT TRAVEL DISTANCE FOR A BUILDING EQUIPPED WITH AUTOMATIC SPRINKLERS BE LESS THAN 250 FEET. MAXIMUM TRAVEL DISTANCE IN BUILDING IS 84 FEET.

2

2. AREAS OF REGUGE AS REQIURED IN IBC SECTION 1007 3. UPON CHANGE OF DIRECTION A LANDING MUST BE PROVIDED AND BE AT LEAST THE DIMESIONS OF THE PATH OF EGRESS.

4'-2 1/2" 5'-0"

11'-0 1/4"

4'-6 1/2"

5'-0"

4. EGRESS CORRIDORS MUST HAVE AT LEAST 80” OF HEAD ROOM AS PER IBC SECTION 1009

7'-4"

8'-0 1/2"

1'-0 3/4" 4'-11 1/2"

ACCESS RAMP PLAN

4'-0"

1 1/2"

5. EGRESS STAIRS MUST MEET HEIGHT, WIDTH, NOSING AND EDGE REQUIREMENTS OUTLINED IN IBC SECTION 1009

1’ = 1/16” 15'-9 1/2"

ENCLOSED STAIR PLAN

EXTERIOR STAIR PLAN

1’ = 1/16”

1’ = 1/16”

6. RAMPS CANNOT EXTEND MORE THAN 30’ WITHOUT PROVIDING A LANDING OF ADEQUATE SIZE 7. RAMPS CANNOT EXCEED 12% GRADE

5

8

4

7

8. HANDRAILS AND GUARDS MUST BE COMPLIANT WITH IBC SECTION 1012 AND 1013.

8

9. THE OFFICES HAVE BEEN GIVEN A FIRE RATED EXIT CORRIDOR TO THE EXTERIOR OF THE BUILDING

15'-9 1/2"

3'-8 1/4"

M

3'-8 3/4"

MY

CY

6'-5"

30'-0"

CM

4'-4"

Y

10. HANDRAILS MUST EXTEND 12” BEYOND THE LAST STEP AND MUST RETURN TO THE WALKING SURFACE AS PER IBC SECTION 1012.5

8'-9 1/2"

C

3'-10 1/2"

3'-9 3/4"

3'-0 1/4"

3'-8"

12. RESTROOMS SERVICE THE FLOORS ABOVE AND BELOW. THE NUMBER OF FACILITIES HAS BEEN MADE COMPLIANT WITH IBC SECTION 400.

2'-6"

CMY

K

11. GUARDS MUST BE PLACED AT ANY EDGE WITH A DROP FO MORE THAN 30” AS REQUIRED BY IBC SECTION 1013.

8'-8" 4'-2 1/2" 4'-11 1/2"

ACCESS RAMP SECTION

ENCLOSED STAIR SECTION 1’ = 1/16”

13. RESTROOMS HAVE BEEN MADE COMPLIANT WITH ADA ACCESSIBILITY STANDARDS AS OUTLINED IN SECTION 604.

EXTERIOR STAIR SECTION

1’ = 1/16”

1’ = 1/16”

14. SECTION 1020 REQUIRES THAT 50% OF INTERIOR EGRESS MUST BE ENCLOSE WITH FIRE BARRIORS CONTRUCTED AS PER THE REQUIREMENTS IN SECTION 709

FIRST FLOOR BATHROOM PLAN

3'-7"

6'-11"

3'-9"

5'-10"

5'-10"

4'-3"

5'-10"

6'-11"

6'-11" 5'-10"

4'-3"

3'-7"

4'-3"

6'-11"

4'-3"

MEANS OF EGRESS (STAIRS AND RAMPS) 3'-9"

ASSIGNMENT 2 PAGE: 3 OF 4

GROUND FLOOR BATHROOM PLAN

1’ = 1/16”

1’ = 1/16”

13

12

13

12

48-215 MATERIALS & ASSEMBLY SPRING 2018 INSTRUCTOR: DAMIANI CHRISTOPH ECKRICH


48215_eckrich_christoph_assignment2_p4_150.pdf 1 3/23/2018 1:11:44 PM

CODE ANNOTATION KEY 1. TABLE 1016.1 REQUIRES THAT THE MAXIMUM EXIT TRAVEL DISTANCE FOR A BUILDING EQUIPPED WITH AUTOMATIC SPRINKLERS BE LESS THAN 250 FEET. MAXIMUM TRAVEL DISTANCE IN BUILDING IS 84 FEET. 2. AREAS OF REGUGE AS REQIURED IN IBC SECTION 1007 3

3. UPON CHANGE OF DIRECTION A LANDING MUST BE PROVIDED AND BE AT LEAST THE DIMESIONS OF THE PATH OF EGRESS. 4. EGRESS CORRIDORS MUST HAVE AT LEAST 80” OF HEAD ROOM AS PER IBC SECTION 1009 5. EGRESS STAIRS MUST MEET HEIGHT, WIDTH, NOSING AND EDGE REQUIREMENTS OUTLINED IN IBC SECTION 1009 6. RAMPS CANNOT EXTEND MORE THAN 30’ WITHOUT PROVIDING A LANDING OF ADEQUATE SIZE 7. RAMPS CANNOT EXCEED 12% GRADE 8. HANDRAILS AND GUARDS MUST BE COMPLIANT WITH IBC SECTION 1012 AND 1013.

6 7

9. THE OFFICES HAVE BEEN GIVEN A FIRE RATED EXIT CORRIDOR TO THE EXTERIOR OF THE BUILDING 10. HANDRAILS MUST EXTEND 12” BEYOND THE LAST STEP AND MUST RETURN TO THE WALKING SURFACE AS PER IBC SECTION 1012.5

C

M

11. GUARDS MUST BE PLACED AT ANY EDGE WITH A DROP FO MORE THAN 30” AS REQUIRED BY IBC SECTION 1013.

Y

CM

MY

CY

12. RESTROOMS SERVICE THE FLOORS ABOVE AND BELOW. THE NUMBER OF FACILITIES HAS BEEN MADE COMPLIANT WITH IBC SECTION 400.

CMY

K

13. RESTROOMS HAVE BEEN MADE COMPLIANT WITH ADA ACCESSIBILITY STANDARDS AS OUTLINED IN SECTION 604.

11

14. SECTION 1020 REQUIRES THAT 50% OF INTERIOR EGRESS MUST BE ENCLOSE WITH FIRE BARRIORS CONTRUCTED AS PER THE REQUIREMENTS IN SECTION 709

MEANS OF EGRESS (STAIRS AND RAMPS)

ASSIGNMENT 2 PAGE: 4 OF 4 14

48-215 MATERIALS & ASSEMBLY SPRING 2018 INSTRUCTOR: DAMIANI CHRISTOPH ECKRICH