Holophane Outdoor Product Catalog

Page 262

HOLOPHANE® Pulse Start Metal Halide: Pulse start ballasts are for metal halide lamps that require a high voltage pulse for starting. Peak lead, reactor, lag and magnetic regulator ballasts are all available in pulse start configurations. Starters are required, however the pulse requirements may vary with lamp wattage. Starters for HPS ballasts are not interchangeable with those for pulse start metal halide.

BALLAST TYPES:

Reactor

HX – High Reactance

A reactor may be used when the input voltage to the luminaire meets the operational voltage requirements of a metal halide lamp. A ±5% line voltage variation will result in a ±12% in lamp wattage. Power factor is typically above 90% when the capacitor is included. The maximum line current is drawn when the lamp is not operating.

260

|

OUTDOOR

|

Line starting current is greater than operating current. Power factor is above 90%. A ±5% line voltage variation will result in ±10% variation in wattage.

PRODUCT INFORMATION GUIDE

|

CWA

Mag Reg

The starting current in this circuit is lower than the operating current. A ±10% line voltage variation will result in a ±10% variation in wattage. Power factor is above 90%.

Ballast Information Guide

|

Magnetic HID Ballasts

The starting current in this circuit is lower than the operating current. A ±10% line voltage variation could result in a ±3% change in wattage depending on design factors. Power factor is above 90%. Internal wattage losses are higher than Lead–type regulators.

www.holophane.com


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.