Type Y510
Fisher Controls
Instruction Manual
Type Y510 Low Pressure Shutoff
September 1974
Form 5016
STANDARD METER SET
BREAKAWAY NIPPLE TYPE Y510
MOBILE HOME
FLEXIBLE CONNECTOR
STOP COCK DWG NO T20445
GAS MAIN
Figure 1. Typical installation of Y510
Install, use, and maintain per Fisher instructions and all applicable federal, state, and local laws and codes. The vent (or vent assembly) on the shutoff must remain unobstructed-check the vent opening after a freezing rain, sleet storm, or heavy snow. Also immediately check the service regulator if appliance lights fail to stay on, gas can be smelled, or any other abnormal situation occurs.
Introduction Type Y510 is used on low pressure gas systems to shutoff gas supply if pressure to the appliances in the building being served drops below the set point of the Y510. The unit will also close if there is a loss or near loss of supply pressure or if a pipeline failure downstream of the Y510 causes a flow which exceeds the Y510 capacity. Inlet pressure must not exceed 1 psig, and the Y510 must never be used as a service regulator.
Installation WARNING Point the vent vertically down on all outdoor
ŠFisher Controls International, Inc., 1974; All Rights Reserved
installations. The installation should be adequately protected from vehicular traffic. Only personnel trained in the proper procedures, codes, standards, etc. should install or service this equipment. Before installing the shutoff, check for damage which might have occured in shipment. Also check for dirt or foreign matter which may have accumulated in the shutoff body or in the pipeline. Apply pipe compound to the male threads of the pipeline and install the Y510 so that flow is in the direction indicated by the arrow cast on the body. The actuator portion of the shutoff is connected to the body with two cap screws (key 18). By loosening these screws, the diaphragm case assembly can be rotated to any position relative to the body. Also, removing cap screws and nuts (key 14 and 15) permits rotating the spring case assembly (key 1) so that the vent can be pointed downward. Replace the unit if water gets into the spring case or the lower casing. Do not install the shutoff in a location where there can be excessive water accumulation, such as directly beneath a down spout.
Vent WARNING All vents should be kept open to permit free flow to atmosphere.
D100702X012
WARNING