Skip to main content

Cable Tray Systems Full Catalog

Page 4

Saving you Time, Saving you Money, Putting you First!

TABLE OF CONTENTS Introduction ------------------------------------------------------------------------------------------------------

4

Superior Tray Benefits ----------------------------------------------------------------------------------------

5

Ladder Tray -----------------------------------------------------------------------------------------------------

6

Hefty Tray --------------------------------------------------------------------------------------------------------

9

Cable Tray Fittings --------------------------------------------------------------------------------------------

12

Instrument Channel -------------------------------------------------------------------------------------------

22

Center Hung -----------------------------------------------------------------------------------------------------

27

Basket Tray -------------------------------------------------------------------------------------------------------

32

Special Tray -----------------------------------------------------------------------------------------------------

36

Support Material ------------------------------------------------------------------------------------------------ 42 Covers and Cover Fasteners -------------------------------------------------------------------------------

49

Accessories, Splices and Connectors --------------------------------------------------------------------

53

Superior Tray Quote Form ----------------------------------------------------------------------------------- 62 Company Contacts --------------------------------------------------------------------------------------------

For more information, please call 604.572.4419 or visit www.superiortray.com

64

page 3


Saving you Time, Saving you Money, Putting you First!

INTRODUCTION Medico Fabrication Inc. has been in business since 1996. But it wasn’t until the acquisition of M.P. Husky (B.C.) Ltd. in 2004, that we began using the trade name SUPERIOR TRAY. We have since become a major competitor in the Cable Tray and Cable Bus industry, as well as a leader in the manufacturing of EHouses/Kiosks and Custom Enclosures, while still maintaining our superiority and craftsmanship for custom fabrication. We offer you the ability to purchase directly from us, no need to go through a distributor, saving any markup cost and any questions you may have are answered quickly and more efficiently. We offer shorter lead times than any other manufacturer. We take great pride in our ability to help build client success with products that are done right, on budget and on time. You can be assured Superior Tray will exceed your expectations with our state of the art CNC equipment, automation production, robotics, and our highly trained team of technical staff that will take a blue print, sketch, or a simple thought and turn your concept into the perfect product, whether it is a Cable Tray System, Bus Duct, Cable Bus Package, Modular Bus, Wireways, Electrical Enclosures, or E-houses/Kiosks. We have also designed and developed an Integrated Walkway and Integrated Service Chaseway System. Superior Tray is a CSA and UL certified Cable Tray/Cable Support System. Medico Fabrication Inc. manufactures custom designed top quality heavy duty cable tray systems which are reliable, robust and cost effective. They are excellent in quality, performance and durability. Superior Tray manufactures six (6) types of Cable Tray Systems; namely, Ladder Tray, Hefty Tray, Instrument Channel, Center Hung, Basket Tray and Special Trays. 1. Ladder Tray (Flanges In) This tray with flanges in is best for supporting instrumentation, power and control cables of various diameters. It is particularly used by power plants, pulp and paper mills, petrochemical plants and industrial construction that require reliability and may have limited space available. These trays are manufactured from aluminum, mill galvanized steel, HDGAF steel or stainless steel based on project needs. Powder coat finishes are also available.

2. Hefty Tray (Flanges Out) This tray with flanges out is designed for multiple large cables and is frequently installed at paper mills, power plants and other industrial plants. The design has the rungs welded to the outside of the rails to further enhance its structural integrity while reducing side rail rotation. These trays are manufactured either from aluminum, mill galvanized steel, HDGAF steel or stainless steel based on project requirements. Powder coat finishes are also available. 3. Instrument Channel Instrument Channel is a one-piece channel section, typically used to carry instrumentation, control, data communication, computer or telephone cable. The channel section comes with ventilated or solid bottom. The tray is designed to carry both single power cable and multiple circuit cables. 4. Center Hung This tray has been designed to simplify the support and routing of power and telecom/teledata cabling. Reduced support requirements make installation easier, providing substantial savings on both cost and installation time. On a center hung tray, cables may run on both sides. 5. Basket Tray This is a wire mesh style cable tray designed for the data and communications cabling industry, provides the additional support that sensitive cables and fiber optics require to prevent damage by using basket tray’s welded mesh. 6. Special Trays The design and manufacturing team of Superior Tray have developed several custom designed unique trays for our customers’ specific project needs. These special trays have been classified into five categories: a) b) c) d) e)

EMI Tray or EMI Enclosure System EAM Tray (Integrated Wireway System) AI 7 Tray Telco Tray Universal Tray

For more information, please call 604.572.4419 or visit www.superiortray.com

page 4


Saving you Time, Saving you Money, Putting you First!

SUPERIOR TRAY BENEFITS The benefits of Superior Tray Cable Tray Systems vary depending on the type of tray required.

Where the power cables enter or exit conduit, the conduit to cable tray clamps may be installed upright or inverted to terminate conduits on the top or bottom of the cable tray side rail.

The Ladder Tray is used in approximately 75% of the cable tray wiring system installations, due to its many desirable features:

•

Moisture cannot accumulate in ladder trays.

•

•

If cable trays are being installed where working space is a problem, hand access through the cable tray bottom may help to facilitate the installation of small diameter cables such as: control instrumentation, signal, etc.

•

•

A Ladder Tray without covers permits the maximum free flow of air across the cables. This allows the heat produced in the cable’s conductor to effectively dissipate. Under such conditions, the conductor insulation in the cables of a properly designed cable tray system will not exceed its maximum operating temperature. The cables will not prematurely deteriorate due to excessive operating temperatures. The rungs of the Ladder Tray provide convenient anchors to tie down the cables in the non-horizontal cable tray runs or where the positions of the cable tray must be maintained in the horizontal cable tray runs. This is necessary for single conductor cable installations, because under fault conditions (short circuit), the magnetic forces produced by the fault current will move the single conductor cables from the cable tray if they are not securely anchored to the tray.

Hefty Tray benefits are similar to ladder tray with the major difference is the tray’s outward flanges that is required at many power cable installation project for external rigid attachment. It is most suitable for multiple large cables installation. Center Hung Tray is used to support and route power and telecom/teledata cables. The simple design saves time and has less support requirements. This saves 50% in material cost compared to standard cable trays. On the other hand, the basket tray is designed to provide additional support to prevent damage of the sensitive and fiber optic cables for the data and communications cabling industry.

Power cables may exit or enter the ladder trays through the top or the bottom of the cable tray.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 5


Saving you Time, Saving you Money, Putting you First!

LADDER TRAY TECHNICAL DATA Depth

3 3/8 inches, 4 inches, 4 1/2 inches, 6 inches and 6 1/4 inches.

Length

10 feet (120″) standard. Also available in 20 feet (240″).

Widths (inside)

6, 9, 12, 18, 24, 30 and 36 inches.

Rung Spacing

6, 9 or 12 inches.

Materials

Aluminum Alloy 6061-T6 or 6063-T6, Stainless Steel, Mill Galvanized or HDGAF Steel. Painted, epoxy and other finishes are also available.

Fittings

12, 24 or 36 inch radii. See the Fittings Section of this catalog.

Splice Plates

Straight sections and fittings are supplied with splice connectors and hardware.

CATALOG NUMBER

A9JA–24–120 Material

Tray Type Rung (Prefix) Space

Length in Inches

Width

Materials: A = Aluminum, P = Mill Galvanized, S = HDGAF Steel, 4 = 304 Stainless, 6 = 316 Stainless

BOTTOM DIMENSIONS 3.65" .75"

.75" .50"

2.12"

2.12"

.75"

.75"

.50" .78"

For 30" or 36" wide for H, J, JC,M, MD All widths for YD, XB, XC and CD

For 24" wide or less for H, J, JC,M, MD Straight Only

.50" (Heavy rungs available)

HOW TO ORDER Prefix

Prefix – Width – Length

Splices

A( )JA, A( )JB, A( )YA

–(

) – 120

ASP-H2

A( )MB, A( )X, A( )X1

–(

) – 120

ASP-M2

S( )H, S( )J, S( )JC, S( )YD

–(

) – 120

SSP-H2

S( )M, S( )MD, S( )XC, S( )XD

–(

) – 120

SSP-H2

Note: Insert Rung Space in Prefix, and then insert Width. All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 6


Saving you Time, Saving you Money, Putting you First!

LADDER TRAY A9JA NEMA 12A exceeds CSA C1 use ALJA fittings

Span (ft) Width

0.75" 3.91"

4.50" W

A9JB NEMA 12B exceeds CSA C1 use ALJB fittings

0.75" 3.91"

W

A9YA NEMA 20A, 16B, 12C CSA D1 use ALYA fittings

1.48"

W

A9X NEMA 20B, 16C, 12C CSA E use ALX fittings

1.75"

Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

Defl 1.63 1.63 1.63 1.63 1.63 1.63 1.54

14 Load 102 102 102 102 102 102 102

Defl 0.92 0.92 0.92 0.87 0.69 0.58

14 Load 153 153 153 153 153 131

8 Load 135 135 135 135 135 135 131

Defl 0.61 0.61 0.61 0.61 0.61 0.61 0.59

10 Load 86 86 86 86 86 86 86

Defl 0.96 0.96 0.96 0.96 0.96 0.96 0.96

4 Load 696 523 393 262 196 157 131

Defl 0.32 0.32 0.32 0.28 0.21 0.17 0.14

8 Load 169 169 169 169 169 157 131

Defl 0.57 0.57 0.57 0.57 0.57 0.53 0.14

10 Load 108 108 108 108 108 108 108

Defl 0.89 0.89 0.89 0.89 0.89 0.89 0.89

12 Load 139 139 139 139 139 139 131

Defl 2.22 2.22 2.22 2.22 2.22 2.22 2.22

16 Load 78 78 78 78 78 78 78

Defl 2.90 2.90 2.90 2.90 2.90 2.90 2.90

18 Load 50 50 50 50 50 50 50

Defl 4.53 4.53 4.53 4.53 4.53 4.53 4.53

Defl 1.64 1.64 1.64 1.64 1.64 1.64

20 Load 75 75 75 75 75 75

Defl 2.56 2.56 2.56 2.56 2.56 2.56

Span (ft) Width

5.41"

1.75"

Width

5.41"

W

6″ 9″ 12″ 18″ 24″ 30″ 36″

9″ 12″ 18″ 24″ 30″ 36″

W

6.0"

Defl 0.14 0.11 0.08 0.05 0.04 0.03 0.03

6 Load 300 300 300 262 196 157 131

Defl 0.34 0.34 0.34 0.34 0.28 0.22 0.19

Span (ft)

3.89"

4.50"

A9X1 NEMA 20C exceeds CSA E use ALX fittings

Defl 0.15 0.15 0.11 0.07 0.05 0.04 0.04

6 Load 240 240 240 240 196 157 131

Span (ft) Width

4.50"

6.0"

6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 540 523 393 262 196 157 131

9″ 12″ 18″ 24″ 30″ 36″

12 Load 208 208 208 196 157 131

Defl 1.26 1.26 1.26 1.26 1.26 1.08

16 Load 117 117 117 117 117 117

Span (ft) 12 14 16 20 Load Defl Load Defl Load Defl Load Defl 277 1.12 204 1.53 156 1.99 100 3.13 277 1.12 204 1.53 156 1.99 100 3.13 262 1.06 204 1.53 156 1.99 100 3.13 196 0.79 196 1.47 156 1.99 100 3.13 157 0.63 157 1.18 156 1.99 100 3.13 131 0.53 131 0.98 131 1.67 100 3.13 Note: The unit of Load is lb and Deflection is inch.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 7


Saving you Time, Saving you Money, Putting you First!

LADDER TRAY S9H & P9H NEMA 12A exceeds CSA C1 use SLH or PLH fittings

Span (ft) Width

0.75" 2.82"

3.38" W S9J & P9J NEMA 12B exceeds CSA C1 use SLJ or PLJ fittings

0.75"

W S9JC & P9JC NEMA 12C CSA D1-3M use SLJC or PLJC fittings

0.75"

0.75"

W S9XB & P9XB NEMA 20B, 16C, 12C CSA E use SLXB or PLXB fittings

6″ 9″ 12″ 18″ 24″ 30″ 36″

Width

1.75" 5.69"

6.25"

6″ 9″ 12″ 18″ 24″ 30″ 36″

Width

5.44"

6.0"

Defl 0.06 0.04 0.03 0.02 0.02 0.04 0.03

6 Load 300 272 204 136 102 229 191

Defl 0.04 0.03 0.02 0.01 0.01 0.02 0.02

6 Load 408 272 204 136 102 229 191

Defl 0.02 0.01 0.01 0.01 0.01 0.01 0.01

6 Load 346 272 204 136 102 229 191

Defl 0.32 0.31 0.23 0.15 0.12 0.26 0.22

8 Load 157 157 157 136 102 157 157

Defl 0.57 0.57 0.57 0.49 0.37 0.57 0.57

10 Load 101 101 101 101 101 101 101

Defl 0.88 0.88 0.88 0.88 0.88 0.88 0.88

4 Load 408 272 204 136 102 229 191

Defl 0.22 0.20 0.15 0.10 0.08 0.17 0.14

8 Load 169 169 169 136 102 169 169

Defl 0.40 0.40 0.40 0.32 0.24 0.40 0.40

10 Load 108 108 108 108 102 108 108

Defl 0.62 0.62 0.62 0.62 0.59 0.62 0.62

Defl 0.41 0.41 0.34 0.22 0.17 0.38 0.32

10 Load 158 158 158 136 102 158 158

Defl 0.65 0.65 0.65 0.56 0.42 0.65 0.65

Defl 0.17 0.17 0.17 0.12 0.09 0.17 0.17

10 Load 125 125 125 108 102 125 125

Defl 0.27 0.27 0.27 0.62 0.59 0.27 0.27

Span (ft)

W S9M & P9M NEMA 12B CSA D1 on 3M use SLM or PLM fittings

6″ 9″ 12″ 18″ 24″ 30″ 36″

Width

3.94"

4.50"

Defl 0.09 0.06 0.05 0.03 0.02 0.05 0.04

6 Load 280 272 204 136 102 229 191

Span (ft) Width

3.44"

4.0"

6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 408 272 204 136 102 229 191

9″ 12″ 18″ 24″ 30″ 36″

4 Load 408 272 204 136 102 229 191

4 Load 408 272 204 136 102 229 191

Defl 0.21 0.14 0.11 0.07 0.06 0.12 0.10

8 Load 248 248 204 136 102 229 191

Span (ft) Defl 0.10 0.08 0.06 0.04 0.03 0.07 0.06

8 Load 195 195 195 136 102 195 191

Span (ft) 12 14 16 20 Load Defl Load Defl Load Defl Load 236 0.71 173 0.97 133 1.27 85 236 0.71 173 0.97 133 1.27 85 236 0.71 173 0.97 133 1.27 85 236 0.71 173 0.97 133 1.27 85 229 0.69 173 0.97 133 1.27 85 191 0.57 173 0.97 133 1.27 85 Note: The unit of Load is lb and Deflection is inch.

Defl 1.99 1.99 1.99 1.99 1.99 1.99

W For more information, please call 604.572.4419 or visit www.superiortray.com

page 8


Saving you Time, Saving you Money, Putting you First!

HEFTY TRAY TECHNICAL DATA Depth

4 inches, 4 1/2 inches, and 6 inches.

Length

10 feet (120″) standard. Also available in 20 feet (240″) except in steel.

Widths (inside)

6, 9, 12, 18, 24, 30 and 36 inches.

Rung Spacing

9, 12 or 18 inches.

Materials

Aluminum Alloy 6061-T6 or 6063-T6, Mill Galvanized or HDGAF Steel. Painted, epoxy finishes are also available.

Fittings

12, 24 or 36 inch radii. See the fittings section of this catalog.

Splice Plates

Straight sections and fittings are supplied with splice connectors and hardware.

CATALOG NUMBER

A12BB–24–120 Material

Rung Space

Tray Type (Prefix)

Length in Inches

Width

Materials: A = Aluminum, P = Mill Galvanized, S = HDGAF Steel, 4 = 304 Stainless, 6 = 316 Stainless

RUNG SECTION & DIMENSIONS 1 1/8"

3/4"

1/16"

1/2"

HOW TO ORDER Prefix

Prefix – Width – Length

Splices

A( )BA, A( )BB, A( )CA

–(

) – 120

ASP-H2

A( )E, A( )E1

–(

) – 120

ASP-M2

S( )B, S( )BC, S( )P, S( )PD

–(

) – 120

SSP-H2

Note: Insert Rung Space in Prefix, and then insert Width. All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 9


Saving you Time, Saving you Money, Putting you First!

HEFTY TRAY A9BA NEMA 12A CSA C1 use ALBA fittings

Width

0.75" 4.50"

W

Width

A9BB NEMA 12B exceeds CSA C1 use ALBB fittings

0.75" 4.50"

W A9CA NEMA 20A, 16B, 12C CSA D1 use ALCA fittings

1.50"

1.75" 6.0"

W A9E1 NEMA 20C, 16C, 12C exceeds CSA E use ALE fittings

1.75" 6.0"

W

4 Load 675 675 655 435 327 262 218

Defl 0.15 0.15 0.15 0.12 0.09 0.07 0.06

6 Load 240 240 240 240 240 240 218

Defl 0.14 0.14 0.14 0.09 0.07 0.05 0.05

6 Load 300 300 300 300 300 262 218

Defl 1.63 1.63 1.63 1.63 1.63 1.63 1.63

14 Load 102 102 102 102 102 102 102

Defl 0.92 0.92 0.92 0.92 0.92 0.92 0.92

14 Load 153 153 153 153 153 153 153

Span (ft) Defl 0.34 0.34 0.34 0.34 0.34 0.34 0.31

8 Load 135 135 135 135 135 135 135

Defl 0.61 0.61 0.61 0.61 0.61 0.61 0.61

10 Load 86 86 86 86 86 86 86

Defl 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Defl 0.57 0.57 0.57 0.57 0.57 0.57 0.57

10 Load 108 108 108 108 108 108 108

Defl 0.89 0.89 0.89 0.89 0.89 0.89 0.89

Defl 2.90 2.90 2.90 2.90 2.90 2.90 2.90

20 Load 50 50 50 50 50 50 50

Defl 4.53 4.53 4.53 4.53 4.53 4.53 4.53

Defl 1.64 1.64 1.64 1.64 1.64 1.64 1.64

20 Load 75 75 75 75 75 75 75

Defl 2.56 2.56 2.56 2.56 2.56 2.56 2.56

Span (ft) Defl 0.32 0.32 0.32 0.32 0.32 0.28 0.23

8 Load 169 169 169 169 169 169 169

Span (ft)

W NEMA 20B, 16C, 12C CSA E use ALE fittings

6″ 9″ 12″ 18″ 24″ 30″ 36″

Width

4.50"

A9E

6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 540 540 540 435 327 262 218

6″ 9″ 12″ 18″ 24″ 30″ 36″

12 Load 139 139 139 139 139 139 139

Defl 2.22 2.22 2.22 2.22 2.22 2.22 2.22

16 Load 78 78 78 78 78 78 78

Span (ft) Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

12 Load 208 208 208 208 208 208 208

Defl 1.26 1.26 1.26 1.26 1.26 1.26 1.26

16 Load 117 117 117 117 117 117 117

Span (ft) 12 14 16 20 Load Defl Load Defl Load Defl Load 277 1.12 204 1.53 156 1.99 123 277 1.12 204 1.53 156 1.99 123 277 1.12 204 1.53 156 1.99 123 277 1.12 204 1.53 156 1.99 123 277 1.12 204 1.53 156 1.99 123 262 1.06 204 1.53 156 1.99 123 218 0.88 204 1.53 156 1.99 123 Note: The unit of Load is lb and Deflection is inch.

For more information, please call 604.572.4419 or visit www.superiortray.com

Defl 2.56 1.99 1.99 1.99 1.99 1.99 1.99

page 10


Saving you Time, Saving you Money, Putting you First!

HEFTY TRAY S9B

NEMA 12B exceeds CSA C1 use SLB fittings

0.75" 4"

W

S9BC NEMA 12C exceeds CSA C1 use SLBC fittings

0.75"

W NEMA 12B CSA D1 on 3m use SLP fittings

0.75" 6.0"

W S9PD NEMA 12C CSA D1 on 3m use SLPD fittings

0.75" 6.0"

W

6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 675 675 675 500 375 300 250

Defl 0.10 0.10 0.10 0.07 0.06 0.04 0.04

6 Load 300 300 300 300 300 300 250

Defl 0.10 0.10 0.08 0.05 0.04 0.03 0.02

6 Load 440 440 440 440 375 300 250

Defl 0.04 0.04 0.04 0.03 0.02 0.02 0.01

6 Load 351 351 351 351 351 300 250

Span (ft) Defl 0.24 0.24 0.24 0.24 0.24 0.24 0.10

8 Load 169 169 169 169 169 169 169

Defl 0.42 0.42 0.42 0.42 0.42 0.42 0.42

10 Load 108 108 108 108 108 108 108

Defl 0.65 0.65 0.65 0.65 0.65 0.65 0.65

Defl 0.41 0.41 0.41 0.41 0.41 0.41 0.41

10 Load 158 158 158 158 158 158 158

Defl 0.65 0.65 0.65 0.65 0.65 0.65 0.65

Defl 0.17 0.17 0.17 0.17 0.17 0.17 0.17

10 Load 125 125 125 125 125 125 125

Defl 0.27 0.27 0.27 0.27 0.27 0.27 0.27

Span (ft)

4.50"

S9P

Width

Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 990 990 750 500 375 300 250

Defl 0.23 0.23 0.23 0.23 0.20 0.16 0.13

8 Load 248 248 248 248 248 248 248

Span (ft) Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

Width 6″ 9″ 12″ 18″ 24″ 30″ 36″

4 Load 791 791 750 500 375 300 250

Defl 0.09 0.09 0.09 0.09 0.09 0.08 0.06

8 Load 196 196 196 196 196 196 196

Span (ft) 4 6 8 10 Load Defl Load Defl Load Defl Load 1116 0.05 496 0.12 279 0.22 179 1000 0.04 496 0.12 279 0.22 179 750 0.03 496 0.12 279 0.22 179 500 0.02 496 0.12 279 0.22 179 375 0.02 375 0.09 279 0.22 179 300 0.01 300 0.07 279 0.22 179 250 0.01 250 0.06 250 0.20 179 Note: The unit of Load is lb and Deflection is inch.

For more information, please call 604.572.4419 or visit www.superiortray.com

Defl 0.35 0.35 0.35 0.35 0.35 0.35 0.35

page 11


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS ORDERING INFORMATION FOR FITTINGS CATALOG NUMBER

ALJA–24H90–12 Tray Type (Prefix)

Material

Width

Tray Fitting Prefix

Degree Bend

Fitting Radius

Bend Type (Horizontal)

Materials: A = Aluminum, P = Mill Galvanized, S = HDGAF Steel, 4 = 304 Stainless, 6 = 316 Stainless

FITTING PREFIX Aluminum Tray Prefix A( A( A( A( A( A(

Fitting Prefix

)JA )JB )YA )X )X1 )X1M

Steel Tray Prefix

ALJA ALJB ALYA ALX ALX1 ALX1M

S( S( S( S( S( S( S( S(

)H )J )JC )YD )M )XB )XC )XD

Fitting Prefix

Steel Tray Prefix

SLH SLJ SLJC SLYD SLM SLXB SLXC SLXD

P( P( P( P( P( P( P( P(

)H )J )JC )YD )M )XB )XC )XD

Fitting Prefix PLH PLJ PLJC PLYD PLM PLXB PLXC PLXD

VERTICAL TEES Width

Radius

36

36 24 12

30

24

Depth

A

18

LB

12

R C 9

Depth X2 6

36 24 12 36 24 12 36 24 12 36 24 12 36 24 12 36 24 12

Catalog No. Prefix Basic Add Prefix ▼ ▼ ▼ ▼ ▼ ▼

36VT-36 36VT-24 36VT-12 30VT-36 30VT-24 30VT-12 24VT-36 24VT-24 24VT-12 18VT-36 18VT-24 18VT-12 12VT-36 12VT-24 12VT-12 9VT-36 9VT-24 9VT-12 6VT-36 6VT-24 6VT-12

R

A

B

D

34 22 11

75 51 30

37 25 15

36 24 13

34 22 11

77 53 31

38 26 15

36 24 13

H

L 3-

56 38 21 4″ Deep 57 38 21

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 78 39 22 54 27 16 32 11

36 24 14

M,MB,MD,X,X1,P,PB,PD,E,E1 34 40 81 22 57 28 35 11 17

37 25 14

XB,XC,XD,EB,EC,ED 34 81 22 57 11 36

37 25 15

4-

″ Deep 57 38 22 6″ Deep 58 40 23

640 28 18

″ Deep

″ Deep 59 40 23

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 12


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS VERTICAL BENDS 30° VERTICAL OUTSIDE BEND Width

Radius

36

36 24 12

30

24

A

18

D D

Depth

9

B L

R

12

6

36 24 12 36 24 12 36 24 12 36 24 12 36 24 12 36 24 12

Catalog No. Prefix Basic Add Prefix ▼ ▼ ▼ ▼ ▼ ▼

R

A

B

D

34 22 11

18 12 6

4 3 1

9 6 3

34 22 11

18 12 6

4 3 1

9 6 3

H

36VO30-36 36VO30-24 36VO30-12

L 3-

″ Deep 18 12 7

30VO30-36 30VO30-24 30VO30-12 24VO30-36 24VO30-24 24VO30-12 18VO30-36 18VO30-24 18VO30-12

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 18 4 22 12 3 11 7 1

9 6 3

12VO30-36 12VO30-24 12VO30-12

M,MB,MD,X,X1,P,PB,PD,E,E1 34 18 5 22 12 3 11 7 2

10 6 4

XB,XC,XD,EB,EC,ED 34 18 22 12 11 7

5 3 2

10 6 4

19 13 7

L

9VO30-36 9VO30-24 9VO30-12 6VO30-36 6VO30-24 6VO30-12

4″ Deep 19 12 7 4-

″ Deep 19 12 7 6″ Deep 19 13 7

6-

″ Deep

45° VERTICAL OUTSIDE BEND

Width

Radius

36

36 24 12

30

24 A D

18 D

Depth

12 B

9 R

L

6

36 24 12 36 24 12 36 24 12 36 24 12 36 24 12 36 24 12

Catalog No. Prefix Basic Add Prefix ▼ ▼ ▼ ▼ ▼ ▼

12VO45-36 12VO45-24 12VO45-12 9VO45-36 9VO45-24 9VO45-12 6VO45-36 6VO45-24 6VO45-12

A

B

D

34 22 11

25 17 9

10 7 4

15 10 5

34 22 11

25 17 9

10 7 4

15 10 5

H

36VO45-36 36VO45-24 36VO45-12 30VO45-36 30VO45-24 30VO45-12 24VO45-36 24VO45-24 24VO45-12 18VO45-36 18VO45-24 18VO45-12

R

3-

28 19 10 4″ Deep 28 19 10

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 10 26 22 17 7 4 11 10

15 10 5

M,MB,MD,X,X1,P,PB,PD,E,E1 34 26 11 7 22 18 10 4 11

15 10 6

XB,XC,XD,EB,EC,ED 34 26 22 18 11 10

15 10 6

4-

″ Deep 28 19 11 6″ Deep 29 20 11

611 7 4

″ Deep

″ Deep 29 20 11

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 13


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS 60° VERTICAL OUTSIDE BEND Radius

36

36 24 12

Add Prefix

36VO60-36 36VO60-24 36VO60-12

30

36 24 12

▼

30VO60-36 30VO60-24 30VO60-12

36 24 12

▼

18

36 24 12

▼

18VO60-36 18VO60-24 18VO60-12

12

36 24 12

▼

12VO60-36 12VO60-24 12VO60-12

9

36 24 12

▼

9VO60-36 9VO60-24 9VO60-12

6

36 24 12

▼

6VO60-36 6VO60-24 6VO60-12

24

A D Depth

D

B

R L

Catalog No. Prefix Basic

Width

24VO60-36 24VO60-24 24VO60-12

R

A

B

D

H

L 3-

34 22 11

31 20 11

18 12 6

20 13 7

34 22 11

31 21 12

18 12 6

21 14 8

37 25 14 4″ Deep 38 25 14

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

31 21 12

18 12 7

421 14 8

32 22 12

6″ Deep 39 26 15

21 14 8

18 12 7

XB,XC,XD,EB,EC,ED 34 22 11

618 12 7

32 22 13

″ Deep 38 25 14

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

″ Deep

21 14 8

″ Deep 39 26 15

90° VERTICAL OUTSIDE BEND Radius

36

36 24 12

Add Prefix

36VO90-36 36VO90-24 36VO90-12

30

36 24 12

▼

30VO90-36 30VO90-24 30VO90-12

36 24 12

▼

24VO90-36 24VO90-24 24VO90-12

18

36 24 12

▼

18VO90-36 18VO90-24 18VO90-12

12

36 24 12

▼

12VO90-36 12VO90-24 12VO90-12

9

36 24 12

▼

9VO90-36 9VO90-24 9VO90-12

24

A Depth B

R

6

L

Catalog No. Prefix Basic

Width

36 24 12

▼

6VO90-36 6VO90-24 6VO90-12

R

A

B

34 22 11

36 24 13

36 24 13

56 38 21

34 22 11

36 24 13

36 24 13

57 38 21

H

L 3-

″ Deep

4″ Deep

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

36 24 14

36 24 14

457 38 22

6″ Deep

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

37 25 14

37 25 14

XB,XC,XD,EB,EC,ED 34 22 11

37 25 15

58 40 23 6-

37 25 15

″ Deep

″ Deep

59 40 23

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 14


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS 30° VERTICAL INSIDE BEND Radius

36

36 24 12

Add Prefix

36VI30-36 36VI30-24 36VI30-12

30

36 24 12

▼

30VI30-36 30VI30-24 30VI30-12

36 24 12

▼

24VI30-36 24VI30-24 24VI30-12

24

L

R

B

Depth

D D

Catalog No. Prefix Basic

Width

18

36 24 12

▼

18VI30-36 18VI30-24 18VI30-12

12

36 24 12

▼

12VI30-36 12VI30-24 12VI30-12

9

36 24 12

▼

9VI30-36 9VI30-24 9VI30-12

A 6

36 24 12

▼

R

A

B

D

34 22 11

18 12 6

4 3 1

9 6 3

34 22 11

18 12 6

4 3 1

9 6 3

H

L 3-

18 12 7 4″ Deep 19 12 7

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

18 12 7

4 3 1

49 6 3

18 12 7

5 3 2

10 6 4

XB,XC,XD,EB,EC,ED

6″ Deep 19 13 7

6VI30-36 6VI30-24 6VI30-12

6-

34 22 11

18 12 7

5 3 2

10 6 4

R

A

B

D

″ Deep 19 12 7

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

″ Deep

″ Deep 19 13 7

45° VERTICAL INSIDE BEND Radius

36

36 24 12

Add Prefix

36VI45-36 36VI45-24 36VI45-12

30

36 24 12

▼

30VI45-36 30VI45-24 30VI45-12

24

36 24 12

▼

24VI45-36 24VI45-24 24VI45-12

18

36 24 12

▼

18VI45-36 18VI45-24 18VI45-12

12

36 24 12

▼

12VI45-36 12VI45-24 12VI45-12

9

36 24 12

▼

9VI45-36 9VI45-24 9VI45-12

L R B Depth

D D

Catalog No. Prefix Basic

Width

A

6

36 24 12

▼

6VI45-36 6VI45-24 6VI45-12

H

L 3-

34 22 11

25 17 9

10 7 4

15 10 5

34 22 11

25 17 9

10 7 4

15 10 5

28 19 10 4″ Deep 28 19 10

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

26 17 10

10 7 4

4-

26 18 10

6″ Deep

11 7 4

15 10 6

11 7 4

15 10 6

XB,XC,XD,EB,EC,ED 34 22 11

26 18 10

″ Deep 28 19 11

15 10 5

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

″ Deep

29 20 11 6-

″ Deep 29 20 11

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 15


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS 60° VERTICAL INSIDE BEND Width

Radius

36

36 24 12

Add Prefix

36VI60-36 36VI60-24 36VI60-12

30

36 24 12

▼

30VI60-36 30VI60-24 30VI60-12

24

36 24 12

▼

24VI60-36 24VI60-24 24VI60-12

18

36 24 12

▼

18VI60-36 18VI60-24 18VI60-12

12

36 24 12

▼

12VI60-36 12VI60-24 12VI60-12

9

36 24 12

▼

9VI60-36 9VI60-24 9VI60-12

36 24 12

▼

6VI60-36 6VI60-24 6VI60-12

L R B

D

Depth D

Catalog No. Prefix Basic

6

A

R

A

B

D

34 22 11

31 20 11

18 12 6

20 13 7

H

L 3-

37 25 14 4″ Deep 38 25 14

J,B 34 22 11

18 12 6

31 21 12

21 14 8

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

31 21 12

18 12 7

421 14 8

32 22 12

6″ Deep 39 26 15

21 14 8

18 12 7

XB,XC,XD,EB,EC,ED 34 22 11

618 12 7

32 22 13

″ Deep 38 25 14

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

″ Deep

21 14 8

″ Deep 39 26 15

90° VERTICAL INSIDE BEND Radius

36

36 24 12

Add Prefix

36VI90-36 36VI90-24 36VI90-12

30

36 24 12

▼

30VI90-36 30VI90-24 30VI90-12

36 24 12

▼

18

36 24 12

▼

18VI90-36 18VI90-24 18VI90-12

12

36 24 12

▼

12VI90-36 12VI90-24 12VI90-12

9

36 24 12

▼

9VI90-36 9VI90-24 9VI90-12

24

L

R

B

Catalog No. Prefix Basic

Width

Depth 6

36 24 12

▼

24VI90-36 24VI90-24 24VI90-12

6VI90-36 6VI90-24 6VI90-12

R

A

B

34 22 11

36 24 13

36 24 13

56 38 21

34 22 11

36 24 13

36 24 13

57 38 21

H

L 3-

″ Deep

4″ Deep

J,B

JA,JB,JC,BA,BB,BC,YA,CA,YD,CD 34 22 11

36 24 14

36 24 14

457 38 22

6″ Deep

M,MB,MD,X,X1,P,PB,PD,E,E1 34 22 11

37 25 14

37 25 14

XB,XC,XD,EB,EC,ED 34 22 11

37 25 15

58 40 23 6-

37 25 15

″ Deep

″ Deep

59 40 23

Note: All dimensions are in inches

A For more information, please call 604.572.4419 or visit www.superiortray.com

page 16


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS HORIZONTAL CROSS AND TEE HORIZONTAL CROSS

A

Width

Radius

36

36 24 12

30

A

B

C

Add Prefix

36X-36 36X-24 36X-12

54 42 30

108 84 60

54 42 30

36 24 12

▼

30X-36 30X-24 30X-12

51 39 27

102 78 54

51 39 27

24

36 24 12

▼

24X-36 24X-24 24X-12

48 36 24

96 72 48

48 36 24

18

36 24 12

▼

18X-36 18X-24 18X-12

45 33 21

90 66 42

45 33 21

12

36 24 12

▼

12X-36 12X-24 12X-12

42 30 18

84 60 36

42 30 18

9

36 24 12

▼

9X-36 9X-24 9X-12

40 28 16

81 57 33

40 28 16

6

36 24 12

▼

6X-36 6X-24 6X-12

39 27 15

78 54 30

39 27 15

B

W

C R

W L

HORIZONTAL TEE Radius

A

B

C

D

36

36 24 12

Add Prefix

36T-36 36T-24 36T-12

54 42 30

108 84 60

54 42 30

72 60 48

30

36 24 12

▼

30T-36 30T-24 30T-12

51 39 27

102 78 54

51 39 27

66 54 42

24

36 24 12

▼

24T-36 24T-24 24T-12

48 36 24

96 72 48

48 36 24

60 48 36

18

36 24 12

▼

18T-36 18T-24 18T-12

45 33 21

90 66 42

45 33 21

54 42 30

12

36 24 12

▼

12T-36 12T-24 12T-12

42 30 18

84 60 36

42 30 18

48 36 24

9

36 24 12

▼

9T-36 9T-24 9T-12

40 28 16

81 57 33

40 28 16

45 33 21

6

36 24 12

▼

6T-36 6T-24 6T-12

39 27 15

78 54 30

39 27 15

42 30 18

W D

C R

W

Catalog No. Prefix Basic

Width

B A

Catalog No. Prefix Basic

L

L 84 66 47 80 61 42 75 56 37 70 51 33 66 47 28 63 44 25 61 42 23

L 84 66 47 80 61 42 75 56 37 70 51 33 66 47 28 63 44 25 61 42 23

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 17


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS HORIZONTAL BENDS 30° HORIZONTAL BEND

D

A

B

D

Radius

A

B

C

D

L

36

36 24 12

Add Prefix

36H30-36 36H30-24 36H30-12

7 5 4

27 21 15

54 42 30

14 11 8

28 22 15

30

36 24 12

▼

30H30-36 30H30-24 30H30-12

6 5 3

25 19 13

51 39 27

13 10 7

26 20 14

24

36 24 12

▼

24H30-36 24H30-24 24H30-12

6 4 3

24 18 12

48 36 24

12 9 6

25 18 12

18

36 24 12

▼

18H30-36 18H30-24 18H30-12

6 4 2

22 16 10

45 33 21

12 8 5

23 17 11

12

36 24 12

▼

12H30-36 12H30-24 12H30-12

5 4 2

21 15 9

42 30 18

11 8 4

22 15 9

9

36 24 12

▼

9H30-36 9H30-24 9H30-12

5 3 2

20 14 8

40 28 16

10 7 4

21 14 8

6

36 24 12

▼

6H30-36 6H30-24 6H30-12

5 3 2

19 13 7

39 27 15

10 7 4

20 14 7

Width

Radius

A

B

C

D

L

36

36 24 12

Add Prefix

36H45-36 36H45-24 36H45-12

15 12 8

38 29 21

54 42 30

20 17 12

42 33 23

30

36 24 12

▼

30H45-36 30H45-24 30H45-12

14 11 7

36 27 19

51 39 27

21 16 11

40 30 21

24

36 24 12

▼

24H45-36 24H45-24 24H45-12

14 10 7

33 25 17

48 36 24

19 14 9

37 28 18

18

36 24 12

▼

18H45-36 18H45-24 18H45-12

13 9 6

31 23 14

45 33 21

18 13 8

35 25 16

12

36 24 12

▼

12H45-36 12H45-24 12H45-12

12 8 5

29 21 12

42 30 18

17 12 7

33 23 14

9

36 24 12

▼

9H45-36 9H45-24 9H45-12

11 8 4

28 20 11

40 28 16

16 11 6

31 22 12

6

36 24 12

▼

6H45-36 6H45-24 6H45-12

11 7 4

27 19 10

39 27 15

16 11 6

30 21 11

L

C R W

45° HORIZONTAL BEND

D

A

L B D

C R W

Catalog No. Prefix Basic

Width

Catalog No. Prefix Basic

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 18


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS 60° HORIZONTAL BEND

A

Radius

A

B

C

D

L

36

36 24 12

Add Prefix

36H60-36 36H60-24 36H60-12

27 21 15

46 36 26

54 42 30

31 24 17

56 44 31

30

36 24 12

▼

30H60-36 30H60-24 30H60-12

25 19 13

44 33 23

51 39 27

29 22 15

53 40 28

24

36 24 12

▼

24H60-36 24H60-24 24H60-12

24 18 12

41 31 20

48 36 24

27 20 13

37 25

18

36 24 12

▼

18H60-36 18H60-24 18H60-12

22 16 10

39 28 18

45 33 21

26 19 12

47 34 22

12

36 24 12

▼

12H60-36 12H60-24 12H60-12

21 15 9

36 26 15

42 30 18

24 17 10

44 31 18

9

36 24 12

▼

9H60-36 9H60-24 9H60-12

20 14 8

36 24 14

40 28 16

23 16 9

42 29 17

6

36 24 12

▼

6H60-36 6H60-24 6H60-12

19 13 7

33 23 13

39 27 15

22 15 8

40 28 15

D L B

C

D

R

Catalog No. Prefix Basic

Width

W

90° HORIZONTAL BEND

A

Radius

A

B

C

L

36

36 24 12

Add Prefix

36H90-36 36H90-24 36H90-12

54 42 30

54 42 30

54 42 30

84 66 47

30

36 24 12

▼

30H90-36 30H90-24 30H90-12

51 39 27

51 39 27

51 39 27

80 61 42

24

36 24 12

▼

24H90-36 24H90-24 24H90-12

48 36 24

48 36 24

48 36 24

75 56 37

18

36 24 12

▼

18H90-36 18H90-24 18H90-12

45 33 21

45 33 21

45 33 21

70 51 33

12

36 24 12

▼

12H90-36 12H90-24 12H90-12

42 30 18

42 30 18

42 30 18

66 47 28

9

36 24 12

▼

9H90-36 9H90-24 9H90-12

40 28 16

40 28 16

40 28 16

63 44 25

6

36 24 12

▼

6H90-36 6H90-24 6H90-12

39 27 15

39 27 15

39 27 15

61 42 23

L B R

W

C

Catalog No. Prefix Basic

Width

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 19


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS REDUCERS HEFTY TRAY REDUCER

LADDER TRAY REDUCER

CONCENTRIC REDUCTION

CONCENTRIC REDUCTION

ECCENTRIC REDUCTION LEFT

ECCENTRIC REDUCTION LEFT

ECCENTRIC REDUCTION RIGHT

ECCENTRIC REDUCTION RIGHT

For more information, please call 604.572.4419 or visit www.superiortray.com

page 20


Saving you Time, Saving you Money, Putting you First!

CABLE TRAY FITTINGS DIMENSIONS FOR HEFTY TRAY REDUCER 24" 10"

7"

7"

W1 W

A W

W1 A

Concentric

7"

10" 24"

7"

7"

B

C

B

24" 10"

7"

C

W

W1

Right Hand

Left Hand

DIMENSIONS FOR LADDER TRAY REDUCER 3"

6"

3"

6"

W1

A

B

C

W W1

W

W

C

B W1

A

3"

6"

Left Hand

Concentric

Right Hand

REDUCERS for HEFTY TRAY and LADDER TRAY

W

W1

Concentric Catalog No. Prefix Basic

36

30 24 18 12 9 6

Add Prefix

36R30 36R24 36R18 36R12 36R9 36R6

30

24 18 12 9 6

▼

30R24 30R18 30R12 30R9 30R6

24

18 12 9 6

▼

24R18 24R12 24R9 24R6

▼

12 9 6

▼

18R12 18R9 18R6

▼

Width

18

Left Hand Catalog No. Prefix Basic

Right Hand Catalog No. Prefix Basic

Add Prefix

36RL30 36RL24 36RL18 36RL12 36RL9 36RL6

▼

30RL24 30RL18 30RL12 30RL9 30RL6

A or B

C

Add Prefix

36RR30 36RR24 36RR18 36RR12 36RR9 36RR6

3 6 9 12 13 15

6 12 18 24 27 30

▼

30RR24 30RR18 30RR12 30RR9 30RR6

3 6 9 10 12

6 12 18 21 24

24RL18 24RL12 24RL9 24RL6

▼

24RR18 24RR12 24RR9 24RR6

3 6

6 12 15 18

18RL12 18RL9 18RL6

▼

18RR12 18RR9 18RR6

7 9 3 6

6 9 12

3

3 6

4

12

9 6

▼

12R9 12R6

▼

12RL9 12RL6

▼

12RR9 12RR6

1

9

6

▼

9R6

▼

9RL6

▼

9RR6

1

3

Note: All dimensions are in Inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 21


Saving you Time, Saving you Money, Putting you First!

INSTRUMENT CHANNEL INTRODUCTION Instrument Channel is a one-piece channel section, typically used to carry instrumentation, control, data communication, computer and telephone cable. The channel section is either ventilated or solid bottom based on the industry requirement. This tray is designed to use a single power cable as well as multiple circuit cables.

TECHNICAL DATA ″ outside with a loading depth of ″ inside.

Depth:

1 1

Length:

10′ (120″) or 20′ (240″) standard.

Width (inside):

4″ and 6″. Aluminum alloy 6063-T6, Stainless Steel, Mill-galvanized Steel, HDGAF Steel. Painted, Epoxy and other finishes are also available. Ventilated or solid. 12, 24 or 36 inch standard radii. All fittings are non-ventilated.

Materials:

Channel Bottom: Fittings: Splice Plates:

Straight sections and fittings are supplied with splice plates and hardware.

Safety Factor:

1.5 NEMA standard.

CATALOG NUMBER

SSG–6–120 Material Channel Solid Bottom

Width

Length in Inches

Tray Type (Prefix)

HOW TO ORDER Bottom Ventilated Solid

Straight Sections Type Prefix Basic Catalog Number HDGAF Steel Aluminum (Prefix) – Width – Length * SG-

AG-

( ) – 6 – 120 *

SSG-

ASG-

( ) – 4 – 120 *

LOADING TABLES

Steel Aluminum

Width Weight 6 (inch) (lb/ft) Load Defl. 4 1.30 6 1.43 4 0.68 6 0.74 -

8 Load 22.5 23.5 22.4 23.4

Defl. 0.57 0.54 1.10 1.05

Span (ft) 10 Load Defl. 14.4 0.89 15.0 0.86 14.3 1.72 15.0 1.65

12 Load Defl. 10.0 1.29 10.4 1.23 10.0 2.47 10.4 2.37

14 Load Defl. 7.35 1.75 7.70 1.68 7.30 3.37 7.60 3.23

Note: The unit of load is lb and deflection is inch. * Use 240 for a 20 foot length.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 22


Saving you Time, Saving you Money, Putting you First!

INSTRUMENT CHANNEL VERTICAL BENDS 30° VERTICAL OUTSIDE BEND A

D

Radius

6

36 24 12

Add Prefix

4

36 24 12

▼

D B

L

1 3/4" Depth C

R

Catalog No. Prefix Basic

Width

A

B

C

D

L

6VO30-36 6VO30-24 6VO30-12

18 12 5

4 3 1

36 24 12

9 6 3

19 13 6

4VO30-36 4VO30-24 4VO30-12

18 12 5

4 3 1

36 24 12

9 6 3

19 13 6

A

B

C

D

L

45° VERTICAL OUTSIDE BEND A

D

D L

1 3/4" Depth C

B

Width

Radius

6

36 24 12

4

36 24 12

Catalog No. Prefix Basic Add Prefix

6VO45-36 6VO45-24 6VO45-12

26 17 9

10 7 3

36 24 12

15 10 5

28 19 10

▼

4VO45-36 4VO45-24 4VO45-12

26 17 9

10 7 3

36 24 12

15 10 5

28 19 10

A

B

C

D

L

R

60° VERTICAL OUTSIDE BEND A D D 1 3/4" Depth

B

L

Width

Radius

6

36 24 12

Add Prefix

6VO60-36 6VO60-24 6VO60-12

31 21 11

18 12 6

36 24 12

21 14 7

38 26 13

4

36 24 12

▼

4VO60-36 4VO60-24 4VO60-12

31 21 11

18 12 6

36 24 12

21 14 7

38 26 13

A

B

C

L

C R

Catalog No. Prefix Basic

90° VERTICAL OUTSIDE BEND A

Width

Radius

6

36 24 12

4

36 24 12

1 3/4" Depth C R

L

B

Catalog No. Prefix Basic Add Prefix

6VO90-36 6VO90-24 6VO90-12

36 24 12

36 24 12

36 24 12

57 39 20

▼

4VO90-36 4VO90-24 4VO90-12

36 24 12

36 24 12

36 24 12

57 39 20

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 23


Saving you Time, Saving you Money, Putting you First!

INSTRUMENT CHANNEL VERTICAL BENDS 30° VERTICAL INSIDE BEND C

Width

Radius

6

36 24 12

Add Prefix

4

36 24 12

▼

R L

B D

D A

Catalog No. Prefix Basic

1 3/4" Depth

A

B

C

D

L

6VI30-36 6VI30-24 6VI30-12

17 11 5

4 3 1

35 23 11

9 6 3

18 12 5

4VI30-36 4VI30-24 4VI30-12

17 11 5

4 3 1

35 23 11

9 6 3

18 12 5

A

B

C

D

L

45° VERTICAL INSIDE BEND

L B

C

Radius

6

36 24 12

Add Prefix

6VI45-36 6VI45-24 6VI45-12

24 16 7

10 6 3

35 23 11

14 9 4

27 18 8

4

36 24 12

▼

4VI45-36 4VI45-24 4VI45-12

24 16 7

10 6 3

35 23 11

14 9 4

27 18 8

A

B

C

D

L

R

D D A

Catalog No. Prefix Basic

Width

1 3/4" Depth

60° VERTICAL INSIDE BEND

L B

C R

D

D

A

Catalog No. Prefix Basic

Width

Radius

6

36 24 12

Add Prefix

6VI60-36 6VI60-24 6VI60-12

30 20 9

17 11 5

35 23 11

20 13 6

36 24 11

4

36 24 12

▼

4VI60-36 4VI60-24 4VI60-12

30 20 9

17 11 5

35 23 11

20 13 6

36 24 11

Width

Radius

A

B

C

L

6

36 24 12

4

36 24 12

1 3/4" Depth

90° VERTICAL INSIDE BEND

C B

R L

A 1 3/4" Depth

Catalog No. Prefix Basic Add Prefix

6VI90-36 6VI90-24 6VI90-12

35 23 11

35 23 11

35 23 11

55 36 17

▼

4VI90-36 4VI90-24 4VI90-12

35 23 11

35 23 11

35 23 11

55 36 17

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 24


Saving you Time, Saving you Money, Putting you First!

INSTRUMENT CHANNEL HORIZONTAL BENDS 30° HORIZONTAL BEND B D L

A

Width

Radius

6

36 24 12

Add Prefix

4

36 24 12

▼

R

D

Catalog No. Prefix Basic

W

R

A

B

D

L

6H30-36 6H30-24 6H30-12

34 22 11

18 12 11

5 3 2

10 6 4

19 13 7

4H30-36 4H30-24 4H30-12

34 22 11

18 12 6

4 3 1

9 6 3

19 12 7

45° HORIZONTAL BEND B

Width

Radius

6

36 24 12

Add Prefix

4

36 24 12

▼

D L

A D

R

Catalog No. Prefix Basic

R

A

B

D

L

6H45-36 6H45-24 6H45-12

34 22 11

26 18 11

11 7 4

15 10 6

29 20 11

4H45-36 4H45-24 4H45-12

34 22 11

25 17 9

10 7 4

15 10 5

28 19 10

Catalog No. Prefix Basic

R

A

B

D

L

W

60° HORIZONTAL BEND B D

Width

Radius

6

36 24 12

Add Prefix

6H60-36 6H60-24 6H60-12

34 22 11

32 22 12

18 12 7

21 14 8

39 26 15

4

36 24 12

▼

4H60-36 4H60-24 4H60-12

34 22 11

31 21 12

18 12 6

21 14 8

38 25 14

R

A

B

L

L

A D

R

W

90° HORIZONTAL BEND B

L A

W

Catalog No. Prefix Basic

Width

Radius

6

36 24 12

Add Prefix

6H90-36 6H90-24 6H90-12

34 22 11

37 25 14

37 25 14

58 40 23

4

36 24 12

▼

4H90-36 4H90-24 4H90-12

34 22 11

36 24 13

36 24 13

57 38 21

R

Note: All dimensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 25


Saving you Time, Saving you Money, Putting you First!

INSTRUMENT CHANNEL HORIZONTAL CROSSES AND TEES HORIZONTAL CROSS

A

W

B L W Width

Radius

6

36 24 12

4

36 24 12

Catalog No. Prefix Basic

C

A

B

C

L

Add Prefix

6X-36 6X-24 6X-12

39 27 15

78 54 30

39 27 15

61 42 23

▼

4X-36 4X-24 4X-12

38 26 14

76 52 28

38 26 14

59 40 21

R

B

HORIZONTAL TEE

A W D

L W Catalog No. Prefix Basic

Width

Radius

6

36 24 12

Add Prefix

4

36 24 12

▼

C

A

B

C

D

L

6T-36 6T-24 6T-12

39 27 15

78 54 30

39 27 15

42 30 18

61 42 23

4T-36 4T-24 4T-12

38 26 14

76 52 28

38 26 14

40 28 16

59 40 21

R

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 26


Saving you Time, Saving you Money, Putting you First!

CENTER HUNG TRAY INTRODUCTION

Easy step 1, 2, 3 connections for fast and effective site installation: Step 1 - insert rod in splice

For an integrated wire management system, Center Hung Tray simplifies the support and routing of power and telecom/teledata cabling. A single hanger rod is used at each support point. This makes installation easier by reducing support requirements and eliminating the need to pull cable through the trapeze supports. Center Hung provides substantial savings in cost and time. With Center Hung Tray, cables can be laid in on both sides. Both the support and connection of the Center Hung Tray sections are accomplished by a single splice coupling designed to save time. If additional support is needed beyond the 10 feet or 3 meter intervals, an intermediate support hanger can be used.

Step 2 - connect center section to splice

Center Hung Tray rungs come already attached transversely through either the top or bottom of the center tubular rail. Each rung is securely staked to the center rail in four places, providing additional strength and rigidity for reliable cable support. The chances for damaging and losing rungs during transportation and cable installation are significantly reduced with this safe, reliable and secure method of rung attachment.

TECHNICAL DATA Step 3 - slide together

Depth

6 to 24 inches.

Length

10 feet (120″) standard.

Fill Depth

3, 4 and 6 inches.

Rung Spacing

3, 6, 9, 12 and 18 inches.

Materials

Aluminum Alloy 6061-T6, 6063-T6.

CATALOG NUMBER

A12L4–12–120 Material

Rung Style Space (Prefix)

Depth

Width

Length in Inches

Style: • •

T = Center Hung Top Mount Rung L = Center Hung Bottom Mount Rung

• •

WT = Wall Mount Top Rung Single Tier WL = Wall Mount Bottom Rung Single Tier

For more information, please call 604.572.4419 or visit www.superiortray.com

page 27


Saving you Time, Saving you Money, Putting you First!

CENTER HUNG TRAY DIMENSIONS

Top Rung

Bottom Rung 1/2"

Load Width

1/2"

Load Width

Depth

1 1/2"

Depth

A

A

1 1/2"

Depth 3″ 4″ 6″

A Overall Height Top 5 6 8

″ ″ ″

A Overall Height Bottom 3 4 6

″ ″ ″

TYPES OF CENTER HUNG

Width

Load Width Bottom

6″ 9″ 12″

Top 6″ 9″ 12″

18″ 24″

18″ 24″

18″ 24″

7 10 13

″ ″ ″

TOP CENTER HUNG

BOTTOM CENTER HUNG

DUAL CENTER HUNG

WALL RACK

Unique dual width rungs provide 4 separate cable compartments without dividers. Dual width rung catalog numbers utilize our standard format, except both widths are shown.

Three 3/4″ wall spacers that are provided with each standard 10′ or 3m section must be mounted between back of spine and wall at mounting points. This unique design permits a wall rack to be installed without the use of a wall bracket.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 28


Saving you Time, Saving you Money, Putting you First!

CENTER HUNG TRAY CENTER HUNG FITTINGS AND CONNECTORS HORIZONTAL TEE/90° CONNECTOR

HORIZONTAL CROSS COUPLING

Horizontal Cross Coupling

Horizontal Tee/90°Connector

Width 6 9 12 18 24

Bottom Rung ASP-TL-3 ASP-TL-4 ASP-TL-6 ASP-TL-9 ASP-TL-12

Top Rung ASP-TT-3 ASP-TT-4 ASP-TT-6 ASP-TT-9 ASP-TT-12

Width 6 9 12 18 24

Bottom Rung ASP-XL-3 ASP-XL-4 ASP-XL-6 ASP-XL-9 ASP-XL-12

Top Rung ASP-XT-3 ASP-XT-4 ASP-XT-6 ASP-XT-9 ASP-XT-12

VERTICAL TEE/90° CONNECTOR (ASP-VT)

SPLICE CONNECTOR (ASP-CR-B)

OFFSET VERTICAL CONNECTOR (ASP-VOFF-3)

VERTICAL HINGE CONNECTOR (AFS-VCR)

HORIZONTAL HINGE CONNECTOR (AFS-HCR)

For more information, please call 604.572.4419 or visit www.superiortray.com

page 29


Saving you Time, Saving you Money, Putting you First!

CENTER HUNG TRAY ACCESSORIES BOX CONNECTOR

BARRIER STRIP

Catalog Number: A B C ( ) – W – D Width (W): 3″, 6″, 9″, 12″, 18″, 24″ Depth (D): 3″, 4″, 6″

Depth 3″ 4″ 6″

Width

For mounting to equipment and wall entrance flanges.

Part No. A3S-144-CR A4S-144-CR A6S-144-CR

Fixing Clamps and Screws included.

WALL BRACKET

WALL MOUNT

Rugged construction together with the ability to hang tray without any special clamps makes this bracket an efficient and economical device.

Catalog Number: ASP-WALL

Tray Width 6″ 9″ 12″ 18″ 24″

Part No. WBK-6 WBK-7 WBK-9 WBK-12 WBK-15

This connector allows for a sturdy connection for short wall-to-wall runs.

CABLE DROP OUT Drop Out Width 3″ 4 ″ 6″ 8 ″

Part No. AVD-3-CR AVD-4 -CR AVD-6-CR AVD-8 -CR

Drop Out Width 9″ 11 ″ 12″

Part No.

RUNG CAP Rung caps are used for system identification.

AVD-9-CR AVD-11 -CR AVD-12-CR

Option A RUNG CAP

Option B

Attaches to rung with hardware provided.

Color Red Black Blue Orange

Catalog No. RCAP – Red RCAP – Black RCAP – Blue RCAP – Orange

For more information, please call 604.572.4419 or visit www.superiortray.com

page 30


Saving you Time, Saving you Money, Putting you First!

CENTER HUNG TRAY RAIL END CAP

BLIND END

Catalog Number: A E P - C R Simplified one nut and bolt installation to close up end of spline.

Catalog Number: A E P ( ) - W - D Simple one nut and bolt installation. Please advise width and rung type (top/bottom) when ordering.

( ) For Cable Tray Please insert T for Top Rung and L for Bottom Rung.

( ) For Wall Rack Please insert TR for Top Right Hand, TL for Top Left Hand, LR for Lower Right Hand and LL for Lower Left Hand.

CENTER HUNG COVERS Cover Attachment Illustration

Center Hung Cover

Cover Insert

SOLID TOP COVER

SOLID BOTTOM INSERT

Technical Data Width: 6″ to 24″ Length: 10 feet (120″) standard

Technical Data Width: 6″ to 24″ Length: 10 feet (120″) standard

Catalog Number

Catalog Number For top mounted rung: AST-W-D-120 For bottom mounted rung: ASL-W-D-120

For top mounted rung: CACTF-W-120 For bottom mounted rung: CACLF-W-120

Notch permits cover to slide between the support nut and washers for secure attachment

Notch permits cover to slip under washer & nut for easy hold down

Note: Includes one sheet metal connector per insert. D – Depth

W – Width.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 31


Saving you Time, Saving you Money, Putting you First!

BASKET TRAY INTRODUCTION

BASKET TRAY FITTINGS

Basket tray is a wire mesh style cable tray system designed for sensitive cable applications in the data and communications industry. It utilizes high mechanical strength steel wire that is welded into a 2″ x 2″ grid system. This grid system is then formed into channels which support and carry cables. By using Basket Tray’s welded mesh, sensitive cables and fiber optics receive additional support and are safe from any damage due to sharp edges.

HORIZONTAL 90° CONNECTOR KIT (SSP-90-2)

This kit uses our unique 90° splice connectors that maximize cable support while field cutting is minimized by overlapping and clamping into place. Each Kit has 2 back plates, one “L” shaped plate, nuts and bolts.

T CONNECTOR KIT

TECHNICAL DATA Depth:

2″, 4″ and 6″ or 50mm, 100mm & 150mm.

Length:

10 feet (120″) or 3 meter standard.

Width (inside):

2″, 4″, 6″, 10″, 12″, 16″, 18″, 20″, and 24″.

Materials:

Welded steel wire, mill galvanized; other materials available by request. The 2″ x 2″ grid size provides support for cables every 2″ instead of every 4″ like other mesh trays on the market.

Basket Tray T Connectors require 2 Horizontal 90° Connector Kits.

X CONNECTOR KIT

CATALOG NUMBER

WB24–24–120 Wire Basket Grid Depth Size

Tray Series WB22-12 WB22-24 WB24-12 WB24-24 WB26-12 WB26-24

Width

Tray Size inch mm 2X12 50X300 2X24 50X600 4X12 100X300 4X24 100X600 6X12 150X300 6X24 150X600

Length

1.52m/5ft kg/ft lb/ft 35.8 79 42.6 102 42.6 102 42.6 102 52.6 115 52.6 115

Basket Tray X Connectors require 4 Horizontal 90° Connector Kits to make a Cross. Remove a section of each Tray side wall, overlap and connect.

1.82m/6ft kg/ft lb/ft 24.9 55 32.2 71 32.2 71 32.2 71 36.2 80 36.2 80

2.13m/7ft kg/ft lb/ft 18.1 40 23.6 52 23.6 52 23.6 52 26.8 59 26.8 59

2.43m/8ft kg/ft lb/ft 14.1 31 18.1 40 18.1 40 18.1 40 20.4 45 20.4 45

Maximum # of Cables * 315 651 608 1260 936 1540

* This chart is based on 50% fill of 4 UTP Category 5 cable (O.D. of 0.21″ 0.026lbs/ft) For more information, please call 604.572.4419 or visit www.superiortray.com

page 32


Saving you Time, Saving you Money, Putting you First!

BASKET TRAY BASKET TRAY SPLICES

VERTICAL ADJUSTABLE SPLICE CONNECTOR (SFS-VWB2)

SPLICE CONNECTOR (SSP-WB2) Splice connectors are used to clamp two Basket Tray sections together effortlessly. The inner ridged plate clamps the vertical side wires to the outer L-formed plate leveling and supporting the horizontal wire.

Vertical Adjustable Splices are used when modifying the elevation of the cable tray routing.

ACCESSORIES

CENTER HANGER CLAMP

HOLD DOWN CLAMP

2 Hold Down Clamps are fastened to sustain Tray from 1/4″ threaded rod. 2 pieces are required per hanger rod.

(WBHDC) Hold Down Clamps allow Basket Tray sections to be securely fastened into place.

For 1/4″ rod: WBHDC

For 3/8″ rod: WBHDC-3/8

SIDE HANGER CLAMP For trapeze type supports, this clamp attaches threaded rod to the side of the cable tray. For 1/4″ rod: WBVHC

For 3/8″ rod: WBVHC-3/8

For more information, please call 604.572.4419 or visit www.superiortray.com

page 33


Saving you Time, Saving you Money, Putting you First!

BASKET TRAY SUPPORTS AND CONNECTORS UNDER FLOOR BRACKET

UNDER FLOOR PAN SUPPORT

Superior Tray provides an “L” bracket support for 2″ to 24″ wide Basket Tray that includes a clamp, 3/8″ x 1″ square bolt and 1 WBHDC hold down clamp to attach to bracket.

We provide a 6″ Floor Pan Support that includes a WBHDC hold down clamp to attach the tray to floor pan.

Part No. WBUFB-( )

Part No. WBUFB-6

( ) = Width

(C) (B) (A)

BOX CONNECTOR

DROP OUTS

A Box Connector is used to terminate a Basket Tray run to an enclosure, wall or some other junction to a flat perpendicular surface. Includes all mounting hardware.

Drop Outs are provided for both ends of Basket Tray runs and for exiting the side of Basket Tray. They include mounting hardware.

Part No. WBBC-(W)

Part No. WBD-(W)

W = Width

W = Width

W

2 1/16"

5 1/2"

W 2 1/16"

END PLATE

WALL BRACKET

End Plates are available for Basket Tray and are furnished with mounting hardware.

Wall Brackets are to be used for mounting Basket Tray from walls or other structures. Hold down clamps WBHDC and cap screws are not included.

Part No. WEP-(W)-(D) W = Width D = Depth

Part No. WBVBK-( )

( ) = Tray width

D

W 2"

For more information, please call 604.572.4419 or visit www.superiortray.com

page 34


Saving you Time, Saving you Money, Putting you First!

BASKET TRAY SEPARATORS / BARRIERS

CENTER HANGER CLIP

Separators are available in 2″-6″ Heights and come slotted at regular intervals to facilitate installation. Drilling is not required.

For 1/4″ rod Part No. WBCHC For 3/8″ rod Part No. WBCHC-3/8

Part No. S( )S-120-WB

( ) = Height

6 1/4"

1"

2 7/8"

With our Center Hanger Clips, all of our Basket Trays are installed in a true center hung position.

FLANGED COVERS

Z BRACKETS

Flanged Covers are available for all Basket Tray widths. The WBCC cover clamp is available for all depths.

The Z Bracket is recommended to be used when attaching a Basket Tray to a wall, an enclosure or to the floor.

Part No. WBCF2-( )-120 ( ) = Width

Part No. WBBC-( ) ( ) = Depth

3/8 "

Part No. WB-Z

1 1/4"

1 1/4"

H

120 "

1 1/4"

W

8"

CENTER SUPPORT CHANNEL

TRAPEZE HANGER SUPPORT Hanger Rod (1/4" or 3/8")

1/4" Hanger rod

3/4" W

W

3/4"

1 1/2"

1 1/2"

Part # WBCS-28 WBCS-24 WBCS-22 WBCS-20 WBCS-18 WBCS-16

W 28 24 22 20 18 16

″ ″ ″ ″ ″ ″

Part # WBCS-12 WBCS-8 WBCS-6 WBCS-4 WBCS-2

W 12 8 6 4 2

″ ″ ″ ″ ″

Part #

W

Part #

W

WBTHS-28 WBTHS-24 WBTHS-22 WBTHS-20 WBTHS-18 WBTHS-16

32″ 28″ 26″ 24″ 22″ 20″

WBTHS-12 WBTHS-8 WBTHS-6 WBTHS-4 WBTHS-2

16″ 12″ 10″ 8″ 6″

Note: Hanger Rod is supplied seperately.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 35


Saving you Time, Saving you Money, Putting you First!

SPECIAL TRAY INTRODUCTION

HOW TO ORDER EMI

Superior Tray developed several custom designed trays, classified as Special Trays because they are custom manufactured for special installations. Special trays such as the EMI and EAM tray are utilized in industrial facilities having computerized or automated processing equipment where it is necessary to minimize the interferences that are induced in process control and instrumentation cables. We also manufacture AI7 tray, Telco Tray and Universal Tray for special commercial and industrial installations.

The catalog number for a straight section is: E M (D) – (W) – 120 Replace (D) with desired depth and (W) with the width. Each straight section includes cover, wrap-around splice, hardware and self-drilling cover screws.

HOW TO ORDER FITTINGS The catalog number for a fitting is: E M (D) – (W) (Type) – (R) Replace (D) with desired depth, (W) with the width and (R) with the radius. Each fitting includes cover, wraparound splice, hardware and self-drilling cover screws. Standard fittings are 12 and 24 inch radius.

EMI TRAY OR EMI ENCLOSURE SYSTEM Superior Tray offers a wide variety of EMI enclosure systems to protect control and instrumentation cables from undesirable electric noise or electrostatic and electromagnetic interference.

HOW TO ORDER COVERS The catalog number for a cover is: E M C – (W) Specify the size of the cover by replacing (W) with the width. Covers are supplied in 10 foot (120″) lengths and come with each straight section.

TECHNICAL DATA Depth

4 inches and 6 inches nominal.

Length

10 feet (120″) standard.

Widths (inside)

6, 9, 12, 18 and 24 inches.

Materials

Hot-dip mill galvanized steel. Other finishes are also available.

STANDARD COVER HOLDING DEVICE Self-drilling sheet metal screws: Catalog # B-26 All holding devices should be located on 2 foot centers.

LOADING Span (ft) 8 10 Load Defl Load Defl

Depth

Width

(D)

(W)

4

6″ 9″ 12″ 18″ 24″

749 *591 *443 *295 *221

0.11 0.08 0.06 0.04 0.03

333 333 333 *295 *221

0.24 0.24 0.24 0.22 0.16

187 187 187 187 187

0.44 0.44 0.44 0.44 0.44

119 119 119 119 119

0.69 0.69 0.69 0.69 0.69

83 83 83 83 83

0.99 0.99 0.99 0.99 0.99

6″ 9″ 12″ 18″ 24″

*887 *591 *443 *295 *221

0.05 0.03 0.02 0.02 0.01

414 414 414 *295 *221

0.11 0.11 0.11 0.08 0.06

233 233 233 233 *221

0.20 0.20 0.20 0.20 0.20

149 149 149 149 149

0.32 0.32 0.32 0.32 0.32

103 103 103 103 103

0.46 0.46 0.46 0.46 0.46

6

4 Load Defl

6 Load Defl

12 Load Defl

D

W Enclosure Cross-section

Note: * indicates that allowable load is limited by the load carrying capacity of the transverse member. The unit of Load is lb and Deflection is inch.

OPTIONAL COVER HOLDING DEVICES Clamps Clamps permit easy removal of the cover and access to the cable. Clamps are reusable.

Tray Depth

Catalog Number

4″ 6″

JCC MCC

Clamp

Wrap-Around Splice Wrap-Around The catalog number of the splice is: Splice E M S (D) – (W) The size of the splice is specified by replacing (D) with the desired depth and (W) with the width. The splice is supplied with all necessary hardware.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 36


Saving you Time, Saving you Money, Putting you First!

THE EMI ENCLOSURE SYSTEM FITTINGS Horizontal Cross Catalog No. Prefix Basic

Width

Radius

A

B

C

L

24

24 12

▼

24X-24 24X-12

36 24

72 48

36 24

56 37

18

24 12

▼

18X-24 18X-12

33 21

66 42

33 21

51 33

12

24 12

▼

12X-24 12X-12

30 18

60 36

30 18

47 28

9

24 12

▼

9X-24 9X-12

28 16

57 33

28 16

44 25

6

24 12

▼

6X-24 6X-12

27 15

54 30

27 15

42 23

A W B L R C

W

Horizontal Tee Catalog No. Prefix Basic

A

B

C

D

▼

24T-24 24T-12

36 24

72 48

36 24

48 36

56 37

24 12

▼

18T-24 18T-12

33 21

66 42

33 21

42 30

51 33

12

24 12

▼

12T-24 12T-12

30 18

60 36

30 18

36 24

47 28

9

24 12

▼

9T-24 9T-12

33 21

44 25

24 12

▼

6T-24 6T-12

30 18

42 23

Width

Radius

24

24 12

18

6

28 16 27 15

57 33 54 30

28 16 27 15

L

B A W

D L

W

R C

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

page 37


Saving you Time, Saving you Money, Putting you First!

THE EMI ENCLOSURE SYSTEM Vertical Outside Bends

Horizontal Bends B

B

B

D

D

B D

D

R

D

D

R

R

R

R

A

D

W

W

H30°

H45°

W

W

H60°

VO30°

C

A

L

A

L

A

L

B

L

1 3/4" Depth

L

D A

A

D

D

H90°

L

1 3/4" Depth C

B

VO45°

R

Horizontal Bends 45°

30° Width

Radius

A

B

60°

A

B

A

90°

A

B

D

A

B

24

24 12

4 3

24 12

4 2

18 12

10 7

25 17

18 12

31 20

36 24

36 24

9 6

23 14

16 10

28 18

33 21

33 21

VO60°

D 1 3/4" Depth

B

L C R A

18

16 10

VO90°

1 3/4" Depth C

8 5

21 12

15 9

26 15

30 18

30 18

14 8

8 4

20 11

14 8

24 14

28 16

28 16

13 7

7 4

19 10

13 7

23 13

27 15

27 15

4

12

24 12

2

9

24 12

3 2

6

24 12

3 2

15 9

Vertical Inside Bends C R L

B

Vertical Inside Bends 30° Width

Radius

6

24 12

VI30°

D

45°

A

B

11 5

3 1

A

60° B

16 7

6 3

A 20 9

D A

90° B

11 5

A 23 11

B

L

R

1 3/4" Depth

B 23 11

L B

C

R

VI45°

D D A

4

24 12

11 5

3 1

16 7

6 3

20 9

11 5

23 11

1 3/4" Depth

23 11

L B

C R

D

VI60°

Vertical Outside Bends 45°

30° Width

Radius

6

24 12

4

24 12

A 12 5 12 5

B 3 1 3 1

A 17 9 17 9

60° B

7 3 7 3

A 21 11 21 11

90° B

12 6 12 6

A 24 12 24 12

A

D

B 24 12

1 3/4" Depth

VI90°

C B

24 12

Note: All dimensions are in inches

For more information, please call 604.572.4419 or visit www.superiortray.com

R L

A 1 3/4" Depth

page 38


Saving you Time, Saving you Money, Putting you First!

THE EMI ENCLOSURE SYSTEM TECHNICAL INFORMATION With the increased use of computerized processing equipment in large industrial facilities, the minimization of interference induced in the communication link between the in-plant transducers or primary elements and controllers becomes critical. Depending upon the installation, this link, in most cases a pair or electrical conductors, may be very short, or may run for several hundred feet. The longer the control-signal cable, the more susceptible it is to induced electrical noise. Shielding these cables with a copper braid or metallic tape will protect them from each other, but for long runs a better method of shielding is necessary for protection against external interferences. To shield these cables individually is impractical because of the large number used in a complex industrial control system. Numerous control signal cables can be protected from interference by using a properly designed and shielded enclosure. Undesirable voltage is induced into the control signal cables by five methods: 1. Electrostatic Fields. 2. Electromagnetic Fields. 3. Plane Wave Radiation. 4. Cross Talk 5. Common Mode. Cross Talk and Common Mode interference are functions of the control circuits themselves and must be handled through the proper selection of cable and grounding methods. Plane wave radiation, which is of concern at very high frequencies (30 MHz), is generally not a problem in the typical industrial or utility environments. Electrostatic and Electromagnetic Fields are important and directly influence the selection of shielded cable enclosures. Electrostatic interference is caused by stray capacitance between the control-signal cable and other conductors and machinery in the area. This stray capacitance can be reduced by completely enclosing the control-signal in a shielded enclosure which is a good electrical conductor. The measure of electrical effectiveness in this situation is the electrostatic attenuation. This attenuation is determined by measuring the undesirable induced voltage in the control signal cable within the shielded cable enclosure. The enclosure must be properly grounded if it is to act as an electrostatic shield. Electromagnetic interference is caused by the mutual inductance between the control signal cables and other surrounding power cables and machinery. This mutual inductance can be reduced (shielding the control cable) if the control signal cable is completely enclosed in a

good magnetic material. An electromagnetic attenuation parameter can be defined in the same manner as the electrostatic attenuation. Unfortunately, good electrical conductors are not effective magnetic (high permeability) materials. The converse is also true. In most industrial installations, shielding must be provided against both electrostatic and electromagnetic fields. Thus a compromise must be made. The attenuation parameters (electrostatic and electromagnetic) may be measured under laboratory conditions. A test setup is used to create the proper type of field, and the induced voltage “ ” in a control signal cable is measured with the cable suspended in free air. Then the test is repeated with the control signal cable enclosed in the shielded enclosure and the induced voltage “e” is measured. The shielding effectiveness is given by the ratio of these voltages: S= The greater the ratio, the better the shield is. Due to the wide dynamic range of “S” for different types of shields, the attenuation is usually expressed as twenty times the logarithm to the base ten of “S”. A = 20 S or A = 20 The attenuation parameters are both functions of frequency and therefore are usually shown by a graphical display of “AS” (Electrostatic Attenuation) and “AM” (Electromagnetic Attenuation) plotted versus frequency. Protection of Control and Instrumentation Cable The type of signal transmitted by the primary element to the controller determines how sensitive the signal is to extraneous electrical interference. For example, the lower the voltage the higher the impedance and more susceptible the circuit is to interference. Since most process type primary elements operate at low voltages and amperes, care must be taken when selecting shielding requirements. Typical levels of operation range between less than 100MV to 5V on voltage type elements and 1MA to 50MA on current systems. Many companies, who have installed automated process control, have found that high additional costs are incurred in eliminating interference in systems during the check-out and start-up stages of construction. By selecting the proper cable and EMI enclosure in the engineering stage, additional costs are eliminated.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 39


Saving you Time, Saving you Money, Putting you First!

THE EMI ENCLOSURE SYSTEM The following guidelines will ensure the acceptable method of installing instrumentation: A. B. C. D. E.

most

Use twisted parallel pairs - shielded and grounded. Separate control wires by frequency and voltage level. Route control circuits to avoid power cables and machinery. Install control cable in a Superior Tray EMI enclosure. Ground the shielded EMI enclosure.

Superior EMI enclosures offer excellent attenuation characteristics while providing a low-cost economical installation that allows for additional control cables, check-out and rewiring. The following figures illustrate the attenuation levels for both electromagnetic and electrostatic interference over the general frequency range of concern.

The interfering induced voltages are caused by surge voltages which are either continuous wave or impulse wave types. The over-voltages are present due to periodic transients, switching surges, circuit breaker or GAP flashover. Typically, indeed voltages on the control cables are in the order of 10-15KV if not adequately shielded. A shielded control cable enclosed in an EMI enclosure offers the best overall protection. EMI enclosures facilitate the placement of control cables above ground where rewiring or additions are added without the high costs and corrosion problems associated with underground methods. Voltage Pickup on Control Cable Without Enclosure* With EMI Enclosure**

100

Attenuation (db)

100

Electromagnetic Test with Variable Frequency and Constant Field Intensity

2″ Diameter Steel Rigid Conduit

80

2″ Diameter Aluminum Conduit

60

Superior Tray EMI Galv. Steel Enclosure

40

20

0

60 100

1000

10000

100000

Frequency (Hz)

Attenuation (db)

120 2” Diameter Copper Pipe

100

2” Diameter Aluminum Conduit

80

Electrostatic Test with Variable Frequency and Constant Voltage

60 40

Superior Tray EMI Galv. Steel Enclosure

20 0

60 100

1000

10000

100000

Frequency (Hz)

High Voltage Station Switchyard Control Cable Protection For switchyards with primary system voltages of 230 KV and above, control and instrumentation cables must be protected from induced voltages that can cause control cable insulation breakdown and damage to control components. This problem becomes more acute when solid state devices, which are even more susceptible to damage by overvoltage, are used on new installations.

Surge Voltage 600 KV 1000 KV 1400 KV

Type A

Type B

Type A

Type B

7.3 KV 16.9 KV 24.8 KV

2.9 KV 10.4 KV 16.0 KV

51 Volts 53 Volts 113 Volts

17 Volts 26 Volts 23 Volts

Type A – Control cable with copper tape and drain wire. Type B – Control cable with lead shield. * Shield floating. ** Shield grounded at both ends.

TYPICAL EMI SPECIFICATION 1. General 1.1 Scope This specification includes all the necessary materials to provide an EMI enclosure system with high degree of electrostatic and electromagnetic shielding for low level control circuits. The enclosures are designed and constructed to be equal or better than the EM-shielding attributes herein specified, over the frequency range of 60Hz to 100 KHz. 1.2 Basic Design To meet the requirements of this specification the cable tray and cover must totally enclose the specified cables, circuits, and/or devices with metal. Non-metallic materials are not acceptable for this purpose. 2. Attenuation Requirements 2.1 Electrostatic Attenuation The minimum acceptable electrostatic (electrical field) shielding efficiency for the enclosure to be supplied for this installation is 86 db in the range of 60Hz to 100 KHz. 2.2 Electromagnetic Attenuation The minimum magnetic field shielding efficiency increases from 9 db to 55 db over frequency range of 60 Hz through 100 KHz.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 40


Saving you Time, Saving you Money, Putting you First!

THE EMI ENCLOSURE SYSTEM 2.3 Certification Superior Tray certifies that the EMI enclosure is equal to or better than the shielding efficiency mentioned in paragraph 2.1 and 2.2. Such certification consists of a report evaluation tests performed by Superior Tray or by an independent testing laboratory. The report describes the enclosure, the test methods used to evaluate the product and technical data (graphs, charts, etc.) supporting the shielding performance claims for the products. 3. Additional Requirements 3.1 General In addition to the above attenuation requirements, the completed EMI enclosure systems are readily accessible for installation, rearrangement, and inspection of cables supported. Additionally, the Superior Tray enclosure systems meet the following electrical and mechanical requirements. 3.2 Electrical Continuity and Grounding All components of the enclosure system are thoroughly grounded to conform to the NEC requirements. A bare copper bonding cable is installed in the enclosure to provide adequate grounding continuity. Each section of the enclosure and all fittings are securely bonded to the

ground bus in the enclosure with suitable grounding fitting to ascertain continuity to ground throughout the enclosure system. 3.3 Material Specifications All members of the enclosure system, unless specified otherwise, are made from the same steel as standard cable tray, and all EMI enclosure are hot-dip mill galvanized. Application of design rules and fabrication are in accordance with A.I.S.I specifications and A.W.S. standards. The hot dip galvanized protective covering conforms to the following A.S.T.M. standard. A-525G90 specification for Zinc coating (galvanized) is used on all steel enclosure parts. 3.4 Design Load Design loads (lbs/linear ft.) for the enclosures are in accordance with the loading table of this chapter. 3.5 Approval of EMI Enclosures The contractor shall submit for approval, as soon as practical and within 30 days after the award of contract and before the purchase of material, a complete schedule of the materials and equipment proposed for installation including the specified data and the Manufacturer’s name.

EAM TRAY EAM Tray is more of a wireway enclosure system that protects the control and instrumentation cables from undesirable voltage interference and electric noise. Other than that it is similar to EMI enclosure system.

The wireway enclosure is installed and supported on top of the Cable Tray using ASC Support Channels, Redi-Rods and EAMB brackets. Power Cables are installed on the cable tray while the wireway enclosure provides a segregated barrier to protect the control signal and lighting circuit cables from undesirable interference and electric noise.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 41


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL HANGER RODS

INTRODUCTION Support materials are crucial in installing cable tray systems. Superior Tray classifies the support materials into the following categories:     

Suspension Channels and Fittings Hangers Vertical Run Supports Wall Brackets Strut and Strut Hardware

SUSPENSION CHANNELS AND FITTINGS CENTER SUPPORT

Hanger rods with 1/2″ diameter and 13 threads per inch can be used with all tray support channels, angles and hanger clips. They have continuous threads and are furnished with 4 (N-12) nuts, 2 (W-9) lock-washers and 2 (W-12) flat washers. Maximum allowable load: Use for design, 1100 lbs., in combination with all standard suspension fittings, hanger clips, and couplings normally used. The safe load is much higher. Item 12′-0″ Hanger Rod 6′-0″ Hanger Rod 3′-0″ Hanger Rod Extra Hex Nuts Extra Lock Washers Extra Flat Washers

Plated Steel HR-144G HR-72G HR-36G N-12 W-9 W-12

Stainless Steel (316) 6HR-144G 6HR-72G 6HR-36G N-12-6S W-9-6S W-12-6S

CHANNELS Center Supports offer the economy of less support material and better side access to the tray system for trays carrying light to medium loads. Extra consideration should be given to balancing the cable load during cable installation. It is supplied with Support Channel, Hanger rod sleeve, Nuts and washers, Tray hold down clips and hardware. 1/2″ hanger rod is not included. Max load 800 lbs. with 1.5 safety factor. Tray Type

Aluminum

HDGAF

Stainless Steel (316)

All Ladder Tray

VACS-( )

VSCS-( )

6VSCS-( )

All Hefty Tray

EACS-( )

ESCS-( )

6ESCS-( )

-

VSCS-( )-H

6VSCS-( )-H

H J

-

VSCS-( )-J

6VSCS-( )-J

JA, JB, JC, YA

VACS-( )-K

VSCS-( )-K

6VSCS-( )-K

M, MB, MC

VACS-( )-M

VSCS-( )-M

6VSCS-( )-M

Note: ( ) = tray width

Channels are used with 1/2″ hanger rods to support ladder style trays where hanger clips cannot be utilized and for troughs with or without hold-down clips. When used with trough, only HB-2, JB-2, etc. style hold-down clips can be used. Tray Width 36 30 24 18 12 9 6

Alum.

HDGAF

ASC-36 ASC-30 ASC-24 ASC-18 ASC-12 ASC-9 ASC-6

SSC-36 SSC-30 SSC-24 SSC-18 SSC-12 SSC-9 SSC-6

Stainless Steel 304 316 4SC-36 6SC-36 4SC-30 6SC-30 4SC-24 6SC-24 4SC-18 6SC-18 4SC-12 6SC-12 4SC-9 6SC-9 4SC-6 6SC-6

For more information, please call 604.572.4419 or visit www.superiortray.com

page 42


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL ANGLES

HANGERS

Angles are continuously slotted to hold down Trough using HB-1 bolts, and can be used to support all tray types with 1/2″ hanger rod suspended from overhead.

BEVEL WASHERS

Maximum allowable load: It safely supports any loaded tray of the designated width within the load limits of the hanger rod. Tray Width 36″ 30″ 24″ 18″ 12″ 9″ 6″

HDGAF STSA-36 STSA-30 STSA-24 STSA-18 STSA-12 STSA-9 STSA-6

The standard size is 1-1/4″ square with a 1/2″ bevel and a 9/16″ hole.

Catalog Number: W-11.

VERTICAL HANGERS FOR TRAY

SINGLE CHANNEL HANGERS

Vertical Hangers are used to support single type vertical ladders or troughs from 1/2″ hanger rods. Each is furnished with the required mounting hardware. Maximum allowable load: 250 lbs/unit

Single Channel Hangers are used to support single 4″ or 6″ wide Instrument Channels from 1/2″ hanger rod. The bottom support member, on which the channel rests, is drilled to accommodate HB-10 hold-down bolts. Channel Type

HDGAF

4″, 6″

SH-GU

Stainless Steel 304 316 4SH-GU

6SH-GU

DOUBLE CHANNEL HANGERS Double Channel Hangers support single or double, 4″ or 6″ wide Instrument Channels from 1/2″ hanger rods. The support member, on which the channel rests, is drilled to accommodate HB-10 hold-down bolts, or SGB-GU expansion guide bolts. Channel Type

HDGAF

4″, 6″

SH-2GU

Stainless Steel 304 316 4SH-2GU

6SH-2GU

HDGAF

Stainless Steel 316

SH-VU

6SH-VU

VERTICAL HANGERS FOR CHANNEL This hanger assembly for vertical channels accommodates either 4″ or 6″ wide channels and is furnished with all necessary hardware, except for the top 1/2″ hanger rod to the building steel. Maximum allowable load: 200 lbs/unit HDGAF

Stainless Steel 316

SH-VGU

6SH-VGU

For more information, please call 604.572.4419 or visit www.superiortray.com

page 43


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL CHANNEL CLAMPS

BRACKET ANGLES

Channel Clamp assemblies can be used on all American Standard channels with a flange width of 3-1/4″ or less. They are furnished in zinc plated steel with or without a swivel joint.

Bracket Angles are used to connect two wall brackets, which then serve as a support for vertical runs. Cable trays are then bolted to bracket angles with support angle clips. Bracket angles have a series of slots to allow the attachment of various types of tray of the same width to the same bracket angle. It is fabricated from hot dip galvanized steel.

Maximum allowable load: 500 lbs. with a safety factor of 5 Zinc Plated Steel

Item Clamp Only

HP-177

Clamp with Swivel Joint

HP-177SJ B

HP CHANNEL CLAMPS

A

HP single and back to back strut type support channels are attached to structural beams with a 0.8″ maximum flange thickness. Clamps are furnished with the required hardware. Maximum allowable load: 1,275 lbs. with a safety factor of 5 Channel Type

Zinc Plated Steel

HP-200 Single Strut

HP-2652

HP-201 Double Strut

HP-2651

VERTICAL RUN SUPPORTS Superior Tray supplies a wide variety of vertical run supports depending on the load, support spacing and distance of the run from the wall or supporting structure. The support spacing for vertical runs is recommended to be no less than six feet and no more than twelve feet. Brackets are available for spacing of 3, 12, 24 and 36 inches from the wall to accommodate the various radii bends that may be entering or leaving the supporting wall. Vertical runs usually consist of either a Z-Bracket for a 3 inch distance from the wall only, or a pair of brackets with the necessary support angles and clips to fasten the tray to the support. The proper support angle and number of bracket angle clips for the tray to be used must be determined in addition to wall brackets. For each application, the actual load per bracket must be checked against the maximum allowable load on the bracket.

Tray Width

A

B

Catalog Number

Single Bracket Angles 30″ 24″ 18″ 12″ 09″ 06″

44 38 32 26 23 18

41 35 29 23 20 15

SRSA-30 SRSA-24 SRSA-18 SRSA-12 SRSA-9 SRSA-6

Double Bracket Angles 30″ 24″ 18″ 12″ 09″ 06″

74 62 50 38 32 26

71 59 47 35 29 23

DRSA-30 DRSA-24 DRSA-18 DRSA-12 DRSA-9 DRSA-6

Double Bracket Angles (for U-type support angle clips) 30″ 76 73 DDSA-30 24″ 64 61 DDSA-24 18″ 52 49 DDSA-18 12″ 40 37 DDSA-12 09″ 36 31 DDSA-9 25 06″ 33 DDSA-6

For more information, please call 604.572.4419 or visit www.superiortray.com

page 44


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL Z-BRACKETS

SUPPORT ANGLE CLIPS

Z-Brackets are used to support vertical runs at a distance of 3 inches from the wall. They have a slot pattern similar to that of bracket angles and are made from standard 7 gauge Z-shaped HDGAF steel.

Support Angle Clips are used to fasten a cable tray to a bracket angle or Z-Bracket. They come in single or double configurations (“L” or “U”) and are furnished with the required hardware.

B A

Item

HDGAF

Stainless Steel 304 316

Single Angle Clip

BKSA-C

4BKSA-C

6BKSA-C

Double Angle Clip

BKSA-DC

4BKSA-DC

6BKSA-DC

3"

1 1/2" 2-11/16"

1-1/2"

WALL BRACKETS Tray Width

A

B

Catalog Number

Single Z Bracket 30″ 24″ 18″ 12″ 09″ 06″

44 38 32 26 23 18

41 35 29 23 20 15

SRZ-30 SRZ-24 SRZ-18 SRZ-12 SRZ-9 SRZ-6

71 59 47 35 29 23

DRZ-30 DRZ-24 DRZ-18 DRZ-12 DRZ-9 DRZ-6

Superior Tray offers a variety of wall brackets to support trays and channels from any wall or vertical support. The design of the brackets takes into consideration whether the trays or channels will be supported singly or two in parallel, on horizontal or vertical runs, the distance from the wall, bend radii, etc. The allowable load of each type of bracket is given for two loading conditions: Condition 1: Where the load is applied at two points.

Double Z Bracket 30″ 24″ 18″ 12″ 09″ 06″

74 62 50 38 32 26

Double Z Bracket (for U-type support angle clips) 30″ 76 73 DDZ-30 24″ 64 61 DDZ-24 18″ 52 49 DDZ-18 12″ 40 37 DDZ-12 31 09″ 36 DDZ-9 06″ 33 25 DDZ-6

Condition 2: Where the load is applied as a single concentrated load at the end of the bracket.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 45


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL CHANNEL BRACKETS

ONE PIECE WALL BRACKET

Channel Brackets are designed to accommodate single or double channel runs with pre-drilled holes for HB-10 Hold Down Bolts. The bolts are purchased separately.

This light duty One Piece Wall Bracket is made from 1/8″ hot dip galvanized steel. Placing one bracket below another allows a minimum vertical spacing of cable trays of 8″. Maximum allowable load: Condition 1: 600 lbs. Condition 2: 300 lbs.

Maximum allowable load: Twice the allowable load for the respective channel at a support spacing of 10 feet.

Stainless Steel 304 316

Item

HDGAF

Single for 4″ Channel

SSBK-G

4SSBK-G

6SSBK-G

Double for 4″ Channel

SDBK-G

4SDBK-G

6SDBK-G

Single for 6″ Channel

SSBK-G6

4SSBK-G6

6SSBK-G6

Double for 6″ Channel

SDBK-G6

4SDBK-G6

6SDBK-G6

A

Catalog Number

27 23 19 15 12 9

WBK-28L WBK-24L WBK-20L WBK-16L WBK-12L WBK-10L

LOW HEADROOM BRACKETS

MEDIUM WEIGHT BRACKETS

Low Headroom Brackets are used to attach Ladder Tray to wall mounted channel framing. These brackets are available in HDGAF.

Medium Weight Brackets are used to support 2 ladder trays side by side or 2 ladders one over the other.

Maximum allowable load: Condition 1: 500 lbs. Condition 2: 250 lbs.

These brackets are made of 3/16″ structural angle, welded and hot dip galvanized. The horizontal support angle is continuously slotted to increase the versatility of the bracket. Maximum allowable load: Condition 1: 1200 lbs. Condition 2: 600 lbs.

A

B

C

Catalog Number

25 19 13 10 7

21 15 9 6 3

1

VBK-24 VBK-18 VBK-12 VBK-9 VBK-6

1 2 2 3

Type

A

49″ 39″ 30″ 21″

49 39 31 21

B 31 26 21 18

C

Catalog Number

25 20 15 12

For more information, please call 604.572.4419 or visit www.superiortray.com

WBK-49M WBK-39M WBK-30M WBK-21M page 46


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL HEAVY WEIGHT BRACKETS Heavy Weight Channel Type Brackets are designed to support long spans or multiple ladder or trough installations that exceed the load capacity of ordinary brackets. They are welded from 3″ structural steel channel with 1-1/2″ channel stiffening members and hot dip galvanized. To utilize the full strength of the brackets, the 3 bolts of 1/2″ diameter for which the wall members are drilled must be used. Maximum allowable load: 4,000 lbs. when applied as 2 equally concentrated loads, spaced at least 2′-4″ apart on brackets five feet wide and under; or at least 4′-6″ apart on brackets over five feet wide. The capacity is greater when used for a uniformly distributed load.

Heavy Weight Bracket

Single Strut Bracket

Tray Width 24″ 18″ 12″ 9″ 6″

Uniform Load (lb) 200 500 700 700 1000

Ladder Tray

Hefty Tray

HP-S250-30 HP-S250-24 HP-S250-15 HP-S250-12 HP-S250-9

HP-S250-30 HP-S250-24 HP-S250-18 HP-S250-15 HP-S250-12

DOUBLE STRUT BRACKETS Double strut brackets are used for wider trays and heavier loads. The uniform load shown represents a 2.5 safety factor. These brackets are made from HDGAF steel. Allowable concentrated end load: One half the listed uniform load.

Double Strut Bracket Type

A

B

C

Catalog Number

66″ 60″ 54″ 48″ 42″ 36″

66 60 54 48 42 36

63 63 51 51 39 39

56 56 44 44 32 32

WBK-66C WBK-60C WBK-54C WBK-48C WBK-42C WBK-36C

SINGLE STRUT BRACKETS Designed for use with strut framing, these single strut brackets will work well in other applications. The uniform loads shown represent a 2.5 safety factor. These brackets are furnished in HDGAF steel. Allowable concentrated end load: One half the listed uniform load.

Tray Width 36″ 30″ 24″ 18″

Uniform Load (lb) 400 650 800 1000

Ladder Tray

Hefty Tray

HP-S251-42 HP-S251-36 HP-S251-30 HP-S251-24

HP-S251-42 HP-S251-36 HP-S251-30 HP-S251-24

For more information, please call 604.572.4419 or visit www.superiortray.com

page 47


Saving you Time, Saving you Money, Putting you First!

SUPPORT MATERIAL STRUT TYPE SUPPORT CHANNEL HP-type channels provide indirect support for hanger rods by spanning between available structural support beams and channels. The channel is supplied in 10′ or 20′ lengths and can easily be field cut to the length needed for use as a trapeze type support. These channels are available in single or double (back to back) configurations.

Width Depth Weight/ft Black Steel Mill Galvanized HDGAF

Single 1 ″ 1 ″

Double 1 ″ 3 ″

2 lbs HP-200-( ) HP-200-( )-P HP-200-( )-G

4 lbs HP-201-( ) HP-201-( )-P HP-201-( )-G

Strut Type Support Channel

Note: P = Pre-Galvanized, ( ) = insert 120/240 G = HDGAF, ( ) = insert 120/240

STRUT HARDWARE

W-12

W-9 B-61

HP-10TG

Item

1

N-12

Plated Steel

Stainless Steel 304

316

″ Spring Nut

HP-10TG

4HP-10TG

6HP-10TG

″ Square Black Nut

HP-10WS

4HP-10WS

6HP-10WS

W-10

W-10-4S

W-10-6S

B-61

B-61-4S

B-61-6S

″ Lock Washer

W-9

W-9-4S

W-9-6S

″ x 13 Hex Nut

N-12

N-12-4S

N-12-6S

″ Flat Washer

W-12

W-12-4S

W-12-6S

″ Square Washer, ″x1

″ Hole

″ Hex Head, Cap Screw

Note: All dimensions are in inches. For more information, please call 604.572.4419 or visit www.superiortray.com

page 48


Saving you Time, Saving you Money, Putting you First!

COVERS AND COVER FASTENERS INTRODUCTION Superior Tray offers a wide variety of covers that provides the cables contained within the system protection from sunlight, environmental elements, dirt, debris, and falling objects. All of the covers listed here are used for both indoor and outdoor applications. Covers are fabricated from corrosion resistant aluminum, mill-galvanized steel, and 304 or 316 stainless steel. Although not recommended, covers can be supplied in HDGAF steel on request (some distortion may occur when dipping). Most covers are supplied in standard 10 foot lengths and are available in 5 foot lengths upon request.

Different Cover Types

CATALOG NUMBER FLAT, FLANGED AND VENTILATED COVERS

CS2F( )–24H90–12 Cover Type Material Indicates Tray Thickness Cover Type or Guage

Fitting Designation Length

HAT SHAPED OR PEAKED COVERS

COP–A2S( )–W–120–15 Material Type

Cover Height Indicates Cover

Cover Shape

Tray Type

Cover Type

Width

Thickness or Gauge

Degree of Slope Length

COVER CODE DEFINITIONS Material Type (A) Aluminum (S) Steel (4) 304 Stainless Steel (6) 316 Stainless Steel

Tray Types (1) All Flange In (2) 3/4″ Flange Out (3) 1-3/4″ Flange Out (4) 1-1/2″ Flange Out (5) 1-1/4″ Flange Out

Cover Shape Hat Shaped (S) Solid Top (non-ventilated) (V) Ventilated Peaked (P) Peaked (non-ventilated)

Material Gauge Standards are: 22 Gauge Steel and 0.040″ Aluminum ( ) Insert cover gauge for any cover (2) 22 Gauge Standard Steel (0) 20 Gauge Steel (Optional) (8) 18 Gauge Steel (Optional) (6) 16 Gauge Steel (Optional) or 0.063″ Aluminum (Optional) (4) 14 Gauge Steel (Optional) For Louvered Flat, Flat Flanged and Hat-Shaped covers, “-L” is required at the end of the catalog number. Example: CA1F-24-144-L

Cover Type Flat, Flanged & Ventilated (V) Ventilated (S) Flat (non-ventilated) (F) Flat Flanged (non-ventilated) Hat Shaped & Peaked (S) Flat Solid (non-flanged) (F) Flanged

Length Cover Height (120) 10 Foot Length Hat Shaped (60) 5 Foot Length (2) 2″ High (4) 4″ High Peaked (0) 1/2″ High Peak (If Degree of slope is omitted) ( ) Insert Peak Height in Inches Note: Unit is by degree (°) if Degree of Slope is included.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 49


Saving you Time, Saving you Money, Putting you First!

COVERS AND COVER FASTENERS TYPES OF COVER FLAT AND FLAT FLANGED

LOUVERED

Flat covers are economical and available for all straight sections and fittings. These covers are available flat without flanges or flat with 3/8″ flanges for Ladder Tray and Hefty Tray. Flat flanged covers should be used on all 4″ and 6″ wide channel applications requiring covers.

Louvered covers are available for all straight sections and are available as Flat, Flat Flanged, or Hat Shaped.

Louvered Cover

Flat Flanged Cover

VENTILATED HAT-SHAPED Hat-shaped covers are designed to protect installations where the cables extend above the upper flanges of the tray. Hat-shaped covers are available with a flat solid top as well as ventilated top and are in 2″ or 4″ height.

Hat Shaped Cover

Ventilated covers are rigid, lightweight and will readily form to vertical fittings, with the exception of Hefty Tray style. These ventilated covers can be flat sheet type, hat shaped type or hefty tray style. All covers for horizontal fittings are made of non-ventilated (solid) flat sheets without a flange.

Hat Shaped Ventilated Cover

PEAKED Peaked covers are generally used to deflect falling objects or to prevent the accumulation of snow or other debris. Standard peak height is 1/2″. However, higher peaks are available upon request.

Flat Sheet Ventilated Cover

Peaked covers are not available for fittings.

Peaked Cover Hefty Tray Style Ventilated Cover

For more information, please call 604.572.4419 or visit www.superiortray.com

page 50


Saving you Time, Saving you Money, Putting you First!

COVERS AND COVER FASTENERS COVER FASTENERS A complete line of cover fasteners is available for both indoor and outdoor applications. Local conditions will dictate the selection of the proper fastening device. Cover fasteners must be ordered separately for the application and spacing desired. Both clips and clamps are used indoors, but only clamps are used for outdoor applications. Standard quantities of clips and clamps used for most conditions are given below:

Cover Fastener Flat

Clip Style:  6 per 10′ of straight cover.  4 minimum per horizontal or vertical 90° fitting.  6 per Tee fitting.  8 per Cross fitting. Bar Clamp Style:  3 per 10′ straight cover.  2 min. per horizontal or vertical 90° fitting.  3 per Tee fitting.  4 per Cross fitting.

HOLD DOWN CLAMPS FOR TRAY

Cover Fastener Peaked

These heavy duty cover fasteners are used for covers installed in high wind areas. They are furnished with necessary hardware. Clamps are not recommended for hat-shaped covers.

Tray Type H J JA, JB, JC YA YD XC X, X1, XD B BA, BB, BC CA CD P,PB E, E1, ED EB, EC I6

All Covers (Except Peaked and Hat Shaped) Mill Stainless Steel Galvanized 316 HC-( )-H HC-( )-J HC-( )-JA HC-( )-YA HC-( )-YD HC-( )-XB HC-( )-X HC-( )-B HC-( )-BA HC-( )-CA HC-( )-CD HC-( )-PB HC-( )-E HC-( )-EB HC-( )-I6

6HC-( )-H 6HC-( )-J 6HC-( )-JA 6HC-( )-YA 6HC-( )-YD 6HC-( )-XB 6HC-( )-X 6HC-( )-B 6HC-( )-BA 6HC-( )-CA 6HC-( )-CD 6HC-( )-PB 6HC-( )-E 6HC-( )-EB 6HC-( )-I6

Peaked Covers Mill Galvanized

Stainless Steel 316

HC-( )P-( )-H HC-( )P-( )-J HC-( )P-( )-JA HC-( )P-( )-YA HC-( )P-( )-YD HC-( )P-( )-XB HC-( )P-( )-X HC-( )P-( )-B HC-( )P-( )-BA HC-( )P-( )-CA HC-( )P-( )-CD HC-( )P-( )-PB HC-( )P-( )-E HC-( )P-( )-EB HC-( )P-( )-I6

6HC-( )P-( )-H 6HC-( )P-( )-J 6HC-( )P-( )-JA 6HC-( )P-( )-YA 6HC-( )P-( )-YD 6HC-( )P-( )-XB 6HC-( )P-( )-X 6HC-( )P-( )-B 6HC-( )P-( )-BA 6HC-( )P-( )-CA 6HC-( )P-( )-CD 6HC-( )P-( )-PB 6HC-( )P-( )-E 6HC-( )P-( )-EB 6HC-( )P-( )-I6

COVER CLIPS FOR HEFTY TRAY This cover clip is designed to fasten the Hefty Tray covers. Each clip is mill galvanized steel and furnished with a thumb screw to facilitate inverted installation on flanged covers.

Top Flange

Plated Steel

Stainless Steel 316

″ All Others

ECC ECC-E

6ECC 6ECC-E

For more information, please call 604.572.4419 or visit www.superiortray.com

page 51


Saving you Time, Saving you Money, Putting you First!

COVERS AND COVER FASTENERS COVER CLIPS FOR LADDER TRAY

COVER FASTENING SCREWS

These clips fasten the tray covers to Ladder Tray.

All covers may be secured with regular or self tapping sheet metal screws. Superior Tray offers either zinc plated regular screws or #6-20 Phillips pan head steel plated self drilling and self tapping screws.

Tray Type

Plated Steel

Stainless Steel 316

H

VCC

6VCC

J

JCC

6JCC

JA, JB, JC

KCC

6KCC

YA

YACC

6YACC

YD

YDCC

6YDCC

M, MB, MD

MCC

6MCC

X, X1

XCC

6XCC

MC, XB, XC

XBCC

6XBCC

XD

XDCC

6XDCC

Hex HD Self Dr B-55

B-26 Self Tapping Catalog Number

Description

STAND OFF CLIPS Tray Type

Plated Steel

Stainless Steel 316

H, J, M, JA, JB, JC, MB, MD

RCC-J-( )

6RCC-J-( )

YA, MC, X, X1, YD, XB, XC, XD, I6

RCC-X-( )

6RCC-X-( )

BA, BB, CA, PB, PC, E, E1, B, BC, CD, P, PD, EB, EC, ED (except I6)

RCC-E-( )

6 RCC-E-( )

#10 x

″ Self-Drilling Self-Tapping

B-55

#6-20 x

″ Self-Drilling Phillips Pan Head Sheet Metal Screw

B-26

COVER JOINT STRIPS

Note: ( ) = insert height in Inches. Cover stand-off clips provide a means to mount the cover above the tray side rail, allowing side ventilation. Cover stand-off clips are used only with flanged covers and are available in various heights, offering a choice in the amount of open area for side ventilation.

PEAKED COVER BLIND END

Catalog # Example C ( ) P – (prefix) – W – EP – ( ) C ( ) P = Insert peak in inches W = Width EP = End Plate 0 = 1/2″ peak, 1 = 1″ peak, etc. EP – ( ) = Insert degrees if cover has peak in degrees.

Aluminum Steel

Ladder Tray-ASP-VS-(Width) Hefty Tray-ASP-ES-(Width) Ladder Tray-SSP-VS-(Width) Hefty Tray- SSP-ES-(Width)

SUPPORT BLOCKS Cable support blocks are designed for clamping cables. The width and number of holes are made according to the client’s requirement. Blocks are made from composite nonmagnetic material. Each support block is furnished with the required number of non-magnetic threaded studs, complete with nuts and flat washers.

When ordering, indicate tray width, number of cables, conductor size, and voltage as well as exact outside diameter of the cable.

For more information, please call 604.572.4419 or visit www.superiortray.com

page 52


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS HOLD DOWN CLIPS SINGLE HOLD DOWN/EXPANSION CLIPS FOR LADDER TRAY This clip holds flange in trays securely to a lower support channel or bracket and can also be used as an expansion guide with a “W-12” washer (sold separately) placed under the base. 1/2″ hardware is recommended. Side Rail Height 3

Tray Type

Mill Galvanized

H J JA, JB, JC, YA, YD M, MB, MD, X, X1 XB, XC, XD

4 4 6 6

HB-2 JB-2 KB-2 MB-2 XCB-2

Stainless Steel 304 316 4HB-2 6HB-2 4JB-2 6JB-2 4KB-2 6KB-2 4MB-2 6MB-2 4XCB-2 6XCB-2

Single Hold Down/ Expansion Clip for Ladder Tray

SINGLE HOLD DOWN CLIPS FOR HEFTY TRAY This clip holds ladders securely to a lower support channel or bracket. 1/2″ hardware is recommended. Tray Type

Aluminum

All Hefty Tray and Instrument Channel

AHDC-A

Stainless Steel 304 316

Zinc Plated SHDC-A

4HDC-A

6HDC-A

Single Hold Down Clip for Hefty Tray

SINGLE HOLD DOWN CLIPS FOR LADDER TRAY This clip is used to hold all Ladder Tray ladders to a support channel or bracket. Tray Type

Zinc Plated

Ladder Tray 3/8″ Hardware Strut 1/2″ Hardware

SHDC-V SHDC-V1/2

Stainless Steel 304 316 4HDC-V 6HDC-V 4HDC- V1/2 6HDC-V1/2 Single Hold Down Clip for Ladder Tray

DOUBLE HOLD DOWN CLIPS FOR LADDER TRAY Double Hold Down Clips allow two side by side trays to be fastened to the support with one clip and less hardware. 1/2″ hardware is recommended. Top Flange Width 1 1

″ ″ ″

Aluminum

Plated Steel

AHDC-2A AHDC-2CA AHDC-2C

SHDC-2A SHDC-2CA SHDC-2C

Stainless Steel 304 316 4HDC-2A 6HDC-2A 4HDC-2CA 6HDC-2CA 4HDC-2C 6HDC-2C

Note: All dimensions are in inches.

Double Hold Down Clip for Ladder Tray

For more information, please call 604.572.4419 or visit www.superiortray.com

page 53


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS HOLD DOWN/EXPANSION GUIDE FOR HEFTY TRAY

EXPANSION GUIDES GUIDES FOR LADDER Expansion guides are used to secure ladder trays, while guiding the trays when they move during thermal expansion. For expansion guide recommendations, contact the factory. 1/2″ hardware is recommended.

Guide For Ladder Tray

These special heavy duty tray hold down clamps and expansion guides are ideal for fastening tray to C-Channels, such as those found on bridges. They are easy to install and reduce field labor costs since the beam clamp set screw eliminates the need to drill the C-Channel. Hefty Tray

Zinc Plated

Hold Down Clamp

HP-514A-PW

Expansion Guide

HP-514A-PWO

Guide For Hefty Tray

HOLD DOWN CLIP/EXPANSION GUIDE FOR CHANNEL

Stainless Steel 304 316

Tray Type

Aluminum

Zinc Plated

Ladder Tray

AEXG-VL

SEXG-VL

4EXG-VL

6EXG-VL

Hefty Tray

AEXG-EL

SEXG-EL

4EXG-EL

6EXG-EL

These clips hold 4″ and 6″ wide Instrument Channel to a lower support channel or bracket. It can be used as an expansion guide with a W5 washer (sold separately) placed under the base. 3/8″ hardware is recommended. Nylon Pad for Hold Down Clip is available.

GUIDES FOR DOUBLE LADDER These expansion guides are used to retain two side by side Trays, while allowing tray movement due to thermal expansion. 1/2″ hardware is recommended.

Tray Type

Mill Galvan.

Channel

SHDC-GU

Stainless Steel 304 316 4HDC-GU

6HDC-GU

Table: Guides for Double Ladder Tray Type

Aluminum

H

-

Zinc Plated

Stainless Steel 304 316

SG-2H-EX

4G-2H-EX

6G-2H-EX

J, B

AG-2B-EX

SG-2B-EX

4G-2B-EX

6G-2B-EX

JA, JB, JC, BA, BB, BC

AG-2KB-EX

SG-2KB-EX

4G-2KB-EX

6G-2KB-EX

YA, CA

AG-2CA-EX

SG-2CA-EX

4G-2CA-EX

6G-2CA-EX

YD, CD

AG-2CD-EX

SG-2CD-EX

4G-2CD-EX

6G-2CD-EX

M, MB, MD, P, PB, PD

AG-2PB-EX

SG-2PB-EX

4G-2PB-EX

6G-2PB-EX

X, X1, XB, XC, XD, E, E1, EB, EC, ED

AG-2EB-EX

SG-2EB-EX

4G-2EB-EX

6G-2EB-EX

For more information, please call 604.572.4419 or visit www.superiortray.com

page 54


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS HANGER CLIPS HANGER CLIP SET FOR LADDER TRAY The two-piece Ladder hanger is used in conjunction with the 1/2″ hanger rod and eliminates the need for separate horizontal support members and hold down clips of a Ladder Tray. Tray Type

Zinc Plated

Stainless Steel 316

H, J, JA, JB, JC, M, MB, MD

SHC-M

6HC-M

YA

SHC-YA

6HC-YA

XA

SHC-XA

6HC-XA

XB, XC

SHC-XB

6HC-XB

X, X1, XD, YD

SHC-YX

6HC-YX

Hanger Clip Set for Ladder Tray

SINGLE HANGER CLIPS FOR HEFTY TRAY Two inch wide single hanger clips are used with the 1/2″ hanger rod to hold Hefty Tray Ladder firmly in place. Stainless Steel 304 316

Aluminum

Zinc Plated

-

SHC-CB

4HC-CB

6HC-CB

BA, BB, BC

AHC-KB

SHC-KB

4HC-KB

6HC-KB

CA

AHC-CA

SHC-CA

4HC-CA

6HC-CA

CD

-

SHC-CD

4HC-CD

6HC-CD

P, PB, E, EA, E1

AHC-EP

SHC-EP

4HC-EP

6HC-EP

EB, EC, ED

AHC-EB

SHC-EB

4HC-EB

6HC-EB

Tray Type B

Single Hanger Clip for Hefty Tray

DOUBLE HANGER CLIPS Double hanger clips are used in the center of two side by side ladders and held with a 1/2″ hanger rod. The top bolt is included with each unit. Tray Type B

Aluminum

Zinc Plated

Stainless Steel 316

-

SHC-2B

6HC-2B

BA, BB, BC

AHC-2KB

SHC-2KB

6HC-2KB

CA

AHC-2CA

SHC-2CA

6HC-2CA

CD

-

SHC-2CD

6HC-2CD

P, PB

AHC-2P

SHC-2P

6HC-2P

E, EA, E1

AHC-2E

SHC-2E

6HC-2E

EB, EC, ED

AHC-2EB

SHC-2EB

6HC-2EB

Double Hanger Clips

For more information, please call 604.572.4419 or visit www.superiortray.com

page 55


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS SPLICES AND CONNECTORS BOX CONNECTORS FOR TRAY Box connectors terminate Tray at switchgear housings or other metal structures. Tray Type

Aluminum

H

-

Mill Galvanized

Stainless Steel 316

VBC-( )-3

6VBC-( )-3

J

AVBC-( )-4

VBC-( )-4

6VBC-( )-4

JA, JB, JC,YA, YD

AVBC-( )-4

VBC-( )-4

6VBC-( )-4

M, MB, MD, X, XI

AVBC-( )-6

VBC-( )-6

6VBC-( )-6

XB, XC, XD

AVBC-( )-6

VBC-( )-6

6VBC-( )-6

SBC-( )-4

6SBC-( )-4

B

-

BA, BB, BC, CA, CD

ABC-( )-4

SBC-( )-4

6SBC-( )-4

P, PB, PD, E, EI

ABC-( )-6

SBC-( )-6

6SBC-( )-6

EB, EC, ED

ABC-( )-6

SBC-( )-6

6SBC-( )-6

I6

AVBC-( )-6

-

Box Connector

-

( ) = Insert Tray Width

SINGLE CHANNEL CONNECTORS FOR TRAY These connectors take a single channel off a Tray sideways or downward. Hardware is included with the connector. Channel Type

Aluminum

Zinc Plated

G4, G6

ACC-GU

SCC-GU

Stainless Steel 304 316 4CC-GU

WALL PENETRATION SLEEVE

6CC-GU

Single Channel Connector

STRUCTURAL CONNECTOR FOR TRAY Structural connectors terminate Tray on top of concrete floors. Tray hardware is included. 1/2″ hardware is recommended at floor connection.

D

W

L WAL KNESS THIC

24″

Structural Connector Wall Penetration Sleeve

Channel Type All Trays

HDGAF SSC-U

For more information, please call 604.572.4419 or visit www.superiortray.com

Stainless Steel 304 316 4SC-U

6SC-U

page 56


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS HORIZONTAL AND VERTICAL HINGED SPLICES Horizontal and Vertical Hinged Splices offer field flexibility to go around pipes, ducts, and other obstacles that occur during installation. Electrical continuity is maintained by using (AFS-C) bonding jumpers, which are purchased separately. Hinged Splices for Tray come in sets of two. Hinged splices for Instrument Channel come as single units. Horizontal hinged splices require field drilling of the long hinge member and all hinged splices require additional supports, as they are not considered to be full strength mechanical splices. Table: Horizontal Hinged Splices Tray Depth Mill Stainless Aluminum or Type Galvanized Steel 316 3

, 4, 4

(except I6)

AFS-H4

SFS-H4

6FS-H4

AFS-H6

SFS-H6

6FS-H6

I6

AFS-HI6

-

-

G4 Channel

AFS-H4G

SFS-H4G

6FS-H4G

G6 Channel

AFS-H6G

SFS-H6G

6FS-H6G

Horizontal Splices

Table: Vertical Hinged Splices Tray Depth Mill Stainless Aluminum or Type Galvanized Steel 316 3

, 4, 4

AFS-V4

SFS-V4

6FS-V4

(except I6)

AFS-V6

SFS-V6

6FS-V6

I6

AFS-VI6

-

-

G4 Channel

AFS-V4G

SFS-V4G

6FS-V4G

G6 Channel

AFS-V6G

SFS-V6G

6FS-V6G

Vertical Spices

CHANNEL SPLICE PLATES

STEP DOWN SPLICE PLATES

4″ and 6″ wide Instrument Channel systems are supplied with the following wrap around splice plates and hardware. Additional splice plates for field cuts can be ordered by the following catalog numbers.

These are used to connect 6″ tray to 4″ tray. Hardware is included.

Channel Splices Channel Type Width G4 G6

4 6

Step Down Splices

Aluminum

HDGAF

Stainless Steel 316

ASP-Y2

SSP-Y2

6SP-Y2

ASP-X2

SSP-X2

6SP-X2

Channel Type

Aluminum

6″ to 4″

ASP-MH2

6″ to 4

″

ASP-MJA

For more information, please call 604.572.4419 or visit www.superiortray.com

page 57


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS UNIVERSAL SPLICE CONNECTORS

90° SPLICES FOR TRAY AND CHANNEL

These connectors are furnished with the trays. If required for field cuts, these can be purchased separately.

These splices are used for field cut tees if there is no room for bends or fittings. They are also used for attachment to metal enclosures.

Universal Splice Connector

90° Splices for Tray and Channel

Tray Height or Type 3 6, 6

Aluminum

, 4, 4 (except I6)

I6

HDGAF Steel

Stainless Steel 316

Tray Height or Type

ASP-H2

SSP-H2

6SP-H2

3

ASP-M2

SSP-M2

6SP-M2

6, 6

ASP-E2

-

-

, 4, 4

Aluminum

HDGAF Steel

Stainless Steel 316

ASP-4-90

SSP-4-90

6SP-4-90

ASP-6-90

SSP-6-90

6SP-6-90

, G4

, G6

END PLATES EXPANSION JOINT SPLICE PLATES Expansion Splice Plates for tray are designed to allow 1-1/2″ free movement between adjacent straight lengths. When using expansion splices, it is important that the straight run be fixed permanently to its support at the approximate center between expansion joints whenever possible, and that all other points be supported in a manner that the longitudinal expansion is not restricted. Supports should be provided within one foot on each side of an expansion joint to ensure its proper functioning.

Blind End Plates are available for all tray types and are furnished with mounting hardware.

End Plate

Side Rail Height 3 4

Expansion Joint Splice Plate

Aluminum

Mill Galvanized

Stainless Steel 316

-

SEP-( )-3

6EP-( )-3

-

SEP-( )-4

6EP-( )-4

4

AEP-( )-4

SEP-( )-4

6EP-( )-4

6

AEP-( )-6

SEP-( )-6

6EP-( )-6

6

AEP-( )-6

SEP-( )-6

6EP-( )-6

( ) represents Tray Width.

Tray Height or Type

Aluminum

HDGAF Steel

Stainless Steel 316

3

ASP-4-EX

SSP-4-EX

6SP-4-EX

ASP-6-EX

SSP-6-EX

6SP-6-EX

ASP-I6-EX

-

-

6, 6 I6

, 4, 4 , G6

, G4

CHANNEL END PLATES Channel End Plates are similar to regular end plates mentioned above. The part number is: ( )-EP-W-1 ( ) represents Material Type.

Note: All dimensions are in inches. For more information, please call 604.572.4419 or visit www.superiortray.com

page 58


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS HARDWARE FOR SPLICE CONNECTORS

ACCESSORIES

Splice hardware is offered in standard zinc plated steel finish, or in 304 and 316 stainless steel to withstand corrosive attack under many atmospheric conditions.

END DROPOUT This dropout is used at the end of a cable tray system, or to provide a smooth drop off for small cables at any point between the rungs in the ladder system. It is used in pairs, where dropping cable from both directions, or singly, when dropping cable in one direction.

N-100

B-100 Plated Steel

Stainless Steel 304 316

″ Splice Bolt

B-100

B-17

B-100-6S

Splice Nut/Washer Combination

N-100-6S

-

-

Hardware Item

End Dropout

Splice Split Lock Washer

-

W-17

W-17-6S

Splice Nut

-

N-17

N-17-6S

BONDING JUMPERS Bonding jumpers maintain electrical continuity across hinged and expansion splices. The aluminum jumpers are used with oxidation inhibitor under the contact points. The short circuit rating is 2000 Amperes. Hardware is included.

Tray Type

Al

Mill Galvan.

Stainless Steel 304 316

H, J, JA, JB, JC, M, MB, MD, XB, XC

AVD-( )

SVD-( )

4VD-( )

6VD-( )

XD, I6, YA, YD, X, X1

AVD-( )-X

SVD-( )-X

4VD-( )-X

6VD-( )-X

Hefty Tray (except I6)

ABD-( )

SBD-( )

4BD-( )

6BD-( )

Note: Al = Aluminum,

( ) = Insert Tray Width

CONDUIT SIDE TYPE DROPOUT This type of dropout is a bracket used to secure a conduit clamp (not included), to the side rail of the tray, allowing cables to exit the tray into conduit drops to the equipment.

Bonding Jumper Catalog Number: AFS-C

GROUNDING STRAP Material Type: Tin Plated Braided Copper. Length: 12″ Standard. Catalog Number for 600 amp rating: AFS-CT-600 Catalog Number for 1000 amp rating: AFS-CT-1000

Grounding Strap

Conduit Side Type Dropout

Tray Type

Zinc Plated

Stainless Steel 316

Any Tray (except I6)

VDS-U

6VDS-U

For more information, please call 604.572.4419 or visit www.superiortray.com

page 59


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS GROUNDING CONNECTORS

GROUNDING CLAMPS

Type GC Connectors hold a single through cable and a tap cable while separating the ground conductor from the cable tray surface. Note that the bolt head is mounted on the inside wall of the cable tray to avoid damage to the cable insulation. Grounding connectors may be used with aluminum or galvanized steel cable trays. When mounted horizontally, the bolt may be used to replace one of the bolts in a splice plate.

Type GBM Clamps hold a single through cable directly on the cable tray surface.

Conductor

Conductor

Catalog Number

#2 Sol – 2/0 Str

GC 2626 CT

2/0 Sol up to 250 MCM

GC 2929 CT

Catalog Number

#4 Sol – 2/0 Str

GBM 26

2/0 Sol up to 250 MCM

GBM 29

300 to 500 MCM

GBM 34

Mini Trim

MINI TRIM Mini trim can be used as a protective edging to protect cables from sharp surfaces that cables may contact. Mini trim is a vinyl embossed extrusion with a segmented metal core that can be cut with a knife between the metal core segments. It will grip edges from .010″ to .050″ thick, and is supplied in 100 ft. rolls in black. Catalog Number: Mini Trim For more information, please call 604.572.4419 or visit www.superiortray.com

page 60


Saving you Time, Saving you Money, Putting you First!

ACCESSORIES, SPLICES & CONNECTORS CABLE SEPARATORS

SEPARATOR FOR VERTICAL BENDS

Cable separators (divider strips) are available for all tray types in aluminum, mill galvanized and 304 or 316 stainless steel. Separators come in either 3″ or 5″ heights and are slotted at regular intervals for ease of installation without field drilling. Separator Rung Fasteners must be ordered separately for attachment to Tray rungs without drilling.

The following information is required while ordering: 1. Inside or outside bend 2. Degree of bend 3. Radius of bend Example: A3V-VI45-24

Vertical separators must be factory formed to the proper radius needed. Vertical separators can be ordered to the degree of bend or the customer can order all 90° separators and field cut them to the proper degree bends.

SEPARATOR FOR STRAIGHT LENGTHS Standard length is 12 feet. The grouping of slots is designed to fit the hole-pattern of ventilated Tray.

Sep. Height

Aluminum

Mill Galvanized

Stainless Steel 304 316

3

A3S-144

S3S-144

43S-144

63S-144

5

A5S-144

S5S-144

45S-144

65S-144

SEPARATOR FOR HORIZONTAL BENDS Standard length is 6 feet. Each piece is punched and slotted for easy field adjustment to any degree of radius curvature. Sections may be field cut or continued along a straight run.

Sep. Height

Aluminum

Mill Galvanized

3

A3S-HA

S3S-HA

43S-HA

5

A5S- HA

S5S-HA

45S-HA

Sep. Height

Aluminum

Mill Galvanized

Stainless Steel 304 316

3

A3V-( )

S3V-( )

43V-( )

63V-( )

5

A5V-( )

S5V-( )

45V-( )

65V-( )

( ) = Insert Fitting Suffix

SEPARATOR FASTENERS FOR TRAY Separator fasteners allow attachment of separators to Tray rungs without drilling the rungs. These fasteners are required 4 per straight section, 3 per horizontal fitting and 2 per vertical fitting. Rung fasteners are stainless steel.

CABLE SEPARATOR SPLICES

Sep. Height

Aluminum

Mill Galvanized

63S-HA

3

A3SC

A5SC

43SC

63SC

65S-HA

5

S3SC

S5SC

43SC

65SC

Stainless Steel 304 316

Stainless Steel 304 316

Note: Sep. = Cable Separator. All dim ensions are in inches For more information, please call 604.572.4419 or visit www.superiortray.com

page 61


Saving you Time, Saving you Money, Putting you First!

For a quote, please fill in as much information as you can and we will recommend the rest. You may also attach any specification and sketch concerning your request and fax both to Superior Tray at (604) 572-4416 or email us at info@medicofab.com.

REQUESTED INFORMATION Project Name:

Bid Due Date:

Destination:

Ship Date:

Owner: Engineering Firm:

Contact Name:

Address: Tel:

Fax:

Email: □ Purchase

Type of quotation:

□ Budgetary

Cable Tray Application: Who will buy:

When:

Required Information: 1. Type of Cable Tray: □ Ladder Tray: Rung Spacing

□ 9 □ 12 □ 18 □ Hefty Tray: Rung Spacing □ 9 □ 12 □ 18 □ Instrument Channel: □ Solid □ Ventilated □ Center Hung Tray _________________________________ □ Basket Tray _________________________________ □ Special Tray _________________________________

2. Type of Material

3. Width:

□ Aluminum □ Pregalvanized □ HDGAF □ Stainless 316 □ Stainless 304

□ 6″ □ 9″ □ 12″ □ 18″ □ 24″ □ 30″ □ 36″

4. Fitting Radius: 5. NEMA Class 6. CSA Class

□ 12″ □ 24″ □ 36″

_________________________________

_________________________________

7. Further Notes ___________________________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________

For more information, please call 604.572.4419 or visit www.superiortray.com

page 62


Turn static files into dynamic content formats.

Create a flipbook