7.3

Parameter screens

The parameter setting screens can only be accessed when the Climate Controller C-46 is set up in Installer access level. 7.3.1

Parameter values:

• •

Default setting: 0.2 Parameter range: 0.1–1.6

Navigating parameter screens

To navigate through the parameter setting screens:

7.3.6

1. Press OK for two seconds to highlight the parameter.

The T-adjustment parameter can be set if the Climate Controller C-46 is set up in any Heating – outdoor controlled mode.

2. Press the

and

keys to change the parameter value.

3. Press OK to confirm the setting. 4. Press the Press the

key to display the next screen. key to display the previous information screen.

Example screens:

T-adjustment

The T-adjustment parameter defines the offset used for the temperature graph. For more information, see section 10.2 Adjusting the heat curve, page 46. Parameter values:

• •

Default setting: 3 Parameter range: -8 to +8

7.3.7 Supply information 7.3.2

System standby mode

The System standby mode can be set in any Climate Controller C-46 operating mode. Standby modes:

Normal operation (default)

System standby

7.3.3

Heating supply setpoint

The Heating supply setpoint can be set if the Climate Controller C-46 is set up in Heating – fixed supply mode. Setpoint values:

• •

Default setting: 35 °C Setpoint range: 5–40 °C

7.3.4

Indoor setpoint

The Indoor setpoint can be set if a wired indoor sensor is used and the Climate Controller C-46 is set up in Heating – indoor controlled mode or Heating – outdoor controlled supply with indoor compensation mode. Setpoint values:

• •

Default setting: 22 °C Setpoint range: 5–35 °C

7.3.5

The Supply information can be displayed if the Climate Controller C-46 is set up in any Heating – outdoor controlled mode. The supply information is used as a tool when tuning the temperature graph with the T-slope and T-adjustment parameters. The screen displays the supply temperature for four different outdoor temperatures. For more information, see section 10.2 Adjusting the heat curve, page 46. 7.3.8

Cooling supply setpoint

The Cooling supply setpoint can be set if the Climate Controller C-46 is set up in any Cooling mode. Setpoint values:

• •

Default setting: 18 °C Setpoint range: 5–25 °C

7.3.9 Cooling indoor setpoint The Cooling indoor setpoint can be set if a wired indoor sensor is used and the Climate Controller C-46 is set up in Cooling – indoor compensated supply with dew point control mode. Setpoint values:

• •

Default setting: 20 °C Setpoint range: 5–35 °C

T-slope

The T-slope parameter can be set if the Climate Controller C-46 is set up in any Heating – outdoor controlled mode. The T-slope parameter defines the gradient of the temperature graph. For more information, see section 10.2 Adjusting the heat curve, page 46.

20

CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL