Recommended Lighting Levels Explained 200 Lux - For general occupancy 300 Lux - For moderately easy tasks 500 Lux - For moderately difficult tasks
Lighting design & dimming compatibility guide How to use the ready reckoner lux planner
Design criteria
1. Select the fitting
1. All dimensions shown are in metres
2. Choose the Lux Level you require
2. Ceiling height assumed @ 2500mm. Ariah2 @ 6000mm
3. Select the closest room dimensions of the space
3. Average Surface Reflectances used - Floor 20 / Walls 50 / Ceiling 70
4. Use the table to determine the quantity of fittings required
4. Working Plane measured at 750mm above FFL 5. Maintenance Factor assumed @ 0.85
200, 300 & 500 Lux EN-DDLH413AK/40
EN-DDLH618AK/40
300 & 500 Lux
EN-DDLH818AK/40
EN-DDLH825AK/40
EN-DDLH840AK/40
EN-DDLH1045AK/40
EN-FP6060BAK EN-FP1230BAK
Watts
13
18
18
25
40
45
Watts
40
40
Lumens
1230
1800
1800
2500
4000
4380
Lumens
3400
3400
Room Size
Choose Lux Level
Length (m)
Width (m)
300 Lux
500 Lux
300 Lux
500 Lux
L (m)
W (m)
160 lux
240 lux
160 lux
240 lux
160 lux
240 lux
160 lux
240 lux
240 lux
320 lux
240 lux
320 lux
2.5
2.5
1
1
1
1
2.5
2.5
2
3
2
3
2
3
1
2
1
1
1
1
2.5
5
2
3
2
3
2.5
5
3
5
3
4
3
4
2
4
2
2
2
2
2.5
7.5
3
4
3
4
2.5
7.5
4
6
4
5
4
5
3
4
2
3
2
3
2.5
10
4
5
4
5
2.5
10
5
8
4
7
4
7
4
5
3
4
3
4
5
5
4
4
4
4
5
5
5
8
5
8
5
8
4
5
4
4
4
4
5
7.5
6
6
6
6
5
7.5
6
12
6
9
6
9
5
8
4
5
4
5
5
10
8
8
8
8
5
10
10
15
8
12
8
12
6
10
5
6
5
6
7.5
7.5
6
9
6
9
7.5
7.5
9
16
9
15
9
15
8
12
5
6
5
6
7.5
10
9
12
9
12
7.5
10
12
20
12
16
12
16
9
15
6
9
6
9
10
10
10
16
10
16
10
10
20
30
15
20
15
20
12
16
9
12
9
12
X = Specific luminaire not suitable to achieve LUX level in room size For assistance please email us on australia@enlitelighting.com Notes
150 & 300 Lux
The lighting calculation information displayed above is an indicative guide for the areas and design criteria indicated. It is recommended that the customer carries out his own calculations to verify that the proposed quantity of luminaires meet the specified requirements. All quantities shown are calculated and rounded upwards and then determined into an amount that offers a grid pattern for installation. Enlite does not accept responsibility for lighting installations which fail to comply with specification where this criteria has been used to estimate quantity.
Brand
EN-DGU005H Standard dimmers Cat.No. Dimming Qty GU10 lamps range per dimmer
EN-HB100BAK/40 EN-HB150BAK/40 EN-HB200BAK/40 Watts
100
150
200
Lumens
12350
18525
24700
Room Size
Choose Lux Level
L (m)
W (m)
80 lux
160 lux
80 lux
160 lux
80 lux
160 lux
10
10
2
4
2
4
2
2
10
20
3
6
2
4
2
3
10
30
6
10
3
6
3
4
20
20
6
12
6
9
4
5
20
30
8
15
6
12
4
8
30
30
9
20
9
16
6
12
Manufacturer Cat.No. HPM
MTEcourgar60
SDA450
18 to 100%
2-10
Nelson
MTEcourgar60
CABAC
HNS630DT
17 to 100%
2-10
Speedy
TE-0105 C171
CLIPSAL
32E450UDM
23 to 100%
2-10
CLIPSAL
32ELEDM
13 to 100%
2-10
Speedy
TE-0070 C101
DigiNet
MEDM
13 to 100%
2-10
Osram
ET-Redback 40/230-240
Osram
ET-P 60/230-240
Philips
ET-S 15
Atco
TEC070A
Atco
PossumV99
ASAL
• The maximum number of lamps tested may be above the safe load limit of the dimmer. This information can be gained from the manufacturer of the dimmer. • All tests carried out in lab test conditions.
EN-MR165 lamp with transformer
For up to date dimming & transformer compatibility visit au.enlitelighting.com DUE TO THE NATURE OF EVOLVING LED TECHNOLOGY SPECIFICATION MAY VARY VISIT ENLITELIGHTING.COM FOR UP TO DATE INFORMATION Lumen values +/-10%
au.enlitelighting.com
65