C-46 Manual

Page 28

8.6.3

Min./Max. supply

1. Navigate through the screens using the navigation keys:

The parameters Min./Max. supply are used for setting the minimum and maximum temperatures in the supply circuit.

Uponor > Main menu > Control settings > Cooling > Dew point

To set the minimum and maximum supply temperatures:

Example screen:

1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Cooling > Min./max. supply Example screen:

2. Select Dew point margin 3. Set the parameter to the required value and press OK.

2. Select the required minimum and maximum temperatures. Minimum supply temperature:

• • •

Default setting: 5 °C Setting range: 5–40 °C

Default setting: 25 °C Setting range: 5–40 °C Setting accuracy: 1 °C

3. Confirm the setting by pressing OK. 8.6.4

Default setting: 4 Setting range: 0–8 Setting accuracy: 1

4. Select Dew point offset

Setting accuracy: 1 °C

Maximum supply temperature:

• • •

• • •

Indoor sensor influence

The indoor influence is a supply temperature adjustment that is depending on the difference of the indoor temperature and the indoor setpoint. This means that the supply will be increased if the indoor temperature is to low and it will be decreased if the indoor temperature is to high. The size of the adjustment is given by the Indoor sensor influence parameter. To set the Indoor sensor influence parameter: 1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Heating > Indoor sensor influence Example screen:

5. Set the parameter to the required value and press OK.

• • •

Default setting: 1 Setting range: -5 to +5 Setting accuracy: 1

6. Select Calculated dew point. The screen displays the dew point calculated by the Climate Controller C-46. 7. Select Sensor mode. This selection is used when one or more Relative Humidity Sensors H-56 is connected to the system through the Controller C-56 Radio. To set the indoor sensor mode parameters: 7.1. Navigate through the screens using the navigation keys: Uponor > Main menu > Control settings > Cooling > Sensor mode Example screen:

2. Select the desired settings. Lower value:

• • •

Default setting: 4 Setting range: 0–8 Setting accuracy: 0.1

Upper value:

• • •

7.2. Select Zone. 7.3. Select Mode and press OK. Default mode: Average Mode selections: Average, Maximum

Default setting: 4 Setting range: 0–8 Setting accuracy: 0.1

3. Press OK to confirm the setting. 8.6.5

Dew point

To set the dew point parameters:

28

CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL