MODELS
WHAD 1500 Rack
GENERAL SPECIFICATIONS Rated/Active power
1500 VA / 1050 W
Technology
On line Double Conversion VFI-SS-11
Waveform
Sinusoidal
INPUT SPECIFICATIONS Input voltage Input frequency
230 V 50-60 Hz ±2% Autosensing
Input voltage range
184 V to 265 V at 100% of the load
Input power factor
>0.99
Input Current THD
3%
OUTPUT SPECIFICATIONS Output voltage Output frequency (rated) Crest factor
230V ± 1% 50/60 Hz synchronized 3,5 : 1
THD Output voltage
1%
Permissible overload
300% for 1 sec, 200% for 5 sec, 150% for 30 sec
Bypass
Electromechanical synchronized internal automatic (for overloads and operating faults)
BATTERIES Autonomy expansion Type/Voltage set of batteries
Yes VRLA - AGM 72Vdc
50% load autonomy
30 min
80% load autonomys
15 min
COMMUNICATION & MANAGEMENT Display and Indicators
Multicoloured LED status indicator, alarms and acoustic signals
Communication ports
1 RS232 serial port
Remote management
UPS Communicator software can be downloaded free of charge from www.metasystemenergy.com web site
PHYSICAL SPECIFICATIONS Dimensions H x L x W
88 (2U) x 483 x 552 mm
Battery cabinet dimensions H x L x W
88 (2U) x 483 x 552 mm
Net weight
20,5 Kg
ENVIRONMENTAL CONDITIONS Operating temperature/humidity Maximum noise audible 1 m from unit Thermal dissipation
0 ÷ 40 °C / 20-80% <40 dBA 287 BTU/h
CONFORMITY Certifications Standard Warranty
EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3 2 years, batteries included
53