Lyd fra varmepumper

Page 1

LYD FRA VARMEPUMPER

weishauptenergi.dk
2 Indhold Lyd fra varmepumper 3 Lydudbredelse ...................................................................................................................................................................................................................... 4 Støjgrænse for boligområder ................................................................................................................................................................................... 6 Lyddata på Weishaupt varmepumper ................................................................................................................................................................ 7 Vejledende opstillingsfaktor 7 Split luft/vand varmepumpe 6 kW (WSB A RME AI) 8 Split luft/vand varmepumpe 8 kW (WSB A RME AI) .......................................................................................................................... 8 Split luft/vand varmepumpe 10 kW (WSB A RME AI) ....................................................................................................................... 8 Monoblok luft/vand varmepumpe 18 kW (WWP L 18 AD) ........................................................................................................... 9 Monoblok luft/vand varmepumpe 25 kW (WWP L 25 A-2) .......................................................................................................... 9 Monoblok luft/vand varmepumpe 40 kW (WWP L 40 AD-2) 9 Monoblok luft/vand varmepumpe 60 kW (WWP L 60 AD-2) ..................................................................................................... 9 Lyd fra flere lydkilder ................................................................................................................................................................................................... 10 Kildehenvisning ............................................................................................................................................................................................................... 11

Lyd fra varmepumper

Varmepumper fungerer ved at et kølemiddel fordamper og komprimeres således at kølemidlet stiger i temperatur, herefter afsættes den opnåede temperatur i varmeanlægget og kølemidlet kondenserer, trykket reduceres gennem en ekspansionsventil, hvorefter processen gentages. For udestående varmepumper kan dette generere lyde der sammen med ventilatorerne kan opfattes generende for nogle mennesker. Lyd er en lidt svær størrelse og opfattes meget forskelligt fra person til person.

Skal man forklare lyd helt enkelt, er lyd små vibrationer i lufttrykket, der bevæger sig bølgevis omkring det atmosfæriske tryk. Jo større svingning jo højere lyd.

Den lyd som du hører, opgøres ofte i en enhed kaldet decibel (dB) oftest udtrykt som dB(A), hvor A’et repræsenterer en frekvensvægtning, der får lyden til at være sammenlignelig med den menneskelige opfattelse.

Forholdet mellem trykket der frembringer hørbar lyd og trykket der ligger på smertegrænsen er ca. 1:106, mens forholdet mellem den svageste udsendte effekt, og effekten fra de kraftigste lydkilder er endnu større. Decibel er derfor en nærliggende omregning, dertil kommer at decibel er en relativt nem enhed at arbejde med lyd i, da denne logaritmiske omregning dækker hele det enorme spektrum af lydniveauer som det menneskelige øre kan opfatte.

Når man snakker om lyd fra varmepumper snakker man ofte om lydeffektniveau LwA og lydtryksniveau LpA, og der kan nemt blive rodet rundt i begreberne når man snakker lyd. Men de to begreber hænger også meget sammen og så alligevel ikke. Kort forklaret er lydeffekt den effekt der skal til for at generere lyden, mens lydtrykket er er den lyd som du opfatter i den aktuelle afstand.

3

Lydudbredelse

Da lyd er bølger i luften, vil lyd fra en varmepumpe meget gerne ud af alle sider på varmepumpen. De sider der er afskærmede vil skabe refleksioner og kaste lyden tilbage. Der vil derved også altid komme mere lyd ud af de åbne sider på udedelen, end der kommer ud fra de lukkede.

Hvis man forestiller sig en lyd kilde som en diskokugle under optimal belysning. Lyden kastes ud til alle sider præcis som lyset ville blive fra en diskokugle. Hvis man så sidestiller bløde overflader såsom græs og jord som en halv blank metalplade og hårde overflader såsom vægge og fliser som relativt blanke spejle.

Hvis man holdt den omtalte metalplade op under diskokuglen ville det langt fra være alt lyset der blev kastet tilbage. Holdt man derimod det omtalte spejl op under diskokuglen, ville størstedelen af lyset blive kastet tilbage og sprede sig. Samme forhold opstår med lyd, eksempelvis hvis man stiller en varmepumpe på et hårdt underlag som eksempelvis fliser, vil lyden rejse længere end den vil på en græsoverflade. Stiller man en varmepumpe op af væggen på flise underlag, vil man så have tilføjet endnu en reflekterende overflade og lyden flytter sig igen længere.

Friudstråling

Lydudbredelseudendørs

Lydudbredelseudendørs Reekterendeoverade

Som det ses af ovenstående falder lydtrykket i takt med afstanden til lydkilden stiger. Hvor meget lydtrykket falder, er variabelt alt efter valgt placering og antallet af reflekterende overflader. Kender man varmepumpens lydeffektniveau kan man enten bruge energistyrelsens støjberegner eller den tyske Schallrechner til at beregne lydtryksniveauet ved en given afstand. Alternativt kan man aflæse reduktionen i det efterfølgende skema.

4

Der kan være visse fordele ved at bruge den tyske Schallrechner, da alle producenter på det tyske marked er lagt ind på forhånd med deres lyddata.

Du kan finde beregneren på følgende link: https://www.waermepumpe.de/schallrechner/

Resultatet man får ud kommer i nedenstående format, og du kan selv fastsætte afstanden til modtageren som repræsenteres af den sorte streg.

I det indsatte eksempel ovenfor er der brugt en WWP LB 12-A R i natmodus. Afstanden til modtager er sat til 3 meter og udedelen er fritstående.

5
25 20 15 10 5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Lydtryksniveauet falder med 1/2 sfærisk lydformering Fald i lydtryksniveau [db(A)] Afstand [m] Fritstående installation Installation op ad husmur - Hjørneinstallation

Støjgrænse for boligområder

Miljøstyrelsen lavede i 1984 nogle vejledende støjgrænser til brug i forhold til erhverv og industri. Denne har siden fundet anvendelse i forbindelse med udbredelsen af luft/-vand varmepumper. Med Bygningsreglementet 2010 blev disse grænseværdier skrevet ind i bygningsreglementet, og var derved ikke længere vejledende, men lovgivende. Det er disse værdier kommuner henholder sig til i forbindelse med tvist om støjgener.

Støjgrænser for boligområder Lr

Døgnperiode

Etageboliger, blandet boliger og erhverv. Det åbne land (enkeltliggende huse)

Ovenstående værdier er en lidt underlig størrelse, så for at gøre det sammenligneligt er der indsat en simpel sammenligning nedenunder.

6
Sommerhusområder Tæt lavt boligområde (Parcel huse, rækkehuse mv.)
Hverdage kl. 07 – 18 Lørdage kl. 07 - 14 Lr ≤ 40 dB Lr ≤ 45 dB Lr ≤ 50-55 dB Hverdage kl. 18 – 22 Lørdage kl. 14 – 22 Søndage kl. 07 – 22 Lr ≤ 35 dB Lr ≤ 40 dB Lr ≤ 45 dB Alle dage kl. 22 - 07 Lr ≤ 35 dB Lr ≤ 35 dB Lr ≤ 40 dB
ÅNDEDRÆT VISNE BLADE HVISKEN MODERAT REGNVE JR KØLESKAB SAMTALE BY TRAFIK LASTBIL FØNTØRRER HELIKOPTER TROMBONE UDRYKNING FYRVÆRKERI FLY 140 dB SMERTETÆRSKEL 110 dB EKSTREMT HØJT 80 dB MEGET HØJT 70 dB HØJT 50 dB MODERAT TIL STILLE 40 dB SAGTE 0 dB

Lyddata på Weishaupt varmepumper

Følgende lyddata er ikke målte værdier, men beregnede. Alle værdier er opgivet i dB(A), og er vejledende værdier. Der kan være afvigelser afhængig af opstillingsstedets udformning. Alle lydeffektniveauer er taget fra valideret data. De resulterende lydtrykniveauer er beregnet ud fra en teoretisk tilnærmelse der opstilles som vist nedenfor:

LpA = Lydtryksniveau (dBA),

LwA =Lydeffektniveau (dBA)

Q = Vejledende opstillingsfaktor (-)

r = Afstand mellem varmepumpe og modtager (m)

Vejledende opstillingsfaktor

Beregningen af lydudbredelsen gælder under følgende, idealiserede betingelser:

• Lydkilden er en punktlydkilde.

• Varmepumpens opstilling- og driftsbetingelser svarer til betingelserne ved bestemmelse af lydeffekten.

• Ved Q=2 finder emissionen sted i det åbne område (ingen reflekterende genstande/bygninger i omgivelserne).

• Ved Q=4 og Q=8 forudsættes fuldstændig refleksion på nabofladerne.

• Der er ikke taget højde for andelene af fremmed støj fra omgivelserne.

7 dB dB dB
Q = 2 Q = 4 Q = 8

Split luft/vand varmepumpe 6 kW (WSB A RME AI)

Split luft/vand varmepumpe 8 kW (WSB A RME AI)

Split luft/vand varmepumpe 10 kW (WSB A RME AI)

8
WSB 6-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 62 dB(A) Q=2 54 48 44 42 40 38 37 36 35 34 30 26 Q=4 57 51 47 45 43 41 40 39 38 37 34 29 Q=8 60 54 50 48 46 44 43 42 41 40 37 32 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29 WSB 8 -A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 58 dB(A) Q=2 50 44 40 38 36 34 33 32 31 30 26 22 Q=4 53 47 43 41 39 37 36 35 34 33 30 25 Q=8 56 50 46 44 42 40 39 38 37 36 33 28 Natdrift 56 dB(A) Q=2 48 42 38 36 34 32 31 30 29 28 24 20 Q=4 51 45 41 39 37 35 34 33 32 31 28 23 Q=8 54 48 44 42 40 38 37 36 35 34 31 26 WSB 10-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 63 dB(A) Q=2 55 49 45 43 41 39 38 37 36 35 31 27 Q=4 58 52 48 46 44 42 41 40 39 38 35 30 Q=8 61 55 51 49 47 45 44 43 42 41 38 33 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29 WSB 6-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 62 dB(A) Q=2 54 48 44 42 40 38 37 36 35 34 30 26 Q=4 57 51 47 45 43 41 40 39 38 37 34 29 Q=8 60 54 50 48 46 44 43 42 41 40 37 32 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29 WSB 8 -A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 58 dB(A) Q=2 50 44 40 38 36 34 33 32 31 30 26 22 Q=4 53 47 43 41 39 37 36 35 34 33 30 25 Q=8 56 50 46 44 42 40 39 38 37 36 33 28 Natdrift 56 dB(A) Q=2 48 42 38 36 34 32 31 30 29 28 24 20 Q=4 51 45 41 39 37 35 34 33 32 31 28 23 Q=8 54 48 44 42 40 38 37 36 35 34 31 26 WSB 10-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 63 dB(A) Q=2 55 49 45 43 41 39 38 37 36 35 31 27 Q=4 58 52 48 46 44 42 41 40 39 38 35 30 Q=8 61 55 51 49 47 45 44 43 42 41 38 33 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29 WSB 6-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 62 dB(A) Q=2 54 48 44 42 40 38 37 36 35 34 30 26 Q=4 57 51 47 45 43 41 40 39 38 37 34 29 Q=8 60 54 50 48 46 44 43 42 41 40 37 32 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29 WSB 8 -A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 58 dB(A) Q=2 50 44 40 38 36 34 33 32 31 30 26 22 Q=4 53 47 43 41 39 37 36 35 34 33 30 25 Q=8 56 50 46 44 42 40 39 38 37 36 33 28 Natdrift 56 dB(A) Q=2 48 42 38 36 34 32 31 30 29 28 24 20 Q=4 51 45 41 39 37 35 34 33 32 31 28 23 Q=8 54 48 44 42 40 38 37 36 35 34 31 26 WSB 10-A-RME-AI Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 6 m 7 m 8 m 9 m 10 m 15 m 25 m Max 63 dB(A) Q=2 55 49 45 43 41 39 38 37 36 35 31 27 Q=4 58 52 48 46 44 42 41 40 39 38 35 30 Q=8 61 55 51 49 47 45 44 43 42 41 38 33 Natdrift 59 dB(A) Q=2 51 45 41 39 37 35 34 33 32 31 27 23 Q=4 54 48 44 42 40 38 37 36 35 34 31 26 Q=8 57 51 47 45 43 41 40 39 38 37 34 29

Monoblok luft/vand varmepumpe 18 kW (WWP L 18 AD)

Monoblok luft/vand varmepumpe 25 kW (WWP L 25 A 2)

Monoblok luft/vand varmepumpe 40 kW (WWP L 40 AD-2)

Monoblok luft/vand varmepumpe 60 kW (WWP L 60 AD-2)

Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 46 40 36 34 32 26 22 20 18 16 15 14 Q=4 49 43 39 37 35 29 26 23 21 19 18 17 Q=8 52 46 42 40 38 32 29 26 24 22 21 20 Q=2 51 39 35 33 31 25 21 19 17 15 14 13 Q=4 48 42 38 36 34 28 25 22 20 18 17 16 Q=8 45 45 41 39 37 31 28 25 23 21 20 19 Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 65 53 49 47 45 39 35 33 31 29 28 27 Q=4 62 56 52 50 48 42 39 36 34 32 31 30 Q=8 59 59 55 53 51 45 42 39 37 35 34 33 Q=2 - - - - - - - - - - -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 62 56 52 50 48 42 38 36 34 32 31 30 Q=4 65 59 55 53 51 45 42 39 37 35 34 33 Q=8 68 62 58 56 54 48 45 42 40 38 37 36 Q=2 - - - - - - - - - - -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 66 60 56 54 52 46 42 40 38 36 35 34 Q=4 69 63 59 57 55 49 46 43 41 39 38 37 Q=8 72 66 62 60 58 52 49 46 44 42 41 40 Q=2 62 56 52 50 48 42 38 36 34 32 31 30 Q=4 65 59 55 53 51 45 42 39 37 35 34 33 Q=8 68 62 58 56 54 48 45 42 40 38 37 36 WWP L 18 AD Max 54 dB(A) Natdrift 53 dB(A) WWP L 25 A-2 Max 67 dB(A) Natdrift 67 dB(A) WWP L 40 A-2 Max 70 dB(A) Natdrift 70 dB(A) WWP L 60 AD-2 Max 74 dB(A) Natdrift 70 dB(A) Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 49 43 39 37 35 29 26 23 21 19 18 17 Q=8 40 38 32 29 26 24 22 21 20 Q=2 51 39 35 33 31 25 21 19 17 15 14 13 Q=4 48 42 38 36 34 28 25 22 20 18 17 16 Q=8 45 45 41 39 37 31 28 25 23 21 20 19 Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 65 53 49 47 45 39 35 33 31 29 28 27 62 56 52 50 48 42 39 36 34 32 31 30 Q=8 59 59 55 53 51 45 42 39 37 35 34 33 Q=2 - - - - - - - - - - -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 62 56 52 50 48 42 38 36 34 32 31 30 65 59 55 53 51 45 42 39 37 35 34 33 68 62 58 56 54 48 45 42 40 38 37 36 Q=2 - - - - - - - - - - -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 66 60 56 54 52 46 40 38 36 35 34 Q=4 69 63 59 57 55 49 46 43 41 39 38 37 Q=2 62 56 52 50 48 42 38 36 34 32 31 30 Q=4 65 59 55 53 51 45 42 39 37 35 34 33 Q=8 68 62 58 56 54 48 45 42 40 38 37 36 WWP L 18 AD Max Natdrift 53 dB(A) WWP L 25 A-2 Max Natdrift 67 dB(A) WWP L 40 A-2 Max Natdrift 70 dB(A) WWP L 60 AD-2 Max 74 dB(A) Natdrift 70 dB(A) Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 35 15 Q=4 48 42 38 36 34 28 25 22 20 18 17 16 45 45 41 39 37 31 28 25 23 21 20 19 Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 65 53 47 35 33 31 29 28 27 62 56 52 50 48 42 39 36 34 32 31 30 Q=8 59 59 55 53 51 45 42 39 37 35 34 33 -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 65 59 55 53 51 45 42 39 37 35 34 33 68 62 58 56 54 48 45 42 40 38 37 36 -Q=4 - - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 66 60 56 54 52 46 40 38 36 35 34 Q=2 62 56 52 50 42 36 34 32 31 30 Q=4 65 59 55 53 51 45 42 39 37 35 34 33 Q=8 68 62 58 56 54 48 45 42 40 38 37 36 WWP L 18 AD Max 54 dB(A) Natdrift 53 dB(A) WWP L 25 A-2 Max 67 dB(A) Natdrift 67 dB(A) WWP L 40 A-2 Max 70 dB(A) Natdrift 70 dB(A) WWP L 60 AD-2 Max 74 dB(A) Natdrift 70 dB(A) Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m Q=2 51 39 35 33 31 25 21 19 17 15 14 13 48 42 38 36 34 28 25 22 20 18 17 16 Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 65 53 49 47 45 39 35 33 31 29 28 27 Q=4 62 56 52 50 48 42 39 36 34 32 31 30 59 59 55 53 51 45 42 39 37 35 34 33 Q=2 - - - - - - - - - - -- - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 62 56 52 50 48 42 38 36 34 32 31 30 65 59 55 53 51 45 42 39 37 35 34 33 68 62 58 56 54 48 45 42 40 38 37 36 Q=2 - - - - - - - - - - -- - - - - - - - - - -Q=8 - - - - - - - - - - -Mode Lydeffekt Faktor 1 m 2 m 3 m 4 m 5 m 10 m 15 m 20 m 25 m 30 m 35 m 40 m 69 63 59 57 55 49 46 43 39 38 37 Q=2 62 56 52 50 48 42 38 36 34 32 31 30 Q=4 65 59 55 53 51 45 42 39 37 35 34 33 Q=8 68 62 58 56 54 48 45 42 40 38 37 36 WWP L 18 AD Max 54 dB(A) Natdrift 53 dB(A) WWP L 25 A-2 Max 67 dB(A) Natdrift 67 dB(A) WWP L 40 A-2 Max Natdrift WWP L 60 AD-2 Max Natdrift 70 dB(A)

Lyd fra flere lydkilder

Når man har flere lydkilder, eksempelvis i en varmepumpekaskade, er det vigtigt man husker at lydberegning er logaritmisk. Eksempelvis er 50 dB(A) + 50 dB = 53 dB(A), ikke 100 dB(A).

Hvis man aflæser nedenstående diagram kan man nemt regne sig frem til forøgelsen ud fra antallet af varmepumper. Både for varmepumper med samme lydniveau og ved forskelligt lydniveau.

Ved forskelligt lydniveau regner man differencen mellem de to varmepumper og går ind i det nederste diagram med denne, og aflæser ud fra kurven hvad forøgelsen vil være. Det er vigtigt at forstå at bare nogle få decibels forskel er en meget stor forskel i det opfattede lydtryk. Øger man antallet af decibel med 6 -10 dB vil lyden opfattes som dobbelt så høj.

10
15 0 10 5 0 5 10 15 20 15 0 10 5 0 5 10 15 20 Niveauforøgelse ∆ L [ dB ] Antal lydkilder [ n ] Eksempel 2 lydkilder hver med 80 dB Niveauforøgelse 3 dB Samlet niveau 83 dB Tilføjelse af lydkilder på samme niveau Niveauforøgelse ∆ L [ dB ] Niveauforskel L1- L2 [ dB ] Eksempel Lydkilde 1 80 dB Lydkilde 2 75 dB Niveauforskel 5 dB Niveauforøgelse 1 2 dB Samlet niveau 81 0 dB Tilføjelse af 2 lydkilder på forskellige niveauer 3 2 1

Kildehenvisning

Varme og klimateknik, Grundbog

3. udgave, 1 opslag, 2006

Udgiver: Danvak APS

ISBN: 87-982652-8-8

Styr på støjen, - En guide til installation af luft til vand varmepumper

Rapport udarbejdet for energistyrelsen, 2012

Udgiver: Grontmij

Bygningsreglementet 2018

2 udgave, februar 2020

Plan for varmepumper

Planlægning og installationshåndbog, 2020

Udgiver: Weishaupt

Tryksagsnummer: 83181901

11
weishauptenergi.dk 04/2023

Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.